Manual
2100-486D
Page
17 of 37
ELECTRICAL GROUNDING
When installed, the furnace must be electrically
grounded in accordance with local codes or in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70, or Canadian Electrical Code,
CSA22.1, latest edition. Use a copper wire from green
ground wire on the furnace to a grounded connection in
the service panel or a properly driven and electrically
grounded ground rod. See Table 1 for proper ground
wire size.
FIELD INSTALLED EQUIPMENT
Wiring to be done in the field between the furnace and
devices not attached to the furnace, or between separate
devices which are field installed and located, shall
conform with the temperature limitation for Type T
wire {63 degrees F rise (36 degrees C)} when installed
in accordance with the manufacturer’s instructions.
INSTALLATION OF FLEXIBLE CONDUIT
THROUGH RETURN AIR OPENING
NOTE: To allow proper clearance between the
control panel and any vent options, 90°
conduit fittings must be used on the back of
the control panel.
INSTALLING CONDUIT (See Figure 10.)
1. Remove conduit access panel if required to gain
access to area behind control panel.
2. Remove low voltage and high voltage knockouts
located in rear of control panel.
3. Run low voltage conduit through 7/8 bushing located
in conduit entrance plate and secure to low voltage
opening in rear of control panel.
4. Run high voltage conduit through 1-3/4 bushing
located in conduit entrance plate and secure to high
voltage opening in rear of control panel.
5. Replace conduit access panel if required to complete
installation.
6. Seal around conduit in conduit entrance plate.
WARNING
Failure to provide a proper electrical ground
could result in electric shock or fire.
14. WIRING – MAIN POWER
Refer to unit rating plate for wire sizing information
and maximum fuse or circuit breaker size. Each
outdoor unit is marked with a “Minimum Circuit
Ampacity”. This means that the field wiring used must
be sized to carry that amount of current. All models are
suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked - “
Use
Copper Conductors Only
”. These instructions
must be
adhered to. Refer to the National Electrical Code
(NEC) for complete current carrying capacity data on
the various insulation grades of wiring material. All
wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models.
The unit rating plate lists a “Maximum Fuse” or circuit
breaker that is to be used with the equipment. The
correct size must be used for proper circuit protection.
See “Start Up” section for important information on
three phase scroll compressor start ups.
WARNING
For your personal safety, turn off electric
power at service entrance panel before
making any electrical connections. Failure to
do so could result in electric shock or fire.
WARNING
Failure to provide an electrical power supply
shut off means could result in electric shock
or fire.
Содержание WF0501-A
Страница 12: ...Manual 2100 486D Page 12 of 37 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS...
Страница 13: ...Manual 2100 486D Page 13 of 37 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Страница 19: ...Manual 2100 486D Page 19 of 37 FIGURE 11 LOW VOLTAGE WIRING...
Страница 20: ...Manual 2100 486D Page 20 of 37 FIGURE 12 GAS PIPE CONNECTION...
Страница 28: ...Manual 2100 486D Page 28 of 37 24 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...
Страница 34: ...Manual 2100 486D Page 34 of 37 230 208 60 1...
Страница 35: ...Manual 2100 486D Page 35 of 37 115 60 1...
Страница 36: ...Manual 2100 486D Page 36 of 37 115 60 1...
Страница 37: ...Manual 2100 486D Page 37 of 37 230 208 60 1...