TROUBLESHOOTING GE ECM

TM

 MOTORS

CAUTION:

Disconnect power from unit before removing or 
replacing connectors, or servicing motor.  To avoid 
electric shock from the motor’s capacitors, disconnect 
power and wait at least 5 minutes before opening 
motor.

Symptom

 

Cause/Procedure

Motor rocks slightly 

• 

This is normal start-up for ECM

when starting

Motor won’t start 

• 

Check blower turns by hand

• No movement 

• Check power at motor

 

• Check low voltage (24 Vac R to C) at motor

 

• Check low voltage connections

 

  (G, Y, W, R, C) at motor

 

• Check for unseated pins in connectors on  

 

   motor harness

 

• Test with a temporary jumper between R - G

 

• Check motor for tight shaft

 

• Perform motor/control replacement check

 • 

Perform Moisture Check

• Motor rocks,  

• Check for loose or compliant motor mount

  but won’t start 

• Make sure blower wheel is tight on shaft

 

• Perform motor/control replacement check

Motor oscillates up 

• It is normal for motor to oscillate with no 

load 

& down while being 

  on shaft

tested off of blower

Motor starts, but

runs erratically

• Varies up and down 

• Check line voltage for variation or “sag”

  or intermittent 

• Check low voltage connections

 

  (G, Y, W, R, C) at motor, unseated pins in 

 

  motor harness connectors

 

• Check “Bk” for erratic CFM command (in 

 

   variable-speed applications)

 

• Check out system controls, Thermostat

 • 

Perform Moisture Check

• “Hunts” or “puffs” at 

• Does removing panel or filter reduce 

  high CFM (speed) 

  “puffing”?

 

 - Reduce restriction

 

 - Reduce max airflow

• Stays at low CFM 

• Check low voltage (Thermostat) wires and

  despite system call 

  connections

  for cool or heat CFM 

• Verify fan is not in delay mode; wait until 

 

   delay complete

 

• “R” missing/not connected at motor

 

• Perform motor/control replacement check

• Stays at high CFM 

• “R” missing/not connected at motor

 

• Is fan in delay mode? - wait until delay time

 

  complete

 

• Perform motor/control replacement check

• Blower won’t shut off 

• Current leakage from controls into G, Y or W?

 

  Check for Triac switched thermostat or solid-

 

  state relay

Excessive noise

 

• Determine if it’s air noise, cabinet, duct or

 

  motor noise; interview customer, if necessary

• Air noise 

• High static creating high blower speed?

 

 - Is airflow set properly?

 

 - Does removing filter cause blower to slow

 

   down?  Check filter 

 

 - Use low-pressure drop filter

 

 - Check/correct duct restrictions

Symptom

 

Cause/Procedure

• Noisy blower or cabinet

 • 

Check for loose blower housing, panels, etc.

 

• High static creating high blower speed?

 

  - Check for air whistling through seams in

 

     ducts, cabinets or panels

 

  - Check for cabinet/duct deformation

• “Hunts” or “puffs” at

 • 

Does removing panel or filter reduce

   high CFM (speed) 

   “puffing”?

 

  - Reduce restriction

 

  - Reduce max. airflow

Evidence of Moisture

• Motor failure or  

• Replace motor and 

Perform Moisture Check

  malfunction has occurred

  and moisture is present

• Evidence of moisture  

• 

Perform Moisture Check

  present inside air mover

Do

 

Don’t

• Check out motor, controls,

 • 

Automatically assume the motor is bad.

  wiring and connections

  thoroughly before replacing

  motor

• Orient connectors down so  • Locate connectors above 7 and 4 o’clock

  water can’t get in 

   positions

 - Install “drip loops”

• Use authorized motor and  • Replace one motor or control model # with

  model #’s for replacement     another (unless an authorized replacement)

• Keep static pressure to a  

• Use high pressure drop filters some have 

½"

  

minimum: 

   H20 drop!

 - Recommend high 

• Use restricted returns

   efficiency, low static filters

 - Recommend keeping filters

   clean.

 - Design ductwork for min.

   static, max. comfort

 - Look for and recommend

   ductwork improvement,

   where necessary

• Size the equipment wisely  • Oversize system, then compensate with low

 

    airflow

• Check orientation before 

• Plug in power connector backwards

  inserting motor connectors  • Force plugs 

Moisture Check

• Connectors are oriented “down” (or as recommended by equipment

  manufacturer)

• Arrange harness with “drip loop” under motor

• Is condensate drain plugged?

• Check for low airflow (too much latent capacity)

• Check for undercharged condition

• Check and plug leaks in return ducts, cabinet

Comfort Check

• Check proper airflow settings

• Low static pressure for lowest noise

• Set low continuous-fan CFM

• Use humidistat and 2-speed cooling units

• Use zoning controls designed for ECM that regulate CFM

• Thermostat in bad location?

Содержание T30S1-A

Страница 1: ...B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547H Supersedes 2100 547G Date 8 16 17 T...

Страница 2: ...ons T S Dehum 23 Table 7 Indoor Blower Performance 24 Table 8 Dehumidification Relay Logic Board 27 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomen...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...ould be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National...

Страница 5: ...through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum...

Страница 6: ...ng upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to contro...

Страница 7: ...ting location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The bra...

Страница 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Страница 9: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Страница 10: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Страница 11: ...ACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACT...

Страница 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 13: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Страница 14: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 15: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Страница 16: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Страница 17: ...ooling mode with outdoor fan off Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay...

Страница 18: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Страница 19: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Страница 20: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Страница 21: ...0 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151...

Страница 22: ...3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2...

Страница 23: ...0 10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10...

Страница 24: ...own is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires...

Страница 25: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Страница 26: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Страница 27: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Отзывы: