![Bard SH381 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/bard/sh381/sh381_installation-instructions-manual_4252427023.webp)
Manual
2100-410G
Page
23 of 25
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each
side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and
bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud
assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
REFRIGERANT CHARGE
The correct system R-22 charge is shown on the unit
rating plate. Optimum unit performance will occur with
a refrigerant charge shown on the unit serial plate.
If correct charge is in doubt, recover the refrigerant and
recharge per the charge on the unit rating plate. See
Table 7 for proper subcooling levels for evaluation of
proper charge.
G
N
I
L
O
O
C
G
N
I
T
A
E
H
l
e
d
o
M
d
e
t
a
R
w
o
l
f
r
i
A
D
O
5
9
e
r
u
t
a
r
e
p
m
e
T
D
O
2
8
e
r
u
t
a
r
e
p
m
e
T
D
O
7
4
e
r
u
t
a
r
e
p
m
e
T
D
O
7
1
e
r
u
t
a
r
e
p
m
e
T
1
8
3
H
S
0
0
1
1
8
1
-
5
1
7
1
-
4
1
6
1
-
2
1
5
1
-
1
1
1
3
4
H
S
0
0
3
1
1
2
-
8
1
1
2
-
8
1
2
1
-
8
2
1
-
8
1
9
4
H
S
0
5
2
1
8
1
-
5
1
7
1
-
4
1
9
1
-
5
1
6
1
-
2
1
TABLE 8
RECOMMENDED OPERATING RANGES
* Rated CFM and ESP on high speed tap.
l
e
d
o
M
d
e
t
a
R
*
M
F
C
d
e
t
a
R
*
P
S
E
d
e
d
n
e
m
m
o
c
e
R
e
g
n
a
R
w
o
l
f
r
i
A
1
8
3
H
S
0
0
1
1
5
1
.
0
5
8
–
0
5
2
1
1
3
4
H
S
0
0
3
1
5
1
.
0
0
1
1
–
5
7
4
1
1
9
4
H
S
0
5
2
1
0
2
.
0
0
1
1
–
5
7
4
1
TABLE 9
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Values shown are for units equipped with standard 1-inch
throwaway filter or 1-inch washable filter. Derate ESP by .15
for 2-inch pleated filters.
l
e
d
o
M
1
8
3
H
S
1
3
4
H
S
1
9
4
H
S
W
K
h
g
i
H
d
e
e
p
S
d
e
M
d
e
e
p
S
w
o
L
d
e
e
p
S
h
g
i
H
d
e
e
p
S
d
e
M
d
e
e
p
S
5
0
A
-
3
.
0
3
.
0
3
.
0
3
.
0
3
.
0
8
0
A
-
3
.
0
3
.
0
3
.
0
4
.
0
4
.
0
0
1
A
-
3
.
0
3
.
0
2
.
0
3
.
0
3
.
0
6
0
B
-
4
.
0
3
.
0
3
.
0
3
.
0
3
.
0
9
0
B
-
4
.
0
3
.
0
3
.
0
3
.
0
3
.
0
6
0
C
-
3
.
0
3
.
0
3
.
0
3
.
0
3
.
0
9
0
C
-
3
.
0
3
.
0
3
.
0
3
.
0
3
.
0
TABLE 6
FAN BLADE SETTING
DIMENSION
l
e
d
o
M
A
n
o
i
s
n
e
m
i
D
1
8
3
H
S
1
3
4
H
S
1
9
4
H
S
5
7
.
1
FAN BLADE SETTING DIMENSIONS
Shown in Figure 15 are the correct fan blade setting
dimensions for proper air delivery across the outdoor
coil.
Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.
"A"
AIRFLOW
MIS-1724
FIGURE 15
FAN BLADE SETTING
1
Expected subcooling levels during cooling operation.
Above subcooling levels are provided to troubleshoot low
charge or overcharged conditions. If charge is in doubt,
evacuate and recharge the unit to the refrigerant charge
listed on the serial plate.
TABLE 7
1
REFRIGERANT CHARGE
SUBCOOLING LEVEL