TROUBLESHOOTING  GE  ECM

 MOTORS

CAUTION:

Disconnect power from unit before removing or replacing
connectors, or servicing motor.  To avoid electric shock from
the motor’s capacitors, disconnect power and wait at least 5
minutes before opening motor.

Symptom

Cause/Procedure

Motor rocks slightly

• 

This is normal start-up for ECM

when starting

Motor won’t start

• 

Check blower turns by hand

• No movement

• Check power at motor
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
  (G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
   motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
• 

Perform Moisture Check

• Motor rocks,

• Check for loose or compliant motor mount

  but won’t start

• Make sure blower wheel is tight on shaft
• Perform motor/control replacement check

Motor oscillates up

• It is normal for motor to oscillate with no load

& down while being

  on shaft

tested off of blower

Motor starts, but
runs erratically

• Varies up and down

• Check line voltage for variation or “sag”

  or intermittent

• Check low voltage connections
  (G, Y, W, R, C) at motor, unseated pins in
  motor harness connectors
• Check “Bk” for erratic CFM command (in
   variable-speed applications)
• Check out system controls, Thermostat
• 

Perform Moisture Check

• “Hunts” or “puffs” at

• Does removing panel or filter reduce

  high CFM (speed)

  “puffing”?
 - Reduce restriction
 - Reduce max airflow

• Stays at low CFM

• Check low voltage (Thermostat) wires and

  despite system call

  connections

  for cool or heat CFM

• Verify fan is not in delay mode; wait until
   delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check

• Stays at high CFM

• “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
  complete
• Perform motor/control replacement check

• Blower won’t shut off

• Current leakage from controls into G, Y or W?
  Check for Triac switched thermostat or solid-
  state relay

Excessive noise

• Determine if it’s air noise, cabinet, duct or
  motor noise; interview customer, if necessary

• Air noise

• High static creating high blower speed?
 - Is airflow set properly?
 - Does removing filter cause blower to slow
   down?  Check filter
 - Use low-pressure drop filter
 - Check/correct duct restrictions

Symptom

Cause/Procedure

• Noisy blower or cabinet

• 

Check for loose blower housing, panels, etc.

• High static creating high blower speed?

  - Check for air whistling through seams in
     ducts, cabinets or panels
  - Check for cabinet/duct deformation

• “Hunts” or “puffs” at

• 

Does removing panel or filter reduce

   high CFM (speed)

   “puffing”?
  - Reduce restriction
  - Reduce max. airflow

Evidence of Moisture

• Motor failure or

• Replace motor and 

Perform Moisture Check

  malfunction has occurred

  

and moisture is present

• Evidence of moisture

• 

Perform Moisture Check

  present inside air mover

Do

Don’t

• Check out motor, controls,

• 

Automatically assume the motor is bad.

  wiring and connections
  thoroughly before replacing
  motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
  water can’t get in

   positions

 - Install “drip loops”
• Use authorized motor and

• Replace one motor or control model # with

  model #’s for replacement    another (unless an authorized replacement)
• Keep static pressure to a

• Use high pressure drop filters some have 

½"

  

minimum:

   H20 drop!

 - Recommend high

• Use restricted returns

   efficiency, low static filters
 - Recommend keeping filters
   clean.
 - Design ductwork for min.
   static, max. comfort
 - Look for and recommend
   ductwork improvement,
   where necessary

• Size the equipment wisely

• Oversize system, then compensate with low

    airflow

• Check orientation before

• Plug in power connector backwards

  inserting motor connectors

• Force plugs

Moisture Check

• Connectors are oriented “down” (or as recommended by equipment
  manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airflow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet

Comfort Check

• Check proper airflow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?

Содержание QW2S1

Страница 1: ...NSTALLATION INSTRUCTIONS Models QW2S1 QW3S1 QW4S1 QW5S1 Manual No 2100 532B Supersedes 2100 532A File Vol II Tab 14 Date 07 19 10 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahea...

Страница 2: ...pressor Control Module 23 Adjustments 23 Optional CFM 24 Important Installer Note 24 Phase Monitor 24 Service Hints 24 Sequence of Operation 24 25 Pressure Service Ports 25 Pressure Tables 28 Optional...

Страница 3: ...t Wiring D Option 21 Figure 16 Remote Thermostat Wiring H Option 22 Figure 17 Fluid Connections w Ventilation Wall Sleeve 26 Figure 18 Fluid Connections w o Ventilation Wall Sleeve 27 Figure 19 Circul...

Страница 4: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for the Design IGSHPA of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Страница 5: ...than one field power conductor circuit is run through one conduit the conductors must be derated Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three...

Страница 6: ...CE BACK VIEW FREEBLOW OPTIONAL LOW VOLTAGE ELECTRICAL ENTRANCE 1 11 16 3 3 4 3 1 16 3 3 8 VENT OPTIONAL HIGH INTAKE VOLTAGE VENT EXHAUST ENTRANCE ELECTRICAL ACCESS FOR FLUID CONNECTION FOR DORFC PUMP...

Страница 7: ...it can not be slid through the door then the unit will have to be put on a cart and tipped down to roll through the door It is recommended that an appliance cart be used with a strap to hold the unit...

Страница 8: ...any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities havin...

Страница 9: ...TARY OR TOGGLE DISCONNECT ELECTRICAL ACCESS BLOW PLENUM BOX TOP SIDE AND LOCKING COVER LOW VOLTAGE OPTIONAL FREE ELECTRICAL ENTRANCE TOP REAR SIDE VENTILATION PERMANENT HIGH VOLTAGE QW2S QW3S 42 000 Q...

Страница 10: ...40 FLOOR 8 FT 8 IN INSTALLATION HEIGHT 9 FT MINIMUM REQUIRED UNIT HEIGHT 7 FT 6 IN MINIMUM 25 IN TO DUCT BOTTOM 2 IN MINIMUM FROM DUCT FLANGE INSTALLATION HEIGHT 8 FT 9 IN MINIMUM REQUIRED MINIMUM 12...

Страница 11: ...o the ceiling This extends 20 above the unit for a total height above the floor of 10 7 8 The unit is equipped with a variable speed indoor blower motor which increases in speed with an increase in du...

Страница 12: ...ewall Ifthedrainistoberoutedthroughanunconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall...

Страница 13: ...that the mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator...

Страница 14: ...OVERY VENTILATOR 3 Underneath the heat recovery cassette there is a power connector for the lower blower assembly To disconnect this plug the tabs on both sides of the plug must be squeezed to release...

Страница 15: ...ping connections are to be within the confines of this bracket See Figure 1 for cabinet openings and location of fluid coil connection points 2 Position the unit in front of the wall mounting bracket...

Страница 16: ...of 46 FIGURE 11 UNIT MOUNTING WITHOUT VENTILATION WALL SLEEVE BRACKET WALL MOUNTING BASE TRIM SIDE TRIM CUT TO LENGTH 41 ADJUSTABLE SIDE TRIM EXTENSION KIT ORDERED SEPARATELY SIDE TRIM EXTENSION MIS 2...

Страница 17: ...Manual 2100 532B Page 17 of 46 FIGURE 12 COMPONENTLOCATION WIRE ENTRANCE SIDE FIELD TERMINAL BLOCK REMOTE THERMOSTAT INDOOR DUAL BLOWERS CONTROL BOX CIRCUIT BREAKER PANEL MIS 2745...

Страница 18: ...LTAGE WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptab...

Страница 19: ...for ventilation during occupied programming conditions and feeds through Pin 5 of Plug P2 The W2 terminal is the electric heat signal and feeds through Pin 9 of Plug P2 The W1 E terminal is the emerge...

Страница 20: ...CO2 Controller 24VAC O B Out Part 8403 060 C Y2 A Y1 R G Analog Controller Terminal Strip E W2 O C Y2 A W2 Y1 R Temp and Humidity Low Voltage D YO Orange Orange Orange Yellow Green Green Brown White B...

Страница 21: ...TAT WIRING DIAGRAM D THERMOSTAT OPTION Blue Pink Purple L O B W1 E Y1 Part 8403 060 C Y2 A W2 G R Temp and Humidity Controller D YO Orange Yellow Brown White Brown 9 8 11 10 PLUG 2 Red Yellow Red Whit...

Страница 22: ...E L CO2 Controller Out C Y2 A W2 Analog Temp and Humidity Controller Part 8403 060 Orange Orange Orange Yellow Green Green Brown Brown Brown White Brown Red White PLUG 1 Red Yellow PLUG 2 Red Red Bla...

Страница 23: ...ESSURE SWITCH AND LOCKOUT SEQUENCE If the high pressure switch opens the compressor contactor will de energize immediately The lockout timer will go into a soft lockout and stay in soft lockout until...

Страница 24: ...eakers to be sure that they are the correct rating 3 The heat pump wall thermostats perform multiple functions Be sure that all function switches are correctly set for the desired operating mode befor...

Страница 25: ...2 1 S 2 W Q 0 0 5 0 0 0 8 0 0 8 0 0 9 0 0 0 1 1 S 3 W Q 0 0 5 0 0 0 8 0 0 9 0 5 0 1 0 5 1 1 1 S 4 W Q 0 0 5 0 0 0 9 0 5 1 1 5 2 2 1 0 5 3 1 1 S 6 W Q 0 0 5 0 0 0 9 0 5 2 1 0 0 3 1 0 5 4 1 PRESSURE SER...

Страница 26: ...HIPPED WITH UNIT CEILING SIDE TRIM PIECES SHIPPED WITH UNIT IF THE WALL THICKNESS IS LESS THAN 14 BUT GREATER THAN 8 A SIDE TRIM EXTENSION KIT QSTX42 IS REQUIRED REFER FLUID ACCESS FROM SLEEVE TOP OF...

Страница 27: ...WITHOUT VENTILATION WALL SLEEVE 23 1 2 8 1 2 66 1 2 4 LEFT BRACKET REMOVED FOR FLOOR FLUID ACCESS FROM FLOOR FLUID ACCESS FROM TOP CLARITY WALL BRACKET OPENING IN REAR OF UNIT 3 x 8 BACK OF UNIT MIS...

Страница 28: ...9 8 3 1 3 1 1 0 4 0 4 1 2 1 4 9 4 1 4 2 4 9 5 1 5 3 4 8 6 1 7 4 4 S 5 W Q B D 0 7 e d i S w o L e d i S h g i H 7 3 8 8 2 4 4 0 0 3 1 5 2 1 3 8 5 4 2 3 5 6 5 3 3 2 7 7 4 3 9 7 9 5 3 6 8 1 7 3 3 9 2 8...

Страница 29: ...i t a l P 4 8 4 S B P Q t n i a P y a r G X 8 4 S B P Q t n i a P e g i e B e d i s h c a e n o e l l i r g n o i t c e f e d y a w 2 s u l p 8 4 B P Q s a e m a S s g n i l i e C o t s e x o B m u n...

Страница 30: ...st be closely matched with the pressure of FIGURE 19 CIRCULATIONSYSTEM head loss of the entire system in order to provide the required flow through the heat pump Insufficient flow through the heat exc...

Страница 31: ...capacity If the module selection is correct there is probably trapped air or a restriction in the piping circuit 8 Start the unit in cooling mode by moving the thermostat switch to cool Fan should be...

Страница 32: ...10 20 30 40 50 60 70 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 22 PERFORMANCE MODEL DORFC 2 LOOP PUMP MODULE 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 21 PERFORMANCE...

Страница 33: ...icated by the arrow on the side of the valve body Table 7 is a table showing the flow rate of each valve Two constant flow rate valves may be installed in parallel to increase the flow For example whe...

Страница 34: ...wer disconnect to ON Except as required for safety while servicing do not open the unit disconnect switch 4 Check system airflow for obstructions A Move thermostat fan switch to ON Blower runs B Be su...

Страница 35: ...er 3 Corrosion of Metal Corrosion of metal parts results from either highly corrosive water acid water generally not the case with ground water of galvanic reaction between dissimilar metals in the pr...

Страница 36: ...suspended in the dry well casing Jet pumps and other types of suction pumps normally consume more electrical energy than similarly sized submersible pumps Pipe the unit the same as a water well system...

Страница 37: ...of 46 FIGURE 25 WATER WELL SYSTEM 12 to 15 LAKE or POND WATER LEVEL GRAVEL FILL WELL CAP ELECTRICAL LINE PITLESS ADAPTER TO PRESSURE TANK SUBMERSIBLE PUMP PERFORATED PLASTIC CASING DROP PIPE WATER SU...

Страница 38: ...4 8 0 1 2 1 2 8 2 9 8 1 5 5 9 6 2 1 3 1 4 9 9 6 1 2 4 6 6 7 4 1 4 1 6 0 1 5 4 4 2 3 7 4 8 6 1 5 1 1 8 9 6 8 1 6 1 9 6 7 0 2 7 1 9 9 4 8 2 2 8 1 WARNING Thin ice may result in the vicinity of the disc...

Страница 39: ...Manual 2100 532B Page 39 of 46 FIGURE 26 WATER SOURCE HEAT PUMP...

Страница 40: ...Manual 2100 532B Page 40 of 46 FIGURE 27 WATER SOURCE HEAT PUMP...

Страница 41: ...de while the low side shell and suction line contains pressure the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame To prevent this occurrence it is...

Страница 42: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 43: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Страница 44: ...Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Co...

Страница 45: ...alled 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are for...

Страница 46: ...ontactor A 19 Amperage at compressor common terminal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling F...

Отзывы: