Manual    2100-374
Page      6

INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the unit being installed.

4. The unit is suitable for 0 inch clearance from the

unit, and from the supply and return air ducts.

MOUNTING THE UNIT

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 3.

2. Locate and mark lag bolt locations and bottom

mounting bracket location, if desired.  See Figure 3.

3. Mount bottom mounting bracket, if used.

4. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of
the back.

5. Position unit in opening and secure with 5/16 lag

bolts.  Use 5/16”  flat washers on the lag bolts.

6. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

7. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

8. On side by side installations, maintain a minimum

of 20 inches clearance on right side of unit to allow
access to control panel and heaters, and to allow
proper airflow to the outdoor coil.  Additional
clearance may be required to meet local or national
codes.

WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required.  If this is the
case, the unit serial plate will so indicate.  All models
are suitable only for connection with copper wire.  Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions must be
adhered to.
  Refer to the National Electrical code
(NEC) for complete current carrying capacity data on
the various insulation grades of wiring material.  All
wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C
copper) for all models, including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.  To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out.  This tab
will now line up with the slot in the door.  When shut a
padlock may be placed through the hole in the tab
preventing entry.

Содержание WH242D

Страница 1: ...ONS WALL MOUNTED PACKAGE HEAT PUMP Model WH242D Manual 2100 374D Supersedes 2100 374C File Volume III Tab 17 Date 09 01 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as p...

Страница 2: ...ontrol Board 15 Figure 11 Fan Blade Setting 18 Figure 12 Circuit Diagram H P Cooling Mode 21 Figure 13 Circuit Diagram H P Dehumidification 21 Start Up Important Installer Note 13 Crankcase Heaters 13...

Страница 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Страница 4: ...he equipment covered in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely assembled and charged All internal wiring is com...

Страница 5: ...i n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C D D 2 4 2 H W 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2...

Страница 6: ...three feet of duct attached to the outlet air frame is required See Pages Wall Mounting Instructions and Figure 3 for further details Ducts through the walls must be insulated and all joints taped or...

Страница 7: ...bly and sliding the brackets apart to the required width and retightening the four 4 screws FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is...

Страница 8: ...airflow to the outdoor coil Additional clearance may be required to meet local or national codes WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR...

Страница 9: ...Manual 2100 374 Page 7 FIGURE 3 MOUNTINGINSTRUCTIONS MIS 353...

Страница 10: ...Manual 2100 374 Page 8 FIGURE 5 WALLMOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 549 MIS 548 FIGURE 4 WALLMOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...Manual 2100 374 Page 9 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Страница 12: ...plication of these parts FIGURE 7 WHxxxDx HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000 ENERGY MONITOR FULL TIME DEHUMIDIFICATION FACTORY JUMPER H600A MIS 1561 8403 032 BARD CS2000 8403 038 HONEY...

Страница 13: ...wn in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts FIGURE 8 WHxxxDx...

Страница 14: ...1 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h C l a u n a M r o o t u A 9 4 0 3 0 4 8 0 8 3 3 9 F 1 t a e h e g a t s 3 l o o c e g a t s 2 e l b a m m a r g o r P y a D 7 r e...

Страница 15: ...OOLING Circuit R Y makes at thermostat pulling in compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation...

Страница 16: ...erative to match the correct pressure curve to the unit by model number DEFROST CYCLE The defrost cycle is controlled by temperature and time on the solid state heat pump control See Figure 10 When th...

Страница 17: ...frost operation of the unit without waiting for the outdoor ambient to fall into the defrost region By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost senso...

Страница 18: ...c e c a l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w...

Страница 19: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Страница 20: ...s 3 Remove screws 9 holding fan shroud to condenser and bottom 4 Unwire condenser fan motor 5 Slide complete motor fan blade and shroud assembly out the left side of the unit 6 Service motor fan as ne...

Страница 21: ...2 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6 7 9 2 2 7 7 2 4 2 9 7 6 5 2 0 8 1 7 2 1 8 6 8 2 3 8 2 0 3 4 8 8 1 3 6 8 6 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L...

Страница 22: ...n a l B r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o...

Страница 23: ...V 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL INDOOR COIL REHEAT COIL 4 WAY VALVE CHECK VALVE CAPILLARY DRAIN ASSY 3 WAY VALVE COMPRESSOR TXV 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL FIGURE 12 BARD MFG...

Отзывы: