![Bard W24G3DA Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/bard/w24g3da/w24g3da_installation-instructions-manual_4061101029.webp)
Manual 2100-631
Page
29 of 53
Natural Gas Input Rate
Natural gas heating value (BTU/cu. ft.) can vary
significantly. Before starting natural gas input check,
obtain gas heating value at your location from local
supplier. You will need a stopwatch to measure actual
gas input.
1. Gas supply pressure must be between 5 and 7
inches W.C. for natural gas.
2. Turn off all other gas appliances. You may leave
pilots on.
3. Start furnace following “Operating Instructions” on
front door.
4. Let furnace warm up for 6 minutes.
5. Locate gas meter. Determine which dial has the
least cubic feet of gas and how many cubic feet
per revolution it represents. This is usually one-
half, one or two cubic feet per revolution.
6. With stopwatch, measure time it takes to consume
two cubic feet of gas.
• If dial is one-half cubic foot per revolution,
measure time for four revolutions.
• If dial is one cubic foot per revolution,
measure time for two revolutions.
• If dial is two cubic feet per revolution,
measure time for one revolution.
7. Divide this time by two. This gives average time
for one cubic foot of gas to flow through meter.
Example: If it took 58 seconds for two cubic feet
to flow, it would take 29 seconds for one cubic foot
to flow.
8. Calculate gas input using this formula:
Gas Heating Value (BTU/cu. ft.)
x 3,600 sec/hr
Gas input =
= BTU/hour
Time (Seconds for one
cubic foot of gas)
Example:
Assume it took 29 seconds for one cubic foot of
gas to flow and heating value of 1,000 BTU/cu. ft.
1,000 x 3,600
Gas input =
= 124,138 BTU
29
If you left no other pilots on, this is the furnace gas
input.
9. If you left water heater, dryer or range pilots on,
allow for them in calculating correct furnace gas
input. A quick way is to allow 1,000 BTU per hour
for a water heater, 500 BTU per hour for dryer and
500 BTU per hour for each range burner pilot.
Example:
If you left gas water heater, dryer, two range burner
pilots and one oven pilot on, allow:
Water heater pilot
1,000 BTU per hour
Dryer pilot
500 BTU per hour
2 range burner pilots
1,000 BTU per hour
1 range oven pilot
500 BTU per hour
3,000 BTU per hour
Subtracting 3,000 BTU per hour from 124,138
BTU per hour measured above equals 121,138
BTU per hour. This would be the correct furnace
gas input after allowing for pilots left on.
10. Manifold pressure may be adjusted within the
range of 3.2 inches W.C. to 3.8 inches W.C. to
get rated input ± 2 percent. See Section 19,
“Manifold Pressure Adjustment”. If you cannot
get rated input with manifold pressure within the
allowable range, you must change orifices.
Propane (LP) Gas Input Rate
1. Make sure you have proper main burner orifices.
2. Gas supply pressure must be between 11 and 13
inches W.C. for propane (LP) gas.
3. Start furnace following “Operating Instructions” on
front door.
4. Let furnace warm up for 6 minutes.
5. Adjust manifold pressure to 10.0 W.C. ± 0.3
inches W.C. See Section 19, “Manifold Pressure
Adjustment”.
WARNING
Propane (LP) gas installations do not have
gas meters to double check input rate.
Measure manifold pressure adjustment with
an accurate manometer. Failure to accurately
adjust pressure could cause heat exchanger
failure, asphyxiation, fire or explosion,
resulting in damage, injury or death.
WARNING
Do not set Propane (LP) manifold pressure
at 11.0 inches W.C. It could cause heat
exchanger failure.
Содержание W24G3DA
Страница 13: ...Manual 2100 631 Page 13 of 53 FIGURE 2A MOUNTING INSTRUCTIONS FOR W42G W48G AND W60G ...
Страница 15: ...Manual 2100 631 Page 15 of 53 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS ...
Страница 16: ...Manual 2100 631 Page 16 of 53 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS ...
Страница 26: ...Manual 2100 631 Page 26 of 53 FIGURE 12 GAS PIPE CONNECTION W24G W36G W42G W60G ...
Страница 36: ...Manual 2100 631 Page 36 of 53 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL ...