Bard WH241D Скачать руководство пользователя страница 14

Manual    2100-356
Page      12

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor coil
with a dish detergent.

CRANKCASE HEATERS

WH241 units are provided with compressor crankcase heat.

These models have an insertion well-type heater located in
the lower section of the compressor housing.  This is a self-
regulating type heater that draws only enough power to
maintain the compressor at a safe temperature.

Some form of crankcase heat is essential to prevent liquid
refrigerant from migrating to the compressor causing oil
pump out on compressor start up and possible valve failure.

The decal in Figure 8 is affixed to all outdoor units detailing
start up procedure.  

This is very important.  Please read

carefully.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system which shortens equipment service life as well as
increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch.  Turn thermostat off, then on,
to reset the high pressure switch..

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure they

are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full and

unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING – 

Circuit R-Y makes at thermostat pulling in

compressor contactor, starting the compressor and outdoor
motor. The G (indoor motor) circuit is automatically
completed on any call for cooling operation or can be
energized by manual fan switch on subbase for constant air
circulation.

HEATING –  

A 24V solenoid coil on reversing valve

controls heating cycle operation.  Two thermostat options,
one allowing "Auto" changeover from cycle to cycle and the
other constantly energizing solenoid coil during heating

IMPORTANT

THESE PROCEDURES MUST BE
FOLLOWED AT INITIAL START UP
AND AT ANY TIME POWER HAS
BEEN REMOVED FOR 12 HOURS
OR LONGER.

TO PREVENT COMPRESSOR DAMAGE WHICH
MAY RESULT FROM THE PRESENCE OF LIQUID
REFRIGERANT IN THE COMPRESSOR CRANK-
CASE:

1. MAKE CERTAIN THE ROOM THERMOSTAT IS IN

THE “OFF” POSITION. (THE COMPRESSOR IS
NOT TO OPERATE.)

2. APPLY POWER BY CLOSING THE SYSTEM

DISCONNECT SWITCH.  THIS ENERGIZES THE
COMPRESSOR HEATER WHICH EVAPORATES
THE LIQUID REFRIGERANT IN THE CRANK-
CASE.

3. ALLOW 4 HOURS OR 60 MINUTES PER POUND

OF REFRIGERANT IN THE SYSTEM AS NOTED
ON THE UNIT RATING PLATE, WHICHEVER IS
GREATER.

4. AFTER PROPERLY ELAPSED TIME THE

THERMOSTAT MAY BE SET TO OPERATE THE
COMPRESSOR.

5. EXCEPT AS REQUIRED FOR SAFETY WHILE

SERVICING  — 

DO NOT OPEN SYSTEM

DISCONNECT SWITCH.

7961-061

FIGURE 8

season, and thus eliminating pressure equalization noise
except during defrost, are to be used.  On "Auto" option a
circuit is completed from R-W1 and R-Y on each heating
"on" cycle, energizing reversing valve solenoid and pulling
in compressor contactor starting compressor and outdoor
motor.  R-G also make starting indoor blower motor.  Heat
pump heating cycle now in operation.  The second option
has no "Auto" changeover position, but instead energizes
the reversing valve solenoid constantly whenever the system
switch on subbase is placed in "Heat" position, the "B"
terminal being constantly energized from R.  A Thermostat
demand for heat completes R-Y circuit, pulling in
compressor contactor starting compressor and outdoor
motor.  R-G also make starting indoor blower motor.

Содержание WH241D

Страница 1: ...LATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMP MODELS WH241D Manual 2100 356 File Volume III Tab 17 Date 10 01 99 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as pl...

Страница 2: ...ircuit Diagram H P Cooling Mode 20 Figure 12 Circuit Diagram H P Dehumidification 20 Start Up 12 Important Installer Note 12 Crankcase Heaters 12 Service Hints 12 Sequence of Operation 12 Pressure Ser...

Страница 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contrac...

Страница 4: ...codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air These instructions explain the recommended method to install the...

Страница 5: ...n r u t e R E F G I J K L M N O P Q R S T A B C D D 1 4 2 H W 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6...

Страница 6: ...energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure available for duct design Design the duct work according to methods given by the Air Conditioning Cont...

Страница 7: ...kets apart to the required width and retightening the four 4 screws FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with a fresh ai...

Страница 8: ...as shown in Figure 3 2 Locate and mark lag bolt locations and bottom mounting bracket location if desired See Figure 3 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend...

Страница 9: ...Manual 2100 356 Page 7 FIGURE 3 MOUNTING INSTRUCTIONS MIS 353...

Страница 10: ...Manual 2100 356 Page 8 FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 549 MIS 548 FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...Manual 2100 356 Page 9 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 550...

Страница 12: ...unit rating plate for wire sizing information and maximum fuse or HACR type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must...

Страница 13: ...E SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5...

Страница 14: ...motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation HEATING A 24V solenoid coil on reversing va...

Страница 15: ...compressor will be de energized by the evaporator defrost sensor until the coil temperature rises above 57 degrees PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units...

Страница 16: ...Manual 2100 356 Page 14 FIGURE 9 DEFROST CONTROL BOARD MIS 1174...

Страница 17: ...h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F g n i l o o c n u r t o n s e o d t p e c x e g n i t a e h r o t s o r f e d g n i r u d e...

Страница 18: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Страница 19: ...in a suction line temperature 6 from compressor as shown in Table 7 FIGURE 10 The above suction line temperatures are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across...

Страница 20: ...Outdoor Coil F Low Side Pressure 2 PSIG High Side Pressure 5 PSIG Tables are based upon rated CFM airflow across the evaporator coil and should be found under section titled Refrigerant Charge elsewhe...

Страница 21: ...B r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r...

Страница 22: ...OIL 4 WAY VALVE CHECK VALVE CAPILLARY DRAIN ASS Y 3 WAY VALVE COMPRESSOR TXV 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL FIGURE 12 BARD MFG HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM INDOOR COIL RE...

Отзывы: