background image

Manual 2100-502A
Page

6 of 15

High Pressure Switch and Lockout Sequence

• If the high pressure switch opens, the compressor

contactor will de-energize immediately.  The
lockout time in the CCM will go into a soft
lockout and stay locked out until the high
pressure switch closes and the delay on break has
expired.

• If the high pressure switch opens again during

the same operating cycle the CCM will go into a
manual lockout condition.

• Recycling the wall thermostat resets the manual

lockout.

Low Pressure Switch, Bypass and Lockout
Sequence  (Optional)

• If the low pressure switch opens for more than

120 seconds the compressor contactor will de-
energize and the CCM will go into soft lockout.

• Regardless of the state of the low pressure switch

the compressor contactor will reenergize after
the delay on break time has expired.

• If the low pressure switch remains open, or opens

again for longer than 120 seconds, the CCM will
go into a manual lockout and the alarm relay
circuit will energize.

• Recycling the wall thermostat resets the manual

lockout.

NOTE:

Both high and low pressure switch controls
are inherently automatic reset devices.  The
high pressure switch opens at 425 and closes
at 325 psig, and the low pressure switch opens
at 14 and closes at 30 psig.  The lockout
features, both soft and manual, are a function
of the Compressor Control Module.

Alarm Relay Output

• Alarm terminal on Compressor Control Module

is 24V AC output connection for applications
where signal is desired.  This terminal is
powered whenever compressor is in manual
lockout due to high pressure or low pressure
sequences as described.

SECTION 4  •  TURNING OFF FURNACE IN
AN EMERGENCY

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a three phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the “&” signal is present at the phase monitor
and phases are correct, the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

3.3 MANUAL FAN (CONTINUOUS AIRFLOW)

OPERATION

If wall thermostat is set to MANUAL (ON) position to
operate comfort air blower continuously to provide air
circulation throughout the building, the blower will
operate at a level that is lower than cooling or heating
airflows.  This permits the air to circulate as desired but
helps keep the operating noise level down as well a
conserving energy.

During a call for cooling, the blower automatically
shifts up to cooling speed, and remains there until 60
seconds after thermostat is satisfied then drops back to
heating speed.

         WARNING

Have a qualified installer, service agency
or gas supplier teach you location and
operation of gas and electrical shut-off
devices.  Ask them any questions you have
about this section.  If you don’t turn off your
furnace in an emergency damage, injury or
death could result.

Содержание WG3S Series

Страница 1: ... 502 File Vol I Tab 20 Date 09 05 08 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Thank you for reading these safety statements Please read on so you will know how to maintain your air conditioner gas furnace for years of dependable service WARNING Do not use this air conditioner gas furnace if any part has been under water Immediately call a qualified se...

Страница 2: ...4 Section 7 Air Conditioning Start Up Procedure Crankcase Heater 14 Section 8 Ventilation Options 15 Section 9 Replacement Parts 15 Section 10 Outdoor Coil 15 Figures Figure 1 Typical Gas Piping 8 Figure 2 Step by Step Instructions on Lighting Burners 11 Figure 3 Filter Locations 13 Figure 4 Periodic Inspections 13 Location of Access Panels Figure 5 Start Up Procedures 14 Manufactured under the fo...

Страница 3: ...on products can contain aldehydes and carbon monoxide SECTION 1 RATING PLATE INFORMATION Record the manufacturer s name unit model number and serial number below These are your furnace rating plate Record installation date which is important for warranty purposes YOUR FURNACE INFORMATION Furnace Type ________________________________________________________________ Manufacturer s Name______________...

Страница 4: ...your unit A fire could occur resulting in damage injury or death WARNING Never store or use anything near or on your furnace that can produce vapors that are corrosive to gas fired furnaces Vapors from products containing chlorines fluorines bromines and iodines can cause vent system or heat exchanger failure Examples of such products are spray or aerosol containers detergents bleaches cat litter ...

Страница 5: ...es The inducer will continue to run for 30 seconds and the comfort air blower will continue to run for 2 1 2 minutes 3 2 BASIC OPERATION COOLING CYCLE On a call for cool the compressor and condenser fan will start immediately and the comfort air blower will start 7 seconds later on cooling speed Note Some models may be equipped with optional Low Ambient Control that will cycle the condenser fan mo...

Страница 6: ...arm Relay Output Alarm terminal on Compressor Control Module is 24V AC output connection for applications where signal is desired This terminal is powered whenever compressor is in manual lockout due to high pressure or low pressure sequences as described SECTION 4 TURNING OFF FURNACE IN AN EMERGENCY PHASE MONITOR All units with three phase scroll compressors are equipped with a three phase line m...

Страница 7: ...Meter or Propane LP Gas Tank Normally natural gas is ON when you turn shut off parallel to gas pipe Gas is OFF when you turn shut off 90 from gas pipe Some valves require a wrench or other tools 2 ELECTRICAL SHUT OFF DEVICES In an emergency you may not be able to reach both of your electrical shut off devices Therefore you must know how to turn off electricity using either one of them Here are two...

Страница 8: ...Manual 2100 502A Page 8 of 15 FIGURE 1 TYPICAL GAS PIPING ...

Страница 9: ... condition indicates lack of airflow through furnace ACTION a Make sure air filter is clean and installed correctly b Check that registers and return air grilles are open and unobstructed c If condition continues call your local qualified service technician or gas supplier 4 Possible Emergency While furnace is operating you smell unfamiliar odors that go away when furnace is off ACTION a Turn ther...

Страница 10: ...to light main burners 2 Do not touch or turn on any electrical switch 3 Do not use any phone in your building 4 Immediately call your gas supplier from a neighbor s phone Follow gas supplier s instructions 5 If you cannot reach your gas supplier call fire department 6 B LUBRICATION REQUIREMENTS The main blower motor outdoor fan motor and the induced draft blower motor are permanently lubricated an...

Страница 11: ...Manual 2100 502A Page 11 of 15 FIGURE 2 START UP PROCEDURE ...

Страница 12: ...d the structure 5 Inspect for any obvious signs of deterioration of the furnace 6 Periodic examinations of the vent terminal should also be conducted by the owner on a regular basis preferably every month but at least every two months during the heating season 7 Check the entire vent terminal for any blockage If any debris is present remove it 8 If unit is vertically vented inspect vent system ann...

Страница 13: ...Manual 2100 502A Page 13 of 15 FIGURE 3 FILTER LOCATIONS FIGURE 4 PERIODIC INSPECTIONS ...

Страница 14: ...ankcase heater It is secured on the exterior of the compressor at its base and is controlled internally within the control panel to be energized anytime the compressor is off Some form of crankcase heat is essential to prevent liquid refrigerant from migrating to the compressor causing oil pump out on compressor start up and possible valve failure due to compressing a liquid The decal in Figure 5 ...

Страница 15: ...of the vent option door to cover the air inlet openings which eliminates outside air from entering the unit The optional Commercial Room Ventilator CRV allows up to 50 outside fresh air to be introduced to the building and includes a built in exhaust damper The CRV complies with ASHRAE Standard 62 1 Ventilation for Acceptable Indoor Air Quality The optional EIFM Series Economizer allows for non me...

Отзывы: