background image

Manual

2100-489

Page

17 of 26

OPTIONAL OUTDOOR THERMOSTAT
APPLICATIONS

Since most equipment at the time of manufacture is not
designated for any specific destination of the country and
are installed in areas not approaching the lower outdoor
temperature range, outdoor thermostats are not factory
installed as standard equipment, but are offered as an
option.  There are also different applications for applying
outdoor thermostats.  The set point of either type of outdoor
thermostat application is variable with geographic region
and sizing of the heating equipment to the individual
structure.  Utilization of the heating Application Data, and
the heat loss calculation of the building are useful in
determining the correct set points.

Temperature and Humidity Controller #8403-060, along
with the Outdoor Sensor option Part #8403-061, can be
used to:

• Limit minimum outdoor temperature for cooling option.

• Limit minimum outdoor temperature for heat pump option.

• Inhibit electric heat operation for heat pumps above

selected outdoor temperature.

FIGURE 11

COMPRESSOR CUTOFF THERMOSTAT WIRING

4 & 10KW  1 PH  —  6 & 9KW  3 PH

Thus, not requiring the optional compressor cut-off
thermostat or the electric heat cut-off thermostat option.

OPTIONAL COMPRESSOR CUTOFF
THERMOSTAT  (See Figures 11 and 12)

Heat pump compressor operation at outdoor temperatures
below 0°F are neither desirable nor advantageous in term
of efficiency.  An outdoor thermostat can be applied to
take the mechanical heating (compressor) off line, and
send the (compressor) signal to energize electric heat in
its place (to make electric heat first stage heating).  This
can also be applied to bank the quantity of available
electric heat.  For example:  A heat pump operates with
10KW second stage heat – once the outdoor thermostat
has switched then operates 15KW without the compressor
as first stage heat.

NOTE: The additional LAB (low ambient bypass) relay is
required to prevent heater operation during low
temperature cooling operation.

FIGURE 12

COMPRESSOR CUTOFF THERMOSTAT WIRING

15KW  1 PH & 3 PH

Содержание WH303

Страница 1: ...els WH303 WH363 WALL MOUNTED PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Manual No 2100 489 Supersedes NEW File Volume III Tab 17 Date 01 18 08 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1...

Страница 2: ...6 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Mounting Instructions 10 Figure 4 Electric Heat Clearance 11 Figure 5 Attaching Top Outlet to Unit 12 Figure 6 Top Outlet Model Mounted 12 Figure 7 Wall...

Страница 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...supply and return ducts These instructions explain the recommended method to install the air cooled self contained unit and the electrical wiring connections to the unit These instructions and any in...

Страница 5: ...U T B A U T B A U T B A U T B A U T B 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 5 1 5 2 6 0 0 2 1 5 1 4 5 0...

Страница 6: ...BASIC UNIT NOMINAL l e d o M h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 0 3 H W 6 3 H W 0 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8...

Страница 7: ...8 8 3 5 3 5 6 2 2 5 0 6 0 6 0 3 0 6 6 6 0 1 6 0 1 0 1 0 1 0 1 Z 0 B 0 0 B 3 6 3 H W 6 0 B 3 9 0 B 5 5 1 B 3 8 0 2 0 3 2 1 1 1 1 0 2 8 3 7 4 0 5 5 2 0 4 0 5 0 5 0 1 8 8 8 0 1 0 1 0 1 0 1 Z 0 C 0 0 C 3...

Страница 8: ...the noise transmission to a minimum A 1 4 inch clearance to combustible material for the first three 3 feet of duct attached to the outlet air frame is required See Wall Mounting Instructions and Fig...

Страница 9: ...pped secured to the back of the unit on the right side Attached to unit front right of supply flange for shipping 6 Position unit in opening and secure with 5 16 lag bolts use 7 8 inch diameter flat w...

Страница 10: ...Manual 2100 489 Page 10 of 26 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...AT CLEARANCE WARNING A minimum of 1 4 clearance must be maintained between the supply air duct and combustible materials This is required for the fist three 3 feet of ducting It is important to insure...

Страница 12: ...Manual 2100 489 Page 12 of 26 FIGURE 5 ATTACHING TOP OUTLET AIRFRAMES TO UNIT FIGURE 6 UNIT WITH TOP OUTLET MOUNTED UNDER OVERHANG...

Страница 13: ...0 489 Page 13 of 26 FIGURE 7 WALL MOUNTING INSTRUCTIONS FIGURE 8 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT...

Страница 14: ...Manual 2100 489 Page 14 of 26 FIGURE 9 COMMON WALL MOUNTING INSTALLATIONS...

Страница 15: ...TAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptabl...

Страница 16: ...W VOLTAGE WIRING TABLE 5 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g u a g 4...

Страница 17: ...oor temperature for heat pump option Inhibit electric heat operation for heat pumps above selected outdoor temperature FIGURE 11 COMPRESSOR CUTOFF THERMOSTAT WIRING 4 10KW 1 PH 6 9KW 3 PH Thus not req...

Страница 18: ...thermostat This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from t...

Страница 19: ...2 5 H T t a e h e g a t s 2 l o o c e g a t s 2 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 0 6 0 3 0 4 8 5 4 4 0 2 1 1 t a e h e g a t s 3 l o o c e...

Страница 20: ...d outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation START UP HEATIN...

Страница 21: ...mper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to sh...

Страница 22: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Страница 23: ...0 0 4 0 1 4 0 2 4 0 3 4 0 4 4 0 5 4 0 6 4 0 7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5...

Страница 24: ...filter REMOVAL OF FAN SHROUD 1 Disconnect all power to unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding fan shroud to condenser and bot...

Страница 25: ...2 7 8 4 3 2 8 8 2 5 2 0 9 9 6 2 2 9 9 8 2 4 9 8 0 3 6 9 8 2 3 9 9 0 5 3 3 6 3 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 9 6 4 0 2 1 7 8 1 2 3 7 4 3 2 5 7 0 5 2 7 7 4 6 2 8 7 0 8 2...

Страница 26: ...t a l P f f O k n a l B X X X X X X 3 D A F B r e p m a D r i A h s e r F c i r t e m o r a B X X X X X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X 3 V R C t s u a h x E h t...

Отзывы: