START UP AND OPERATION

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the
time the equipment is put into service.
  If improper
rotation is corrected at this time there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes the compressor’s
internal protector will trip.

All three phase ZR*3 compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminals should maintain proper rotation
direction.

The direction of rotation of the motor may be changed
by reversing any two line connections to the unit.

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling

in compressor contactor starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation, or can be energized by manual fan switch on
subbase for constant air circulation.

HEATING

  –  A circuit R-W1 is completed on each

heating cycle energizing electric heat if so equipped.

START UP NOTES

For improved start up performance, wash the indoor
coil with dishwasher detergent.

INDOOR BLOWER MOTOR

Some models feature a variable speed (ECM) motor
providing high efficiency, low sound levels and soft
start capabilities.  The motor is self adjusting to provide
the proper air flow rate at duct static pressures up to
0.50” WC without user adjustment or wiring changes.

On command from the wall thermostat the motor will
start slowly and ramp up to full speed over a period of
10- 15 seconds.

When the thermostat is satisfied the blower will operate
for approximately 1 minute, and then slow down and
stop.

COMPRESSOR CONTROL MODULE

The compressor control is an anti-short cycle/lockout
timer with high and low pressure switch monitoring and
alarm output.

ADJUSTABLE DELAY-ON-MAKE AND BREAK
TIMER

On a call for compressor operation the delay-on-make
period begins which will be 10% of the delay-on-break
setting.  When the delay-on-make is complete and the
high pressure switch (and low pressure switch if
employed) is closed, the compressor contactor is
energized.  Upon shutdown the delay-on-break timer
starts and prevents restart until the delay-on-break and
delay-on-make periods have expired.

HIGH PRESSURE SWITCH AND LOCKOUT
SEQUENCE  (Standard Feature)

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay-on-
make time has expired.  If the high pressure switch
opens again in this same operating cycle the unit will go
into manual lockout condition and the alarm circuit will
energize.  Recycling the wall thermostat resets the
manual lockout.

Содержание P1124A3

Страница 1: ...P1230A1 P1136A2 P1236A1 P1142A3 P1242A1 P1148A2 P1248A2 P1060A1 INSTALLATION INSTRUCTIONS Manual 2100 353D Supersedes 2100 353C File Volume II Tab 10 Date 03 19 03 Bard Manufacturing Company Bryan Ohi...

Страница 2: ...sions 8 Figure 2 Slab Mounting at Ground Level 10 Figure 3 Airflow and Service Access Clearances 10 Figure 4 Roof Top Application 11 Figure 5 Elevated Mounting Platforms 11 Figure 6 Prefabricated Rood...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Страница 4: ...to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consult...

Страница 5: ...e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 s p m A d a o L d e t a R 0 9 5 8 6 3 1...

Страница 6: ...o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 s p m A d a o L d e t a R 5 0 2 5 8 1 4...

Страница 7: ...l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 s p m A d a o L d e t a R 0 9 5 8 8 2 1 4 1 1 2 6 1 3 4 1 9...

Страница 8: ...0 4 2 A N S A N A N A N A N A N A N A N 5 1 A C P 3 H E 1 8 0 2 0 4 2 A N A N A N S A N A N A N S A N 9 0 B B P 3 H E 3 8 0 2 0 4 2 A A N A A N A S A A N S 5 1 B B P 3 H E 3 8 0 2 0 4 2 A N A N A A N...

Страница 9: ...2 7 2 3 8 0 6 0 3 0 6 0 6 1 1 1 1 3 2 6 2 6 4 3 5 8 6 9 7 1 9 4 0 1 5 2 0 3 0 5 0 6 0 7 0 8 0 0 1 0 1 1 0 1 0 1 8 6 4 4 3 2 0 1 0 1 8 6 9 0 B B P 3 H E 5 1 B B P 3 H E 3 8 0 2 0 4 2 3 8 0 2 0 4 2 9 5...

Страница 10: ...c n I g n i n e p O t c u D H e g r a h c s i D r i A n r u t e R A B C J K L M D E F G 3 A 4 2 1 1 P 2 A 4 2 2 1 P 2 A 0 3 1 1 P 1 A 0 3 2 1 P 2 A 6 3 1 1 P 1 A 6 3 2 1 P 4 1 4 2 6 1 3 8 4 8 1 8 3 8...

Страница 11: ...ing with the operation of the unit A minimum of twelve inch elevation is recommended while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick c...

Страница 12: ...Manual 2100 353 Page 10 FIGURE 2 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature MIS 1184 FIGURE 3 AIRFLOW AND SERVICE ACCESS CLEARANCES MIS 1185...

Страница 13: ...Manual 2100 353 Page 11 FIGURE 5 ELEVATED MOUNTING PLATFORMS MIS 1183 FIGURE 4 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176...

Страница 14: ...Manual 2100 353 Page 12 FIGURE 6 PREFABRICATED ROOF CURB SPECIFICATIONS HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP WELDED LEAKPROOF ONCE PIECE CONSTRUCTION READY TO INSTALL MIS 1177C...

Страница 15: ...P 1 A 2 4 2 1 P 2 A 8 4 1 1 P 2 A 8 4 2 1 P 1 A 0 6 0 1 P 0 6 E H R 4 0 0 2 4 0 9 5 7 3 2 8 5 2 1 4 4 5 2 1 1 4 5 7 3 8 3 5 7 3 5 3 4 4 5 2 1 3 5 2 1 9 1 0 5 5 7 4 1 2 4 5 2 8 3 j A SEPARATE METAL FLA...

Страница 16: ...AIR FILTERS Air filters for the return air side of the system are not provided as part of these models and must be field supplied and installed as part of the final installation Prior thought should b...

Страница 17: ...th the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor WIR...

Страница 18: ...Manual 2100 353 Page 16 FIGURE 9 LOW VOLTAGE WIRING MIS 1180...

Страница 19: ...tarting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air ci...

Страница 20: ...rm signal is desired This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset...

Страница 21: ...mperative to match the correct pressure table to the unit by model number REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a...

Страница 22: ...ormly around the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 11 Do not overheat joint MIS 1179 FIGURE 11...

Страница 23: ...5 2 2 1 8 0 4 2 2 8 0 6 2 4 8 8 7 2 5 8 5 9 2 6 8 5 1 3 7 8 5 3 3 8 8 1 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 4 8 2 1 2 6 8 3 3 2 7 8 8 4 2 8 8 9 6 2 0 9 7 8 2 1 9 5 0 3 2 9 6...

Страница 24: ...d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 3 0 2 4 7 8 1 2 5 7 1 3 2 6 7 6 4 2 8 7 4 6 2 9 7 8 7 2 0 8 4 9 2 1 8 2 1 3 2 8 0 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 8...

Страница 25: ...k c e h C d e e p s M F C h g i h t a s f f u p r o s t n u H g n i f f u p e c u d e r r e t l i f r o l e n a p g n i v o m e r s e o D n o i t c i t s e r e c u d e R w o l f r i a m u m i x a m e...

Страница 26: ...w s c a i r T r o f k c e h C y a l e r N O T P M Y S E R U D E C O R P E S U A C e s i o n e v i s s e c x E e s i o n r o t o m r o t c u d t e n i b a c e s i o n r i a s i t i f i e n i m r e t e...

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ......

Отзывы: