WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing
information and maximum fuse or “HACR” type
circuit breaker size.  Each outdoor unit is marked
with a “Minimum Circuit Ampacity”.  This means
that the field wiring used must be sized to carry that
amount of current.  Depending on the installed KW
of electric heat, there may be two field power
circuits required.  If this is the case, the unit serial
plate will so indicate.  All models are suitable only
for connection with copper wire.  Each unit and/or
wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions 

must be

adhered to.  Refer to the National Electrical Code
(NEC) for complete current carrying capacity data
on the various insulation grades of wiring material.
All wiring muse conform to NEC and all local
codes.

The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly
used heater sizes.  Also shown are the number of
field power circuits required for the various models
with heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is
to be used with the equipment.  The correct size
must be used for proper circuit protection and also
to assure that there will be no nuisance tripping due
to the momentary high starting current of the
compressor motor.

The disconnect access door on this unit may be
locked to prevent unauthorized access to the
disconnect.  To convert for the locking capability,
bend the tab locate in the bottom left hand corner of
the disconnect opening under the disconnect access
panel straight out.  This tab will now line up with
the slot in the door.  When shut, a padlock may be
placed through the hole in the tab preventing entry.
See “Start Up” section for important information on
three phase scroll compressor start ups.

WIRING  –  LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment dual
primary voltage transformers.  All equipment leaves the
factory wired on 240V tap.  For 208V operation,
reconnect from 240V to 208V tap.  The acceptable
operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

Ten (10) wires should be run from thermostat subbase to
the 24V terminal board in the unit.  A nine conductor,
18 gauge copper color-coded thermostat cable is
recommended.  The connection points are shown in
Figure 8.

IMPORTANT

Only the thermostats shown in this Manual
have been tested with this equipment for
proper operation.  Proper unit operation with
thermostats not listed in this Manual, cannot
be assured.

You assume responsibility for proper
operation of the unit when using thermostats
other than those listed above.

FIGURE  8

UNIT 24V TERMINAL BOARD

Содержание SH381

Страница 1: ...TION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models SH381 SH431 SH491 Manual 2100 410G Supersedes 2100 410F File Volume III Tab 17 Date 10 21 08 Bard Manufacturing Company Inc Bryan Ohio 43506 Si...

Страница 2: ...Removal of Fan Shroud 23 Refrigerant Charge 23 Pressure Tables 25 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Mounting Instructions 10 Figure 4 Electric Heat Clear...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...oatedEvaporator andCondenser OUTLET OPTIONS X Front Standard VENTILATION OPTIONS B Blank offPlate E Economizer M Motorized Fresh Air Damper 1 P Commercial Ventilator Motorized Power Return w Exhaust R...

Страница 5: ...p p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T 1 8 3 H S 1 3 4 H S 1 9 4 H S 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6...

Страница 6: ...e r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 0 0 A 1 8 3 H S 5 0 A 8 0 A 0 1 A 1 8 0 2 0 3 2 1 2 r o 1 2 r o 1 2 r o 1 1 3 7 5 3 7 3 8 5...

Страница 7: ...h each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are...

Страница 8: ...equired for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available upon req...

Страница 9: ...h clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 3 and 4 for details WARNING Failure...

Страница 10: ...ng at time of installation MIS 1445 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top S...

Страница 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 12: ...Manual 2100 410G Page 12 of 25 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 410G Page 13 of 25 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in the bottom left...

Страница 15: ...l heating compressor off line and send the compressor signal to energize electric heat in its place to make electric heat first stage heating This can also be applied to bank the quantity of available...

Страница 16: ...ermostat This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the...

Страница 17: ...8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e h e g a t s 2 l o o c e g a t s 2 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 0 6 0 3 0 4 8 5 4 4 0 2 1 1 t...

Страница 18: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Страница 19: ...EQUENCE OF OPERATION COOLING Circuit R Y makes at thermostat pulling in compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call...

Страница 20: ...driver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the inst...

Страница 21: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Страница 22: ...3 4 3 6 2 3 3 2 7 1 3 0 4 8 0 3 6 8 9 9 2 7 5 1 9 2 5 5 3 8 2 7 7 5 7 2 3 2 8 6 2 2 9 0 6 2 3 8 3 5 2 6 9 6 4 2 0 3 0 4 2 4 8 3 3 2 8 5 7 2 2 0 5 1 2 2 1 6 5 1 2 9 8 9 0 2 5 3 4 0 2 6 9 8 9 1 0 3 5 0...

Страница 23: ...m o c e R e g n a R w o l f r i A 1 8 3 H S 0 0 1 1 5 1 0 5 8 0 5 2 1 1 3 4 H S 0 0 3 1 5 1 0 0 1 1 5 7 4 1 1 9 4 H S 0 5 2 1 0 2 0 0 1 1 5 7 4 1 TABLE 9 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY V...

Страница 24: ...C 0 1 2 3 5 2 6 1 5 7 4 1 0 5 3 1 0 5 1 1 5 7 4 1 0 5 3 1 0 5 1 1 5 2 8 5 2 4 1 5 2 3 1 0 0 2 1 5 2 0 1 5 2 3 1 0 0 2 1 5 2 0 1 0 5 7 5 2 1 1 0 0 1 1 0 0 0 1 5 2 8 0 0 1 1 0 0 0 1 0 5 8 5 7 6 0 0 7 1...

Страница 25: ...URE TABLE COOLING Air Temperature Entering Outdoor Coil F l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 8 3 H S B D g e d 5 7 B W g e...

Отзывы: