Manual 2100-631
Page
30 of 53
21. STANDARD ORIFICE SIZING AND
HIGH ALTITUDE DERATE
This furnace is shipped with fixed gas orifices for use
with Natural Gas and sized for 1000 BTU/cubic foot
gas. Make sure actual gas input does not exceed rating
plate input. You may need to change orifices to get
correct gas input. Whether you do or not depends on
input, and your gas heat value at standard conditions
and elevation. Consult your local gas supplier for gas
heat value and any special derating requirements. See
Section 20 for more information.
At higher altitudes, the density of the air is reduced.
Therefore, for proper combustion, the quantity of gas
burned in the furnace must also be reduced. This
is called derating. This unit must be derated when
installed at altitudes greater than 6,000 feet above
sea level. A high altitude pressure switch must also be
installed for operation above 6,000 feet. High altitude
pressure switch kit number 8620-189 is designed for
this application.
TABLE 7
NATURAL GAS DERATE CAPACITIES
FOR ALL MODELS
W**G Rated
Input
Sea Level
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
41,000
45,000
40,500
45,000
39,204
43,560
37,908
42,120
36,612
40,680
35,640
39,600
34,992
38,880
34,182
37,980
33,696
37,440
33,048
36,720
32,643
36,270
32,076
35,640
61,000
68,000
60,750
67,500
58,806
65,340
56,862
63,180
54,918
61,020
53,460
59,400
52,488
58,320
51,273
56,970
50,544
56,160
49,572
55,080
48,965
54,405
48,114
53,460
75,000
81,000
75,000
81,000
72,600
78,408
70,200
75,816
67,800
73,224
66,000
71,280
64,800
69,984
63,300
68,364
62,400
67,392
61,200
66,096
60,450
65,286
59,400
64,152
90,000
100,000
90,000
100,000
87,120
96,800
84,240
93,600
81,360
90,400
79,200
88,000
77,760
86,400
75,960
84,400
74,880
83,200
73,440
81,600
72,540
80,600
71,280
79,200
113,000
125,000
112,500
125,000
108,900
121,000
105,300
117,000
101,700
113,000
99,000
110,000
97,200
108,000
94,950
105,500
93,600
104,000
91,800
102,000
90,675
100,750
89,100
99,000
It is the installer’s responsibility to see that the
furnace input rate is adjusted properly. Derating
must be achieved by reducing the size of the main
burner orifices. Derating the furnace by adjusting the
manifold pressure lower than the range specified in
the Section 19, “Manifold Pressure Adjustment” is
considered to be an improper procedure.
Above 6,000 feet elevation orifice changes are
required, and capacity reductions are a function of
altitude impact and orifice change. Pressure switch
change is required above 6,000 feet elevation. For
Natural Gas see the Altitude Table 7 below and the
Orifice Tables 8 and 8A on following pages.
Содержание W24G3DA
Страница 13: ...Manual 2100 631 Page 13 of 53 FIGURE 2A MOUNTING INSTRUCTIONS FOR W42G W48G AND W60G ...
Страница 15: ...Manual 2100 631 Page 15 of 53 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS ...
Страница 16: ...Manual 2100 631 Page 16 of 53 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS ...
Страница 26: ...Manual 2100 631 Page 26 of 53 FIGURE 12 GAS PIPE CONNECTION W24G W36G W42G W60G ...
Страница 36: ...Manual 2100 631 Page 36 of 53 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL ...