TABLE 5
Wall Thermostats
Part Number
Predominate Features
8403-060
(1120-445)
3 stage Cool; 3 stage Heat; Electronic Programmable/Non-Programmable; HP or Conventional; Auto or Manual
changeover; Dehumidification Output
CS9B-THOA
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover;
Humidity Sensor w/ dehumidification; Motion Sensor w/Intelligent Learning Control; BACnet-compatible
CS9B-THOCA
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover;
Humidity Sensor w/ dehumidification; CO
2
Sensor; Motion Sensor w/Intelligent Learning Control; BACnet-compatible
CS9BE-THOA
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover; Humidity
Sensor w/ dehumidification; Motion Sensor w/Intelligent Learning Control; BACnet-compatible; Ethernet-compatible
CS9BE-THOCA
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover;
Humidity Sensor w/dehumidification; CO
2
Sensor; Motion Sensor w/Intelligent Learning Control; BACnet-compatible;
Ethernet-compatible
8403-089
(T4 Pro)
1 stage Cool, 1 stage Heat – Heat Pump; 1 stage Cool, 1 stage Heat – Conventional; Programmable/Non-
Programmable Electronic; Auto or Manual changeover
8403-090
(T6 Pro)
2 stage Cool, 3 stage Heat – Heat Pump; 2 stage Cool, 2 stage Heat – Conventional; Programmable/Non-
Programmable Electronic; Auto or Manual changeover
8403-091
1 stage Cool, 1 stage Heat; Non-Programmable; FEMA use
8403-092
(T6 Pro Wi-Fi)
2 stage Cool, 3 stage Heat – Heat Pump; 2 stage Cool, 2 stage Heat – Conventional; Programmable/Non-
Programmable Electronic; Auto or Manual changeover; Wi-Fi
controller. The DDC controls option contains the
following installed components:
Dirty Filter Switch Indicator (DFS)
The switch is adjustable and measures pressure drop
across the unit filter surface. When pressure drop is
higher than the switch setting, NO contacts are provided
to indicate the filter needs to be serviced. Refer to page
34 for instructions on making switch adjustments.
Discharge Air Sensor
The discharge air sensor provides a temperature reading
of the supply air leaving the unit. The sensor is a 10K
OHM @ 77°F measuring device. It is installed in the
supply airstream in the heater bracket.
Airflow Switch
The airflow switch measures the pressure differential
between the blower inlet and outlet. It is located directly
above the blower partition. Relay contacts (NO) are
provided for the DDC controls option that indicates the
indoor blower assembly needs to be serviced.
Compressor Current Sensor
The compressor current sensor indicates when the
compressor is operational by measuring amp draw. It is
located inside the unit control panel. Relay contacts (NO)
are provided to indicate the compressor is not operating
See Table 4 for low voltage connections for DDC control.
Standard Units
Units w/
Economizers
Fan Only
Energize G
Energize G
1st Stage
Cooling Mode/
Balanced Climate
Energize Y1, G
Energize Y1, G
2nd Stage
Cooling Mode
Energize Y2 to
overide Balanced
Climate mode
when Y1-Y2
jumper is
removed
Energize Y1, Y2, G
1st Stage Heating
Energize B/W1
Energize B/W1
2nd Stage Heating
(if employed)
Energize B/W1, W2
Energize B/W1, W2
Ventilation
Energize A
Energize A
Dehumidification
(if employed)
Energize D
Energize D
TABLE 4
Low Voltage Connections for DDC Control