FIGURE 15
th-Tune Power and Communications Connections
24V GND
Rx-/Tx- Rx+/Tx+ GND
Communications Wiring
For the communications wiring, use 3-wire 20 gauge
shielded cable.
When wiring communication for the th-Tune, the
green connecter plugged into the wall unit PLC
board (with the jumper leads that connect from the
communications terminal block as shown in Figure 17),
will need to be moved from Fieldbus 2, to Fieldbus 1.
Communications
Power
FIGURE 16
Wall Unit and th-Tune Power and Communications Connections
Communications*
Power
* If power is connected to these terminals,
the th-Tune will be damaged.
24V~/m
GND
Tx/Rx-
WALL UNIT
G
G0
Tx/Rx+
Rx+/Tx+
Rx-/Tx-
GND
TH-TUNE
MIS-3912
(see Figure 5)
FIGURE 17
Proper Communication Connector Placement
Place Green Connector
Here for th-Tune Operation
Green Connector Position
for LC6000 Operation
Terminal Block Label
Terminal Block for
Connecting to th-Tune
NOTE:
A right-hand unit is shown. On
left-hand units, the th-Tune terminal
block is on opposite side of control
board. Make connections according
to the terminal block label. Damage
will occur is power is applied to the
communications terminals.