Manual 2100-614C
Page
15 of 40
USER PAGE
1. The designated Admin person can assign up to 9
additional users and set-up as Admin, Write or
Read
authority.
2. User Name and password must be assigned,
each must be at least 3 characters long, and are
case sensitive.
3. Only “Admin” can add, change or delete users
and has access to all controller pages.
4. “Write” can make changes to the controller
settings and operating characteristics, and has
access to only Log In, System Status, Setpoints,
and Log Out pages.
5. “Read” can only view Status and Setpoints pages
and cannot make any changes.
SYSTEM STATUS PAGE
1. This page shows the overall HVAC status of:
a. Active cooling or heating stages or
dehumidification mode (requires humidity
sensor)
b. Active controller outputs (blower, cooling
Stage 1 or 2, heating) to each air conditioner
c. Which unit is the Lead unit
d. Power loss or refrigerant lock-out for each air
conditioner
e. If economizers are used if on or off (Note:
older style EIFM economizers require a simple
relay kit for this feature to work, Bard Part
Number 8620-221)
2. General status of:
a. Dehumidification Active or not
b. Backup Generator Active or not (if tied to
generator run controls to inhibit lag unit
operation during generator run)
c. Alarm board connected or not
d. Controller system Locked or Unlocked
e. Comfort mode Active or not
3. Temperatures:
a. Average temperature (if more than one sensor
used, if not will read same as Local sensor)
b. Local sensor at controller
c. Remote 1 or Remote 2 if connected
4. General Alarm Status:
a. Fire/Smoke, Clear or Alarm
b. Low Temp, Clear or Alarm
c. High Temp #1, Clear or Alarm
d. High Temp #2, Clear or Alarm
e. Controller Failure, Clear or Alarm
SETPOINTS PAGE (Note: “Read” level authority
can view this screen but cannot make any changes.
“Admin” and “Write” authority can make changes)
1. General Setpoints
a. On initial installation and start-up all
selectable characteristics are set to factory
default settings.
b. Each of these points has a drop-down menu
for ease of use.
2. Alarm Board Setpoints
a. Low temperature alarm setpoint
b. High temperature alarm #1 setpoint
c. High temperature alarm #2 setpoint
3. System Overrides
a. System 1 Cooling Override
b. System 1 Heating Override
c. System 2 Cooling Override
d. System 2 Heating Override
e. Turn Power On to the System (Note: Cannot
remotely turn the controller system Off)
f. Lock/Unlock Controller
g. Advance Lead to Lag Unit
h. Comfort Mode
i. Restore System Defaults
j. Reset Controller. There are built-in routines to
prevent the controller system from getting
“locked up”, but this also allows a manual
remote reset as a backup before having a
service call to the site.
LOG OUT BUTTON
1. Clicking this button will automatically log you off
the controller remote access.
2. To log back in will require entering assigned IP
address into your browser and entering valid User
Name and Password.
CONNECT TO NETWORK
1. After initial set-up using laptop computer,
disconnect computer cable from the Ethernet
port and connect the CAT 5 or CAT 6 network
cable.
2. Remote access is now available using the
assigned IP address and valid User Name and
Password (case sensitive).
CB4000 COMMUNICATION BOARD
RESET BUTTON TO RETURN TO DEFAULT CONTROLLER SETTINGS
ETHERNET PORT
IP DEFAULT ADDRESS RESET
PHONE JACK
CONNECTION
TO MAIN
CONTROLLER
BOARD
Содержание MC4001 Series
Страница 29: ...Manual 2100 614C Page 29 of 40 FIGURE 13 CONTROLLER CONNECTIONS HEAT PUMPS NO ECONOMIZER...
Страница 38: ...Manual 2100 614C Page 38 of 40 This page intentionally left blank...
Страница 39: ...Manual 2100 614C Page 39 of 40 This page intentionally left blank...
Страница 40: ...Manual 2100 614C Page 40 of 40 This page intentionally left blank...