INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at both
sides.  A bottom mounting bracket is provided for ease
of installation, but is not required.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the unit
without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected to

insure that they are capable of carrying the weight of the
unit being installed.

4. The unit is suitable for 0 inch clearance from the unit,

and from the supply and return air ducts.

MOUNTING THE UNIT

1. Two holes for the supply and return air openings must

be cut through the wall as shown in Figure 3.

2. Locate and mark lag bolt locations and bottom

mounting bracket location, if desired.  See Figure 3.

3. Mount bottom mounting bracket, if used.

4. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of the
back.

5. Position unit in opening and secure with 5/16 lag bolts.

Use 5/16”  flat washers on the lag bolts.

6. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

7. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and screwed
or welded to the structural wall itself (depending upon
wall construction).  Be sure to observe required
clearance if combustible wall.

8. On side by side installations, maintain a minimum of 20

inches clearance on right side of unit to allow access to
control panel and heaters, and to allow proper airflow to
the outdoor coil.  Additional clearance may be required
to meet local or national codes.

Содержание WH241D

Страница 1: ...LATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMP MODELS WH241D Manual 2100 356 File Volume III Tab 17 Date 10 01 99 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as pl...

Страница 2: ...ircuit Diagram H P Cooling Mode 20 Figure 12 Circuit Diagram H P Dehumidification 20 Start Up 12 Important Installer Note 12 Crankcase Heaters 12 Service Hints 12 Sequence of Operation 12 Pressure Ser...

Страница 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contrac...

Страница 4: ...codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air These instructions explain the recommended method to install the...

Страница 5: ...n r u t e R E F G I J K L M N O P Q R S T A B C D D 1 4 2 H W 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6...

Страница 6: ...energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure available for duct design Design the duct work according to methods given by the Air Conditioning Cont...

Страница 7: ...kets apart to the required width and retightening the four 4 screws FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with a fresh ai...

Страница 8: ...as shown in Figure 3 2 Locate and mark lag bolt locations and bottom mounting bracket location if desired See Figure 3 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend...

Страница 9: ...Manual 2100 356 Page 7 FIGURE 3 MOUNTING INSTRUCTIONS MIS 353...

Страница 10: ...Manual 2100 356 Page 8 FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 549 MIS 548 FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...Manual 2100 356 Page 9 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 550...

Страница 12: ...unit rating plate for wire sizing information and maximum fuse or HACR type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must...

Страница 13: ...E SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5...

Страница 14: ...motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation HEATING A 24V solenoid coil on reversing va...

Страница 15: ...compressor will be de energized by the evaporator defrost sensor until the coil temperature rises above 57 degrees PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units...

Страница 16: ...Manual 2100 356 Page 14 FIGURE 9 DEFROST CONTROL BOARD MIS 1174...

Страница 17: ...h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F g n i l o o c n u r t o n s e o d t p e c x e g n i t a e h r o t s o r f e d g n i r u d e...

Страница 18: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Страница 19: ...in a suction line temperature 6 from compressor as shown in Table 7 FIGURE 10 The above suction line temperatures are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across...

Страница 20: ...Outdoor Coil F Low Side Pressure 2 PSIG High Side Pressure 5 PSIG Tables are based upon rated CFM airflow across the evaporator coil and should be found under section titled Refrigerant Charge elsewhe...

Страница 21: ...B r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r...

Страница 22: ...OIL 4 WAY VALVE CHECK VALVE CAPILLARY DRAIN ASS Y 3 WAY VALVE COMPRESSOR TXV 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL FIGURE 12 BARD MFG HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM INDOOR COIL RE...