
ALARMS
NOTE:
Screenshots shown in this manual reflect
default settings (when applicable).
Alarm Adjustment
Acknowledging/Clearing Alarms
Alarm conditions activate a red LED indicator that
backlights the ALARM function key. As an option, an
alarm condition may also be enunciated by an audible
alarm signal. An alarm is acknowledged by pressing the
ALARM key. This calls up alarm display screen(s) that
provide a text message detailing the alarm condition(s).
After an alarm condition is corrected, the alarm can be
cleared by pressing the ALARM key for 3 seconds.
Low Temperature Alarm
If the lowest temperature sensor value in a zone is
below the low temperature setpoint, an alarm will be
generated for that zone. Additionally, a relay output will
be actuated from the LC controller to provide remote
notification of the event.
NOTE:
This alarm is per zone. If each zone is meant to
operate within the same alarm parameters, each
zone will need to be set accordingly.
To adjust the low temperature alarm setpoint:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Zone 1
,
Zone 2
or
Zone 3
; press ENTER key.
5. Press UP or DOWN keys to scroll to
Alarm
Setpoints A2-9
(Zone 1),
Alarm Setpoints A3-9
(Zone 2) or
Alarm Setpoints A4-9
(Zone 3
)
.
6. Press ENTER key to scroll to the variable labeled
Low Temp
(see Figure 13).
7. Press UP or DOWN keys to adjust setpoint.
To change the direction of the remote notification relay
output:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Digital Out
Config C3
.
5. Press ENTER key to scroll to the variable in the table
that intersects
LoTemp
and
Dir
(see Figure 14).
6. Press UP or DOWN key to change direction.
The low temperature notification relay has dry contacts.
The
Dir
, direction, is the position of the relay without
a low temperature event.
NO
is normally open;
NC
is
normally closed.
When the
Val
(value) is
OFF,
the relay is not in an alarm
condition. When the
Val
(value) is
ON,
the relay is in
an alarm condition. The relay connections for the low
indoor temperature alarm are on the LC6000 terminal
block; see Table 6 on page 34 for terminal block index.
High Temperature Alarm
If the highest temperature sensor value in a zone is
above the high temperature setpoint, an alarm will be
generated for that zone. When this alarm is present,
emergency cooling in this zone will become active.
There are two high temperature alarm setpoints. This
is the first and there is no remote notification for this
alarm.
NOTE:
This alarm is per zone. If each zone is meant to
operate within the same alarm parameters, each
zone will need to be set accordingly.
To adjust the high temperature alarm setpoint:
1. Press MENU key to go to the Main Menu screen.
FIGURE 13
Adjust Alarm Setpoints
FIGURE 14
Adjust Alarm Remote Notification
Relay Output Direction
Manual 2100-669F
Page
15 of 37