Bard W24G3-A Скачать руководство пользователя страница 19

Manual 2100-630A
Page 

19 of 49

12.  VENT RESIZING INSTRUCTIONS

When an existing furnace is removed from a venting 
system servicing other appliances, the venting system 
is likely to be too large to properly vent the remaining 
attached appliances.

The following steps shall be followed with each of 
the appliances remaining connected to the common 
venting system, placed in operation one at a time 
while the other appliances remaining connected to the 
common venting system are not in operation.

1.  Seal any unused openings in the venting system.

2.  Inspect the venting system for proper size and 

horizontal pitch, as required in the National 
Fuel Gas code, ANSI Z223.1 or the CAN/CGA 
B149 Installation Codes and these instructions.  
Determine that there is no blockage or restriction, 
leakage, corrosion and other deficiencies which 
could cause an unsafe condition.

3.  In so far as is practical, close all building doors 

and windows and all doors between the space 
in which the appliance(s) connected to the 
venting system are located and other spaces of 
the building.  Turn on clothes dryers and any 
appliances not connected to the venting system.  
Turn on any exhaust fans, such as range hoods 
and bathroom exhausts, so they will operate 
at maximum speed.  Do not operate a summer 
exhaust fan.  Close fireplace dampers.

4.  Follow the lighting instructions.  Place the 

appliance being inspected in operation.  Adjust 
thermostat so appliance shall operate continuously. 

5.  Test for draft hood equipped appliance spillage at 

the draft hood relief opening after 5 minutes of 
main burner operation.  Use the flame of a match 
or candle.

6.  After it has been determined that each appliance 

connected to the venting system properly vents 
when tested as outlined above, return doors, 
windows, exhaust fans, fireplace dampers and 
any other gas-burning appliances to their previous 
conditions of use.

7.  If improper venting is observed during any of the 

above tests, the venting system must be corrected.

13.  FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in 
the service panel.  

If the unit is equipped with a fresh air damper 
assembly, the assembly is shipped already attached 
to the unit.  The damper blade is locked in the 
closed position.  To allow the damper to operate, the 
maximum and minimum blade position stops must be 
installed (see Figure 9).

All capacity, efficiency and cost of operation 
information as required for Department of Energy  
“Energyguide” Fact Sheets is based upon the fresh 
air blank-off plate in place and is recommended for 
maximum energy efficiency.

The blank-off plate is available upon request from the 
factory and is installed in place of the fresh air damper 
shipped with each unit.

One of several other ventilation options may be 
installed.  Refer to model number and/or supplemental 
installation instructions.

14.  CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at 
the top of the unit down to the unit base.  There are 
openings in the unit base for the drain hose to pass 
through.  In the event the drain hose is connected to 
a drain system of some type, it must be an open or 
vented type system to assure proper drainage. 

FIGURE 9

Fresh Air Damper

Содержание W24G3-A

Страница 1: ...THESE INSTRUCTIONS AND THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR THE INSTALLATION LOCATION IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS FAIL...

Страница 2: ...w Voltage Wiring 21 17 Thermostats 21 18 Gas Supply and Piping 26 19 Manifold Pressure Adjustment 27 20 Checking Gas Input Rate 27 21 Standard Orifice Sizing and High Altitude Derate 29 22 Conversion...

Страница 3: ...5 Figure 18 Top View of Gas Control 36 Figure 19 Sequence of Operation Electronic Blower Control 38 Figure 20 Furnace Control Board and Blower Control 39 Figure 21 Fan Blade 48 Figure 22 Low NOx Inser...

Страница 4: ...exdale Boulevard Rexdale Ontario Canada M9W 1R3 Telephone 416 447 4044 BARD MANUFACTURING COMPANY INC BRYAN OHIO 43506 USA These publications can help when installing the furnace They can usually be f...

Страница 5: ...omizer Fully Modulating E WGJIFM 3 WGJIFM 5 Energy Recovery Ventilator 230 Volt R WGERV A3B WGERV A5B Energy Recovery Ventilator 460 Volt R WGERV C3C WGERV C5C MODEL Wall Mount CONTROL OPTIONS See tab...

Страница 6: ...Always used with compressor control module CCM which is included See Note LPC Low pressure control is auto reset Always used with compressor control module CCM which is included See Note LAC Low ambie...

Страница 7: ...8 8 8 4 9 Branch Circuit Selection Current 12 8 8 3 5 1 14 1 9 0 5 6 16 7 10 5 5 8 Lock Rotor Amps 64 64 58 58 28 77 77 71 71 38 79 79 73 73 38 Compressor Type Scroll Scroll Scroll Scroll Scroll Scro...

Страница 8: ...6 7 8 Branch Circuit Selection Current 19 9 13 1 6 1 21 8 13 8 6 3 26 3 16 6 7 8 Lock Rotor Amps 109 109 83 83 41 117 117 83 83 41 134 134 110 110 52 Compressor Type Scroll Scroll Scroll Scroll Scrol...

Страница 9: ...TION ENTRANCES FRONT CIRCUIT BREAKER MIS 3239 HIGH VOLTAGE ENTRANCES FRONT DOOR FILTER SERVICE DOOR UNIT A B C D E F G H I J K L M N O P Q R W24G W30G W36G 7 88 27 88 13 88 24 25 40 25 63 81 63 27 38...

Страница 10: ...cording to methods given by the Air Conditioning Contractors of America ACCA When duct runs through unheated spaces it should be insulated with a minimum of one inch of insulation Use insulation with...

Страница 11: ...enough to carry the weight of the unit without transmitting any unit vibration 3 Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the install...

Страница 12: ...PTIONAL 12 FLANGE SCREWS UNIT SUPPORT 1 MIN NECCESSARY NO CLEARANCE SUPPLY AIR DUCT RETURN AIR DUCT CONTROL PANEL VESTIBULE DOOR WALL STRUCTURE OUTSIDE 1 CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT...

Страница 13: ...Manual 2100 630A Page 13 of 49 FIGURE 2A Mounting Instructions for W42G W48G and W60G...

Страница 14: ...of one 1 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first three 3 feet of ducting It is important to insure that the one 1 inch m...

Страница 15: ...Manual 2100 630A Page 15 of 49 FIGURE 4 Wall Mounting Instructions FIGURE 5 Wall Mounting Instructions...

Страница 16: ...Manual 2100 630A Page 16 of 49 FIGURE 6 Common Wall Mounting Installations...

Страница 17: ...d the condenser inlet and discharge openings DO NOT install the unit in a location that will permit discharged air from the condenser to recirculate to the condenser inlet TABLE 2 Minimum Installation...

Страница 18: ...e kit includes a stainless steel transition drain tee silicone sealant and drain tubing If unit is installed with vertical vent kit annually inspect the vent system and drain Replace any portion of th...

Страница 19: ...nce spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle 6 After it has been determined that each appliance connected to the venting sy...

Страница 20: ...a proper electrical ground could result in electric shock or fire 15 WIRING MAIN POWER Refer to unit rating plate for wire sizing information and maximum fuse or circuit breaker size Each outdoor unit...

Страница 21: ...240V tap For 208V operation reconnect from 240V to 208V tap The acceptable operating voltage range for the 240V and 208V taps are TABLE 3 Thermostat Wire Size FIGURE 10 Installation of Flexible Condui...

Страница 22: ...ltage Wiring No Ventilation Package 1 G Y Unit Control Panel G Block W1 E G W1 1 C A W2 E Y2 O F C O B R W2 Thermostat Subbase 2 1 2 SET SWITCH ON THERMOSTAT TO GAS OIL CONFIGURE THERMOSTAT FOR HEAT C...

Страница 23: ...THERMOSTAT TO GAS OIL CONFIGURE THERMOSTAT FOR HEAT COOL RED MUST INSTALL JUMPER FOR 8403 057 OR OTHER THERMOSTAT THAT DOES NOT Low Voltage Wiring G COMMERCIAL ROOM VENTILATOR POWER RED MUST BE CONFIG...

Страница 24: ...03 060 L Y1 2 Y W1 R CONFIGURE THERMOSTAT FOR HEAT COOL Y1 1 WIRES Y2 G W1 E A C C A 1 PURPLE Unit 24V R 1 Thermostat PLUG Thermostat Subbase O B G W2 1 R 3 F E ORANGE W2 Part 8403 058 Y2 Unit Control...

Страница 25: ...Manual 2100 630A Page 25 of 49 FIGURE 14 Gas Pipe Connection W24G W36G W42G W60G...

Страница 26: ...ch pipe connection and watching for bubbles If a leak is found make the necessary repairs immediately and repeat the above test The furnace must be isolated from the gas supply piping system by closin...

Страница 27: ...t manifold pressure by turning gas control regulator adjusting screw clockwise to increase pressure or turning counterclockwise to decrease pressure Manifold pressure must be within allowable range as...

Страница 28: ...eft on this is the furnace gas input 9 If the water heater dryer or range pilots were left on allow for them in calculating correct furnace gas input A quick way is to allow 1 000 BTU per hour for a w...

Страница 29: ...34 992 38 880 34 182 37 980 33 696 37 440 33 048 36 720 32 643 36 270 32 076 35 640 61 000 68 000 60 750 67 500 58 806 65 340 56 862 63 180 54 918 61 020 53 460 59 400 52 488 58 320 51 273 56 970 50 5...

Страница 30: ...hange and Orifice Change Based on BTU Content 8 001 to 10 000 Requires Pressure Switch Change and Orifice Change Based on BTU Content 22250 BTU Per Burner 700 749 2 60 2 50 2 45 750 799 2 50 2 45 2 40...

Страница 31: ...stalled orifice size 2 30 orifices are shipped with the unit for field installed optional 10 derate Optional 10 Field Converted Derate Gas Heat Value BTU Cu Ft Up to 6 000 No Changes Except for BTU Co...

Страница 32: ...2 from furnace Locate thermometer tip in center of plenum to insure proper temperature measurement 6 Place second thermometer in return air duct approximately 2 from furnace Locate thermometer tip in...

Страница 33: ...igh Pressure Switch and Lockout Sequence Standard Feature If the high pressure switch opens the compressor contactor will de energize immediately The lockout timer will go into a soft lockout and stay...

Страница 34: ...make DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of delay on break setting 0 5 minute 30 seconds DOB 123 second DOM 1 0 minute 60 seconds DOB 126 second DOM 2 0...

Страница 35: ...llow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appli...

Страница 36: ...the upper tubes of the heat exchanger Check the exterior of the heat exchanger and the interior flue gas passages for any evidence of deterioration due to corrosion cracking or other causes If signs...

Страница 37: ...sure the supply and return air flange sleeves or duct work are securely fastened to unit and physically sound d Supply and return grilles must be open and free from obstructions e Inspect to make sur...

Страница 38: ...Heat fan on delay timing begins When timing is complete the circulating fan is energized at heat speed Thermostat ends call for heat Ignition system is de energized and gas valve closes Combustion air...

Страница 39: ...heating modes to check for proper blower operation If it is desirable to have both HEAT COOL blower motor speed at the same speed install a jumper wire between HEAT and COOL terminals of the integrate...

Страница 40: ...Input 81 000 BTU Input High Medium Low High Medium Low High Medium Low 0 1 820 1260 1060 1060 870 0 2 950 770 1200 1010 1200 1010 0 3 880 700 1120 1120 940 0 4 790 1030 1030 860 0 5 910 710 950 0 6 8...

Страница 41: ...igh Medium Low 0 1 1000 1260 1060 1260 1060 0 2 1160 950 1370 1200 1010 1200 1010 0 3 1080 880 1290 1120 940 1120 940 0 4 1150 990 1190 1030 1190 1030 860 0 5 1050 910 1090 950 1090 950 0 6 940 980 98...

Страница 42: ...h Medium Low 0 1 1220 1000 1260 1060 1260 1060 0 2 1160 950 1370 1200 1010 1200 1010 0 3 1250 1080 1290 1120 940 1120 940 0 4 1150 990 1190 1030 1190 1030 860 0 5 1050 1090 950 1090 950 0 6 940 980 98...

Страница 43: ...880 1510 1510 1090 0 3 1400 1760 1460 1460 0 4 1480 1290 1670 1340 1670 1340 0 5 1390 1560 1240 1560 1240 0 6 1270 1430 1130 1430 1130 ESP Inches H2 O COOLING MODE MANUAL FAN and HEATING MODE Wet Coil...

Страница 44: ...0 1450 1880 1510 1510 1110 0 3 1600 1400 1760 1460 1460 1090 0 4 1480 1290 1670 1340 1670 1340 0 5 1390 1560 1240 1560 1240 0 6 1270 1430 1430 1130 ESP Inches H2 O COOLING MODE MANUAL FAN and HEATING...

Страница 45: ...0 2 1710 1450 1880 1510 1510 1110 0 3 1600 1400 1760 1460 1460 1090 0 4 1480 1670 1340 1670 1340 0 5 1390 1560 1240 1560 1240 0 6 1430 1430 1130 ESP Inches H2 O COOLING MODE MANUAL FAN and HEATING MOD...

Страница 46: ...uation the inducer will operate for the 30 second postpurge and the comfort air blower will operate for the selected off delay If on Manual Fan operation the comfort air blower will continue to operat...

Страница 47: ...ow Side High Side 115 279 122 301 127 324 134 349 139 374 143 400 148 426 151 453 154 482 157 512 159 542 161 574 162 608 Low side pressure 4 PSIG High side pressure 10 PSIG Tables based upon rated CF...

Страница 48: ...tion and malfunction of the burner system FIGURE 22 Low NOx Insert 35 R 410A REFRIGERANT CHARGE This unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI ca...

Страница 49: ...4085 381 W30G3 A 4085 161 4085 162 W30G3 B 4085 259 4085 260 W30G3 C 4085 382 4085 383 W36G3 A 4085 161 4085 162 W36G3 B 4085 259 4085 260 W36G3 C 4085 382 4085 383 W42G3 A 4085 161 4085 162 W42G3 B 4...

Отзывы: