COMPRESSOR CONTROL MODULE

The compressor control module is standard on all
models covered by this manual.  The compressor control
module is an anti-short cycle/lockout timer with high
and low pressure switch monitoring and alarm relay
output.

Adjustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to
the unit, the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch and low pressure switch is closed, the compressor
contactor is energized.  Upon shutdown, the delay on
break timer starts and prevents restart until the delay on
break and delay on make periods have expired.

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle, the unit will go
into 

manual lockout

 condition and the alarm relay circuit

will energize.  Recycling the wall thermostat resets the
manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds, the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever the compressor is locked out due to
HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner unit model.  The lockout features,
both soft and manual, are a function of the
Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.
See Table 3.

Содержание W3RV1

Страница 1: ...LL MOUNTED VARIABLE CAPACITY PACKAGE AIR CONDITIONERS MODELS W3RV1 W3LV1 W5RV1 W5LV1 W6RV1 W6LV1 Manual 2100 538A Supersedes 2100 538 File Volume III Tab 16 Date 08 02 10 Bard Manufacturing Company In...

Страница 2: ...nt Control Options 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 C...

Страница 3: ...gn for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshir...

Страница 4: ...ards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in acc...

Страница 5: ...FG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity...

Страница 6: ...ght of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to sk...

Страница 7: ...urn Air Opening Built In Optional Electrical Entrances Top Rain Flashing Bottom Installation Bracket Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on W6RV W6LV models 2 Option...

Страница 8: ...CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CA...

Страница 9: ...D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 RETURN AIR FOAM AIR SEAL OPENING 29 Wall Opening and Hole Location View NOTES Supply Opening SUPPLY AIR Return Opening IT IS RECOMMENDED THAT A BEAD...

Страница 10: ...bustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheati...

Страница 11: ...0 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C...

Страница 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 13: ...formation on three phase scroll compressor start ups See Table 4 for Electrical Specifications WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All eq...

Страница 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 15: ...mpact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rota...

Страница 16: ...ked ON as long as the unit is in the Test Mode 2 While in Test Mode 2 the compressor will NOT modulate but will be locked on at 100 to maintain the occupied room setpoint During the Test Mode 2 if the...

Страница 17: ...ll be set at normal outdoor airflow Below 55 degrees the outdoor fan will modulate to maintain a 300 psi head pressure This will act as a low ambient fan cycling control The output may go to zero outp...

Страница 18: ...s expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize Recycling the wall...

Страница 19: ...harge resulting in a liquid subcooling as shown in Table 2 If charge is in doubt reclaim and recharge to factory nameplate charge Values are at 100 capacity TABLE 2 REFRIGERANTCHARGE l e d o M d e t a...

Страница 20: ...1 9 6 4 0 3 1 8 9 4 2 3 1 0 3 5 5 3 1 5 6 5 e e S e t o N 2 F 7 6 0 8 C 4 9 1 7 6 2 e d i S w o L e d i S h g i H 7 3 1 4 6 3 6 3 1 3 8 3 6 3 1 4 0 4 6 3 1 7 2 4 7 3 1 3 5 4 8 3 1 1 8 4 9 3 1 1 1 5 1...

Страница 21: ...A N 6 A N A N 0 1 A N A N A N A N A N 0 1 A N A N 0 1 A N A N A N Z 0 S 1 V L 3 W 1 V R 3 W 6 0 S 9 0 S 3 0 6 8 0 2 0 3 2 0 2 2 3 0 5 0 0 2 1 1 1 9 1 7 3 6 4 0 3 0 4 0 5 0 1 8 8 0 1 0 1 0 1 A N A N A...

Страница 22: ...7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 2 1 4 4 1 0 5 9 0 4 5 1 5 2 6 0 5 2 1 5 0 4 5 0 0 4 8 3 2 6 3 0 0 2...

Страница 23: ...n o i t p i r c s e D 5 1 C M C e s a h P 1 V 0 3 2 t i K t r a t S X X 3 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X 3 P O B e t a l P f f O k n a l B X 5 D A F B d r a...

Отзывы: