background image

Manual 2100-764 
Page 

7 of 8

FIGURE 4

CRV Wiring Diagram

2

6

5

4

3

1

FDBK

4056-265 A

BROWN

3 PIN

BROWN/WHITE

RED

VENT PLUG

25

Actuator Motor

BROWN/WHITE

2

BLACK

P3-3

  P

3-2

  P

3-1

OPTIONAL CO2 CONTROL

REQUIRED FIELD WIRING FOR

1

*B - ON/OFF CO2 CONTROL

*Unused - Tape off

3

TERMINAL STRIP

*A

*B

CRV CONTROL BOARD

UNIT LOW -VOLT

*B

SETTING)

KEY

RED/WHITE

24V

(USING OCC POTENTIOMETER

C

BL

AC

K/W

HIT

E

*A - MODULATING CO2 CONTROL

COM

Control

WHITE

3

24

R

CO2

(8403-096)

60

30

90

0

Содержание QCRV-4

Страница 1: ...cturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 764 Supersedes NEW Date 1 19 22 Commercial Room Ventilator with Exhaust and Optional CO2 Modulation Model QCRV 4 920 0540 For Use with...

Страница 2: ...ard Sequence of Operation 5 Adding Optional CO2 Control Sensor 6 Figures Figure 1 Adjusting OCC Potentiometer on CRV Control Board 3 Figure 2 CRV Installation and Adjustment 4 Figure 3 CRV Control Boa...

Страница 3: ...with built in exhaust provisions FIGURE 1 Adjusting OCC Potentiometer on CRV Control Board QCRV 4 The QCRV 4 has a spring return damper blade If vent operation is no longer required or in the event of...

Страница 4: ...pressure drop 3 Indoor blower motor speed 4 Damper blade open position setting for each mode of operation 5 Tightness or looseness of building envelope To determine the amount of fresh air that will b...

Страница 5: ...rminal strip is energized indicating occupancy Once the selected time has passed the blade will move to the position set by the OCC potentiometer OCC Potentiometer setting This potentiometer can be us...

Страница 6: ...nsor Bard Part 8403 096 to this control will maximize the capabilities of this vent by only supplying fresh air intake to maintain CO2 levels This has multiple benefits Minimizes ventilation load on s...

Страница 7: ...tuator Motor BROWN WHITE 2 BLACK P3 3 P3 2 P3 1 OPTIONAL CO2 CONTROL REQUIRED FIELD WIRING FOR 1 B ON OFF CO2 CONTROL Unused Tape off 3 TERMINAL STRIP A B CRV CONTROL BOARD UNIT LOW VOLT B SETTING KEY...

Страница 8: ...O CHANGE ANY SETTINGS WITH THE SIDE BUTTONS TO LOCK THE CO2 DIP SWITCHES MUST BE POSITIONED AS SHOWN FOR PROPER OPERATION MIS 4025 C Settings Recommended Default RON RELAY ON SET POINT 725 ROF RELAY O...

Отзывы: