TABLE 5
Indoor Blower Performance – CFM (0.00" - 0.50" H
2
0)
NOTE:
These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the
same rate of indoor airflow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.
Maximum ESP (inches WC) shown is with 2" thick disposable filter.
Blower only CFM is the total air being circulated during continuous fan mode. Airflow remains constant.
Blower only CFM reduces during continuous fan mode. Requires wiring modification; consult Wiring Diagram and unplug and leave
disconnected the insulated male/female connector connecting together the Gray & Orange wires located near the 24V terminal block
enclosure.
CFM output on Cooling or Electric Heat.
Model
Rated
ESP
Maximum
ESP
Blower Only
Except for
CRVMP
Vent Options
Blower Only
For CRVMP
Vent Options
Cooling
& Heat Pump
Electric
Heat
T60H
.20
.50
1650
850
1650
1650