background image

Manual 2100-737A 

Page 

24 of 25

TROUBLESHOOTING GE ECM

TM

 MOTORS

CAUTION:

Disconnect power from unit before removing or 
replacing connectors, or servicing motor.  To avoid 
electric shock from the motor’s capacitors, disconnect 
power and wait at least 5 minutes before opening 
motor.

Symptom

 

Cause/Procedure

Motor rocks slightly 

• 

This is normal start-up for ECM

when starting

Motor won’t start 

• 

Check blower turns by hand

• No movement 

• Check power at motor

 

• Check low voltage (24 Vac R to C) at motor

 

• Check low voltage connections

 

  (G, Y, W, R, C) at motor

 

• Check for unseated pins in connectors on  

 

   motor harness

 

• Test with a temporary jumper between R - G

 

• Check motor for tight shaft

 

• Perform motor/control replacement check

 • 

Perform Moisture Check

• Motor rocks,  

• Check for loose or compliant motor mount

  but won’t start 

• Make sure blower wheel is tight on shaft

 

• Perform motor/control replacement check

Motor oscillates up 

• It is normal for motor to oscillate with no 

load 

& down while being 

  on shaft

tested off of blower

Motor starts, but
runs erratically

• Varies up and down 

• Check line voltage for variation or “sag”

  or intermittent 

• Check low voltage connections

 

  (G, Y, W, R, C) at motor, unseated pins in 

 

  motor harness connectors

 

• Check “Bk” for erratic CFM command (in 

 

   variable-speed applications)

 

• Check out system controls, Thermostat

 • 

Perform Moisture Check

• “Hunts” or “puffs” at 

• Does removing panel or filter reduce 

  high CFM (speed) 

  “puffing”?

 

 - Reduce restriction

 

 - Reduce max airflow

• Stays at low CFM 

• Check low voltage (Thermostat) wires and

  despite system call 

  connections

  for cool or heat CFM 

• Verify fan is not in delay mode; wait until 

 

   delay complete

 

• “R” missing/not connected at motor

 

• Perform motor/control replacement check

• Stays at high CFM 

• “R” missing/not connected at motor

 

• Is fan in delay mode? - wait until delay time

 

  complete

 

• Perform motor/control replacement check

• Blower won’t shut off 

• Current leakage from controls into G, Y or W?

 

  Check for Triac switched thermostat or solid-

 

  state relay

Excessive noise

 

• Determine if it’s air noise, cabinet, duct or

 

  motor noise; interview customer, if necessary

• Air noise 

• High static creating high blower speed?

 

 - Is airflow set properly?

 

 - Does removing filter cause blower to slow

 

   down?  Check filter 

 

 - Use low-pressure drop filter

 

 - Check/correct duct restrictions

Symptom

 

Cause/Procedure

• Noisy blower or cabinet

 • 

Check for loose blower housing, panels, etc.

 

• High static creating high blower speed?

 

  - Check for air whistling through seams in

 

     ducts, cabinets or panels

 

  - Check for cabinet/duct deformation

• “Hunts” or “puffs” at

 • 

Does removing panel or filter reduce

   high CFM (speed)

 

   “puffing”?

 

  - Reduce restriction

 

  - Reduce max. airflow

Evidence of Moisture

• Motor failure or  

• Replace motor and 

Perform Moisture Check

  malfunction has occurred
  

and moisture is present

• Evidence of moisture 

 

• 

Perform Moisture Check

  present inside air mover

Do

 

Don’t

• Check out motor, controls,

 • 

Automatically assume the motor is bad.

  wiring and connections
  thoroughly before replacing
  motor
• Orient connectors down so  • Locate connectors above 7 and 4 o’clock
  water can’t get in 

   positions

 - Install “drip loops”
• Use authorized motor and 

• Replace one motor or control model # with

  model #’s for replacement     another (unless an authorized replacement)

• Keep static pressure to a  

• Use high pressure drop filters some have 

½"

  

minimum: 

   H20 drop!

 - Recommend high 

• Use restricted returns

   efficiency, low static filters

 - Recommend keeping filters

   clean.

 - Design ductwork for min.

   static, max. comfort
 - Look for and recommend
   ductwork improvement,
   where necessary

• Size the equipment wisely 

• Oversize system, then compensate with low

 

    airflow

• Check orientation before 

• Plug in power connector backwards

  inserting motor connectors  • Force plugs 

Moisture Check

• Connectors are oriented “down” (or as recommended by equipment
  manufacturer)
• Arrange harness with “drip loop” under motor

• Is condensate drain plugged?

• Check for low airflow (too much latent capacity)

• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet

Comfort Check

• Check proper airflow settings

• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM

• Thermostat in bad location?

Содержание T60H2-A

Страница 1: ...unted Packaged Heat Pump Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 737A Supersedes 2100 737 Date 5 14 21 T60H2 A T60H2 B T60H2 C Page 1 of 25 ...

Страница 2: ...ations 3 Wall Mount General Information 4 Heat Pump Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions 6 Wall Mounting Information 6 Mounting the Unit 6 Placement 6 Clearances Required 6 Minimum Clearances 6 Wiring Main Power 12 Wiring Low Voltage Wiring 12 Optional Outdoor Thermostat Applications 13 Opt...

Страница 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone ...

Страница 4: ...d installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Condi...

Страница 5: ...r factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1 throwaway filter is standard with each unit The filter slides into position making it easy to service This...

Страница 6: ...lashing to wall and caulk across entire length of top See Figure 3 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side t...

Страница 7: ...2 13 A Cond Air Inlet Electrical Entrances Optional Side Wall Mounting Brackets Built In Location Shipping Return Air Opening Supply Air Opening Top Rain Flashing Bottom Installation Bracket Back View M L O E R S S S S S T 44 N Q P B FIGURE 2 Unit Dimensions All dimensions are in inches Dimensional drawings are not to scale Model Width Depth Height Supply Return A B C B E F G I J K L M N O P Q R S...

Страница 8: ...9 3 4 32 12 5 1 2 2 29 OPENING 1 Return Opening IT IS RECOMMENDED THAT A BEAD OF SUPPLY AIR NOTES TOP FLASHING AT TIME OF INSTALLATION RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER MIS 416 F TOP WALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED WALL STRUCTURE FROM COMBUSTABLE 1 4 CLEARANCE ON ALL MATERIALS HEATER ACCESS PANEL FOAM AIR SEAL Right Side View Wall O...

Страница 9: ...rials This is required for the first 3ʹ of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES ...

Страница 10: ...AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME...

Страница 11: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Страница 12: ...at is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bottom le...

Страница 13: ...the correct set points NOTE The additional LAB low ambient bypass relay is required to prevent heater operation during low temperature cooling operation OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 8 9 Heat pump compressor operation at outdoor temperatures below 0 F are neither desirable nor advantageous in term of efficiency An outdoor thermostat can be applied to take the mechanical heating...

Страница 14: ...tat This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the thermostat on start up coming off a night set back condition or someone increasing the thermostat set point NOTE Some programmable thermostats do have a built in time delay for pulling in second stage hea...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out of ...

Страница 16: ...MONITOR All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a f...

Страница 17: ...temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle the heat pump control will restore the system to heating operation automatically after 8 minutes The heat pump defrost control board has an option of 30 60 o...

Страница 18: ... as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor from short cycling conditions The board s LED will have a fast blink rate when in the compressor time delay In some instances it is helpful to the service technician to override or speed up this timing...

Страница 19: ... Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heating only Temperature sensor or heat pump control defective Disconnect temperature sensor from board and jumper across SPEEDUP terminals and SEN JMP t...

Страница 20: ...9 16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102 0 5570 11 0 122089 27 0 37652 65 0 13474 103 0 5446 10 0 118108 28 0 36583 66 0 13137 104 0 5326 9 0 114272 29 0 35548 67 0 12810 105 0 5208 8 0 110575 30 0 34545 68 0 12492 106 0 50...

Страница 21: ...by testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge t...

Страница 22: ...ize Minimum Circuit Ampacity Maximum Circuit Exterior Fuse or Circuit Breaker Field Power Wire Size Ground WIre Size Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C T60H2 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2 1 or 2 1 or 3 43 69 95 95 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 43 43 43 43 26 52 52 52 52 50 50 50 50 30 60 60 60 60 8 8 8 8 10 6 6 6 6 10 10 10 1...

Страница 23: ...ble filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires wiring modification consult Wiring Diagram and unplug and leave disconnected the insulated male female connector connecting together the Gray Orange wires located near the 24V terminal block enclosure CFM output on Cooling or E...

Страница 24: ...f it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed ...

Страница 25: ...site side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from the motor Verify with a standard ohmmeter that the resistance from each motor lead in the motor plug just removed to the motor shell is 100K ohms Refer to Figure 25 Measure to unpainted motor end plat...

Отзывы: