Bard MC4001 Series Скачать руководство пользователя страница 16

Manual 2100-614C
Page 

16 of 40

CONTROLLER WIRING

The MC4001 can be used for controlling two (2) air 
conditioners with or without economizers.  It can 
also be configured for two (2) heat pumps without 
economizers.  Units with economizers will connect 
differently than units without economizers; therefore, it 
is important to use the correct connection diagram.

There are older style EIFM economizers and newer 
style ECONWMT economizers that the MC4001 
controller system can work with, and also an option for 
a remote Ethernet communication board.  Therefore, it 
is important to select the correct low voltage hook-up 
diagram.  See Table 1 — Hook-Up Diagram Selection 
on Page 17.

SECURITY (LOCKING) FEATURE

The MC4001 controller can be locked such that 
unauthorized persons cannot make any changes 
to temperature set points or any other selectable 
parameters of the controller system.

The ON/OFF and Comfort buttons remain fully active 
for their normal intent.  The Advance/Change/Save 
button remains active for the Advance feature only, 
which allows the position of the lead and lag air 
conditioners to be swapped (reversed).  The Program 
button remains partially active - allowing the review of 
temperature sensor(s) actual reading of temperature, 
and the current settings/choices that have been chosen.  
However, no changes can be made when the controller 
is locked, and if the change button is pressed when in 
the Program mode, the display will come up showing 
“Locd” instead of flashing the selectable choices for 
that parameter.  The default (DEF) reset capability is 
also disabled when the controller is in locked mode.

Locking and Unlocking the MC4001 Controller:

  1.  Locking the controller requires using 3 buttons 

while the controller is in the normal operating 
(run) mode.

  2.  Press and hold the Advance/Change/Save 

button and the Up and Down arrow buttons 
simultaneously for 20 seconds until the display 
shows “Locd”.

  3.  To unlock the controller, press the Change, Up 

and Down arrow buttons simultaneously for 20 
seconds until the display reads “uLoc”.

GENERATOR RUN FEATURE

If desired, the MC4001 controller can be signaled 
from a standby generator system to lockout (disable 
operation) of the lag air conditioning system.  This 
is sometimes mandated if the generator size is not 
sufficient to handle the building load (amperage) and 
that of both air conditioning systems.

A normally closed (NC) dry contact as part of generator 
controls is required.  These contacts must open when 
the generator is started, and such action will signal the 
MC4001 controller to this condition and disable lag air 
conditioner run function.

A wire jumper is factory-installed across the G1 and 
G2 terminals or main controller board.  To utilize the 
generator run feature, remove the jumper from G1 and 
G2, and connect the generator normally closed (NC) 
contacts that will open-on-run generator condition to 
the G1 and G2 terminals. 

BACKUP DC POWER CONNECTION

There are input connections available for -24VDC 
or -48VDC (-20 to -56V) backup power connection.  
Making this connection will maintain microprocessor 
operation, front panel display, LED signaling, and alarm 
relay operation during periods of commercial power 
outages and when no standby generator is available.  
This circuit is protected by a replaceable .5A (500mA) 
circuit breaker.

IMPORTANT: 

 

The shelter DC battery power must be 

connected to the controller and wired as shown in 

controller wiring diagrams.
The backup DC power connection is polarity sensitive.  

If polarity is reversed, the controller will not function on 

backup power, no display and no alarm functions will 

be evident.

Содержание MC4001 Series

Страница 1: ...01 SERIES SOLID STATE DUAL UNIT LEAD LAG CONTROLLER INSTALLATION INSTRUCTIONS REPLACEMENT PARTS LIST Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 614C Supersedes 2100 6...

Страница 2: ...trategy 33 MC Series Label 35 Figure 17 Parts List Description Diagram 36 Tables Table 1 Hook Up Diagram Selection 17 Table Parts List 37 Getting Other Information and Publications 3 MC4001 General In...

Страница 3: ...90B and Air Conditioning Systems FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax...

Страница 4: ...red for special applications or user preference The MC4001 can be equipped with one of two alarm boards and these can be factory installed or installed at any time in the field if so desired Should th...

Страница 5: ...e base sides top of the controller TEMPERATURE SENSORS The standard local temperature sensor has 12 leads and comes installed from the factory A secondary sensor is located internally on the main cont...

Страница 6: ...ith jumper installed a H1 H2 Humidity controller input Requires optional controller Field installed a These connections require either jumper or Normally Closed NC relay contact at the Fire Smoke and...

Страница 7: ...located in the electrical control panel of the air conditioners being controlled by the lead lag controller To eliminate the 60 second blower off delay disconnect and isolate the wire that is factory...

Страница 8: ...SETTINGS Order Display Description Range Choice Default LSEn Temperature at local main sensor SP Cooling set point temperature 65 to 90F 18 to 32C 77F 25C db Deadband between cooling SP and heating s...

Страница 9: ...cooling set point is 4F default setting user selectable 2 6F warmer than Stage 1 On a call for 2nd Stage cooling the blower of the lag unit is turned on if not already on See Blower Operation and the...

Страница 10: ...omizer 3rd cooling set point is 2F default setting user selectable 2 3F warmer than Stage 2 On a call for 3rd Stage cooling the lead unit economizer will continue to operate as long as outdoor conditi...

Страница 11: ...ressor Stage 1 partial capacity operation 2nd cooling set point is 4F default setting user selectable 2 6F warmer than Stage 1 at which time the lead unit compressor will switch to compressor Stage 2...

Страница 12: ...int of the economizer control the lead unit economizer will operate instead of the compressor If outdoor conditions are not acceptable for free cooling the compressor will automatically operate on com...

Страница 13: ...NG SEQUENCE OF OPERATION Note All heating sequences for air conditioners with electric heat or heat pumps will automatically operate in Alternating Lead Lag Lead Lag sequence even if controller is set...

Страница 14: ...age should appear For Vista or Windows 7 1 Open Control Panel click Network Internet 2 Click Network Sharing Center 3 Click Local Area Network link 4 Click Properties 5 Highlight Internet Protocol Ver...

Страница 15: ...Alarm b Low Temp Clear or Alarm c High Temp 1 Clear or Alarm d High Temp 2 Clear or Alarm e Controller Failure Clear or Alarm SETPOINTS PAGE Note Read level authority can view this screen but cannot...

Страница 16: ...ttons while the controller is in the normal operating run mode 2 Press and hold the Advance Change Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display shows L...

Страница 17: ...ard Newer ECONWMT Economizer No Communication Board Newer ECONWMT Economizer with CB4000 Communication Board A C with 1 Stage Compressor WA WL W A W L 1 3 5 7 9 11 A C with 2 Stage Compressor WA S WL...

Страница 18: ...Manual 2100 614C Page 18 of 40 FIGURE 2 CONTROLLER CONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS...

Страница 19: ...Manual 2100 614C Page 19 of 40 FIGURE 3 CONTROLLER CONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS NO ECONOMIZER WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 20: ...Manual 2100 614C Page 20 of 40 FIGURE 4 CONTROLLER CONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 21: ...Manual 2100 614C Page 21 of 40 FIGURE 5 CONTROLLER CONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 22: ...Manual 2100 614C Page 22 of 40 FIGURE 6 CONTROLLER CONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 23: ...Manual 2100 614C Page 23 of 40 FIGURE 7 CONTROLLER CONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 24: ...Manual 2100 614C Page 24 of 40 FIGURE 8 CONTROLLER CONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 25: ...Manual 2100 614C Page 25 of 40 FIGURE 9 CONTROLLER CONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 26: ...Manual 2100 614C Page 26 of 40 FIGURE 10 CONTROLLER CONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 27: ...Manual 2100 614C Page 27 of 40 FIGURE 11 CONTROLLER CONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 28: ...Manual 2100 614C Page 28 of 40 FIGURE 12 CONTROLLER CONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 29: ...Manual 2100 614C Page 29 of 40 FIGURE 13 CONTROLLER CONNECTIONS HEAT PUMPS NO ECONOMIZER...

Страница 30: ...Manual 2100 614C Page 30 of 40 FIGURE 14 CONTROLLER CONNECTIONS HEAT PUMPS NO ECONOMIZER WITH OPTIONAL ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 31: ...hod to issue an alarm signal that the lead air conditioner is down or not delivering full capacity and that the lag air conditioner is now operating REFRIGERANT PRESSURE ALARMS Air conditioners with J...

Страница 32: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 33: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 34: ...wn If no buttons are pushed within thirty 30 seconds the controller will automatically revert back to RUN mode To reset all controller settings to the factory default values press the PROGRAM button f...

Страница 35: ...efault is 77F 25C 5 Deadband between cooling and heating setpoint 2 to 40F or 1 1 to 22 2C Default is 17F 9 4C 6 Continuous blower operation None Lead Both Default is None 7 Degree display F or C Defa...

Страница 36: ...Manual 2100 614C Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS 2954 B 15 3 4 5 12 7 9 2 6 13 14 11 16 18 8 10 1 17...

Страница 37: ...or X X X X X 7 8611 099 LTF Fitting X X X X X 8 5400 002 Hinge X X X X X 9 8612 023A Sensor X X X X X 10 7961 731 Label Keypad X X X X X 11 8611 006 Ground Lug 2 2 2 2 2 12 8612 035 Communication Boar...

Страница 38: ...Manual 2100 614C Page 38 of 40 This page intentionally left blank...

Страница 39: ...Manual 2100 614C Page 39 of 40 This page intentionally left blank...

Страница 40: ...Manual 2100 614C Page 40 of 40 This page intentionally left blank...

Отзывы: