TABLE 16
W48G4 Indoor Blower Performance @ 230 AND 460 VOLTS
Recommended W48G cooling airflow range at rated 1450 CFM @ .20 ESP (WC) is 1150 - 1680 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
SG-5, RG-5, non-ducted application adjustment
– Reduce airflow by 170 CFM for SG-5 and RG-5 installations
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
125,000 BTU Input
113,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1185
1501
1668
1788
0.1
1118
1445
1616
1734
0.2
1042
1384
1560
1678
1678
0.3
958
1317
1500
1618
1618
0.4
866
1245
1436
1557
1811
1557
0.5
766
1167
1368
1492
1754
1492
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
100,000 BTU Input
90,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1185
1501
1668
1788
0.1
1118
1445
1616
1734
1734
0.2
1042
1384
1560
1678
1678
0.3
958
1317
1500
1618
1870
1618
0.4
866
1245
1436
1557
1811
1557
0.5
766
1167
1368
1492
1754
1492
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
75,000 BTU Input
68,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
1185
1501
1668
1788
0.1
1118
1445
1616
1734
0.2
1042
1384
1560
1678
1678
0.3
958
1317
1500
1618
1870
1618
0.4
866
1245
1436
1557
1811
1557
0.5
766
1167
1368
1492
1754
1492
Содержание W24G4
Страница 14: ...Manual 2100 721B Page 14 of 54 FIGURE 2B Mounting Instructions for W42G W48G and W60G...
Страница 16: ...Manual 2100 721B Page 16 of 54 FIGURE 4 Wall Mounting Instructions FIGURE 5 Wall Mounting Instructions...
Страница 17: ...Manual 2100 721B Page 17 of 54 FIGURE 6 Common Wall Mounting Installations...
Страница 27: ...Manual 2100 721B Page 27 of 54 FIGURE 14 Gas Pipe Connection W24G W36G W42G W60G...