background image

Manual

2100-467D

Page

22 of 25

NOTE: Affects Models PA13241, PA13301, PA13361

TROUBLESHOOTING  GE  ECM 2.3

 MOTORS

CAUTION:

Disconnect power from unit before removing or replacing
connectors, or servicing motor.  To avoid electric shock from
the motor’s capacitors, disconnect power and wait at least 5
minutes before opening motor.

Symptom

Cause/Procedure

Motor rocks slightly

• 

This is normal start-up for ECM

when starting

Motor won’t start

• 

Check blower turns by hand

• No movement

• Check power at motor
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
  (G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
   motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
• 

Perform Moisture Check

• Motor rocks,

• Check for loose or compliant motor mount

  but won’t start

• Make sure blower wheel is tight on shaft
• Perform motor/control replacement check

Motor oscillates up

• It is normal for motor to oscillate with no

load 

& down while being

  on shaft

tested off of blower

Motor starts, but
runs erratically

• Varies up and down

• Check line voltage for variation or “sag”

  or intermittent

• Check low voltage connections
  (G, Y, W, R, C) at motor, unseated pins in
  motor harness connectors
• Check “Bk” for erratic CFM command (in
   variable-speed applications)
• Check out system controls, Thermostat
• 

Perform Moisture Check

• “Hunts” or “puffs” at

• Does removing panel or filter reduce

  high CFM (speed)

  “puffing”?
 - Reduce restriction
 - Reduce max airflow

• Stays at low CFM

• Check low voltage (Thermostat) wires and

  despite system call

  connections

  for cool or heat CFM

• Verify fan is not in delay mode; wait until
   delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check

• Stays at high CFM

• “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
  complete
• Perform motor/control replacement check

• Blower won’t shut off

• Current leakage from controls into G, Y or W?
  Check for Triac switched thermostat or solid-
  state relay

Excessive noise

• Determine if it’s air noise, cabinet, duct or
  motor noise; interview customer, if necessary

• Air noise

• High static creating high blower speed?
 - Is airflow set properly?
 - Does removing filter cause blower to slow
   down?  Check filter
 - Use low-pressure drop filter
 - Check/correct duct restrictions

Symptom

Cause/Procedure

• Noisy blower or cabinet

• 

Check for loose blower housing, panels, etc.

• High static creating high blower speed?

  - Check for air whistling through seams in
     ducts, cabinets or panels
  - Check for cabinet/duct deformation

• “Hunts” or “puffs” at

• 

Does removing panel or filter reduce

   high CFM (speed)

   “puffing”?
  - Reduce restriction
  - Reduce max. airflow

Evidence of Moisture

• Motor failure or

• Replace motor and 

Perform Moisture

Check

  malfunction has occurred

  

and moisture is present

• Evidence of moisture

• 

Perform Moisture Check

  present inside air mover

Do

Don’t

• Check out motor, controls,

• 

Automatically assume the motor is bad.

  wiring and connections
  thoroughly before replacing
  motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
  water can’t get in

   positions

 - Install “drip loops”
• Use authorized motor and

• Replace one motor or control model # with

  model #’s for replacement    another (unless an authorized replacement)
• Keep static pressure to a

• Use high pressure drop filters some have 

½"

  

minimum:

   H

2

0 drop!

 - Recommend high

• Use restricted returns

   efficiency, low static filters
 - Recommend keeping filters
   clean.
 - Design ductwork for min.
   static, max. comfort
 - Look for and recommend
   ductwork improvement,
   where necessary

• Size the equipment wisely

• Oversize system, then compensate with low

    airflow

• Check orientation before

• Plug in power connector backwards

  inserting motor connectors

• Force plugs

Moisture Check

• Connectors are oriented “down” (or as recommended by equipment
  manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airflow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet

Comfort Check

• Check proper airflow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?

Содержание PA13241-A

Страница 1: ...13361 B PA13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C INSTALLATION INSTRUCTIONS Manual 2100 467D Supersedes 2100 467C File Volume II Tab 10 Date 08 12 08 Ba...

Страница 2: ...tings 18 Pressure Tables 19 20 Suction and Discharge Tube Brazing 21 Troubleshooting ECM Blower Motors 22 25 Figures Figure 1 Unit Dimensions 8 Figure 2 Slab Mounting at Ground Level 10 Figure 3 Airfl...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...m should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a genera...

Страница 5: ...o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0...

Страница 6: ...8 4 3 1 A P C 2 8 4 3 1 A P A 2 0 6 3 1 A P B 2 0 6 3 1 A P C 2 0 6 3 1 A P 5 0 A 3 1 3 P H E 1 8 0 2 0 4 2 X X X 0 1 A 3 1 3 P H E 1 8 0 2 0 4 2 X X X 5 1 A 3 1 3 P H E 1 8 0 2 0 4 2 X X 9 0 B 3 1 3...

Страница 7: ...0 4 8 3 1 4 5 5 2 6 1 8 6 9 7 0 7 0 8 4 4 8 9 0 B 3 1 3 P H E 3 8 0 2 0 4 2 9 0 0 7 0 3 5 7 6 0 0 0 3 2 7 8 1 7 1 2 e n o N 1 4 2 8 2 5 2 0 3 0 1 0 1 0 1 5 1 B 3 1 3 P H E 3 8 0 2 0 4 2 5 1 0 0 2 1 5...

Страница 8: ...package access panel Return opening Supply opening Drain access High voltage knockout Low voltage knockout Heater package knockout L W A E B C D F A C B C H height L length W width D E F G PA PH1324 1...

Страница 9: ...All outdoor duct work must be thoroughly insulated and weatherproofed All attic duct work must be thoroughly insulated Two inch thick insulation with suitable vapor barrier is recommended for both out...

Страница 10: ...re Condenser fan and motor access from top Leave 60 min above fan Side View Top View MIS 2143 between duct and any combustible material if distance between outside wall and unit is less than 3 feet ne...

Страница 11: ...48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Metal frame MIS 2144 Platform...

Страница 12: ...w for expansion of water when it freezes AIR FILTERS Air filters for the return air side of the system are not provided as part of these models and must be field supplied and installed as part of the...

Страница 13: ...l The electrical specifications list fuse and wire sizes 75 F copper for all models including the most commonly used heater sizes The unit rating plate lists a Maximum Time Delay Fuse or HACR type cir...

Страница 14: ...Y Terminal R G C HEAT ON UNITS WITH 15 OR MORE KW C Low Voltage Wiring B R W RC R Y1 L G C G Block R E Y L Thermostat Subbase 3 1 2 W1 W2 F RC B Unit 24V REMOVE JUMPER FOR 2 STAGE ELECTRIC B YO 1120...

Страница 15: ...recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leak...

Страница 16: ...sor operation is inhibited If a fault condition occurs reverse tow of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur SEQUENCE OF OPERATION BLOWER ONLY Wh...

Страница 17: ...never compressor is locked out due to HPC or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset devices The high pressure switch and low pressure...

Страница 18: ...he correct system R 410A charge is shown on the unit rating plate You can reference Tables 10 11 to validate proper system performance However it is recommended that if incorrect charge is suspected t...

Страница 19: ...4 7 2 0 4 1 6 9 2 2 4 1 8 1 3 4 4 1 0 4 3 7 4 1 2 6 3 9 4 1 4 8 3 1 5 1 2 1 4 3 5 1 0 4 4 6 5 1 9 6 4 8 5 1 7 9 4 0 6 1 5 2 5 2 6 1 3 5 5 5 8 B D 2 7 B W e d i S w o L e d i S h g i H 5 4 1 1 6 2 8 4...

Страница 20: ...4 7 3 1 5 6 4 9 3 1 2 9 4 0 4 1 0 2 5 2 4 1 7 4 5 0 8 B D 7 6 B W e d i S w o L e d i S h g i H 4 3 1 5 4 2 5 3 1 0 7 2 7 3 1 4 9 2 8 3 1 9 1 3 9 3 1 4 4 3 1 4 1 8 6 3 2 4 1 3 9 3 4 4 1 1 2 4 5 4 1 9...

Страница 21: ...2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 9 To connect Recommended brazing materials silfos with minimum 5 silver or silver...

Страница 22: ...sive noise Determine if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause b...

Страница 23: ...er to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into...

Страница 24: ...ry d Check the external static pressure total of both supply and return to insure that you are within the ranges as listed on the unit serial plate If higher than allowed additional duct work is neede...

Страница 25: ...nd the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Also check t...

Отзывы: