background image

Manual 2100-578E

Page 

9 of 41

HANDlING UNIT AFTER REMOVAl FROM SKID

If a wide and tall opening exists, the I-TEC can be moved as a 

complete assembled unit.  If not, use the following directions for 

dis-assembly to allow it to pass through a 36" wide door.

1.

 Depress and release both top & bottom door latches and  

  open doors.

2.

 Remove doors by lifting straight up & off from the hinge pins.

3.

 Remove cabinet sides by first removing the four (4) sheet metal  

  screws from the front (leading edge) of the side panel.  The panel 

  will not fall off.  Swing the panel away from the chassis 20-30  

  degrees & then pull forward from the two (2) tabs supporting 

  the rear edge.  At this point, the unit can be tipped on its left 

  side enough to get dolly carts under it.  Use dolly carts to  

  move unit into installation area.  Use care not to damage  

  vent wire harness.  This method is not suggested due to unit 

  weight and if a forklift or unit lift is available, continue with 

  the following steps for separation of top section & bottom base.

4.

 On each side of the unit is a tie plate that secures the top &  

  bottom sections with four (4) cap bolts.  Using a ½" wrench 

  or socket, remove these screws from both plates & set aside.

5.

 If the unit is equipped with a CRV, you must unplug the 

  wire harness on the left-hand side of the control box.

6. A forklift or a lift rated for the load is required to lift the 

  top section off from the bottom base.  Do not attempt to 

  do this manually!  Failure to do so could result in the 

  unit tipping over & causing bodily injury &/or damage to 

  the unit.

7.

 The top section can be forked from either the RH or LH 

  side.  See Figure 1 for fork openings.

8.

 Carefully lift the top section straight up avoiding tipping.

9.

 Move the top section through the doorway & place on flat

 

  surface free of debris.

10.

 The bottom base can now be moved through the doorway 

     the same way.

11.

 Reassemble the unit by reversing this procedure.

Tip unit from left side only.

Failure to do so may result in injury due to unit 

top-heaviness or compressor damage!

A forklift or a lift rated for the load (Figure 2A) is 

required to lift the unit off from the skid.  This unit is 

top heavy and should never be tipped while moving it.
The I-TEC is designed to be lifted off the skid from the 

front or rear of the unit without having to remove any 

doors or side panels.  See Figure 1 for fork openings.  

The shipping brackets on front and rear of the unit must 

be removed and discarded.  The unit can now be lifted 

straight up and the skid can be slid out from underneath.

SHIPPING DAMAGE

Upon receipt of equipment, the unit should be checked 

for external signs of shipping damage.  The skid must 

remain attached until the unit is ready for installation.  

If damage is found, the receiving party must contact 

the last carrier immediately, preferably in writing, 

requesting inspection by the carrier’s agent.

UNIT REMOVAl FROM SKID

      WARNING

This unit is heavy and requires more than one person 

to handle during installation and removal from the 

skid.  Extreme caution must be taken to prevent injury 

to personnel and damage to the unit.  Use appropriate 

safety equipment, including gloves when handling.  

Failure to do so may result in serious injury.

FIGURE  2A   UNIT ON lIFT

FIGURE  2b   UNIT SIDE

CRV

HARNESS CONNECTION

(4) CAP bOlTS

FORK OPENING

(Visible after 

removing tie plate)

TIE PlATE

(Covers entire width; shortened for illustration 

purposes to show Fork Openings)

lEFT 

SIDE 

of 

UNIT

Содержание I36Z1-A

Страница 1: ...INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 578E Supersedes 2100 578D Date 11 10 14 I36Z1 A I36Z1 B I36Z1 C I48Z1 A I48Z1 B I48Z1 C I60Z1 A...

Страница 2: ...ure 1 Unit Dimensions 7 Center of Gravity 8 Figure 2A Unit on Lift 8 Figure 2B Unit Side 8 Wall Mounting Bracket Location 10 Bracket Wall Sect View Wood Framed Install 11 Figure 3 Compressor Shipping...

Страница 3: ...ummer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Conditi...

Страница 4: ...ulation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Tha...

Страница 5: ...TREATMENT X Std Hydrophilic Fin Evap Uncoated Alum Cond Coil 1 Phenolic Coated ID Coil 2 Phenolic Coated OD Coil 3 Phenolic Coated ID OD Coil CONTROLS X 24V Terminal Block Only w o CompleteStat 1 Comp...

Страница 6: ...al Fuse or Ckt Breaker Field Power Wire Size Ground Wire Size Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B I36Z1 A0Z A05 A10 j A15 230 208 1 1 1 1 or 2 1 or 2 26 52 78 84 40 60 80 90 8 6 4 4 10 10...

Страница 7: ...RE TIES PART 7950 031 High Voltage Entrance Entrance Low Voltage 20 x 24 Supply Frame With Sides Removed 1 Total Depth 3 8 8 26 7 2 20 18 4 18 3 2 31 1 61 Total Width 1 4 4 28 1 4 9 3 46 1 8 24 Vent E...

Страница 8: ...nit Tested Front of Unit Door to center Left side to center Floor to Center Crv erv Floor to Center no vent X Dimension Y Dimension Z Dimension Z Dimension I36Z1 A B 13 31 43 47 I36Z1 C 13 31 43 47 I4...

Страница 9: ...e 1 for fork openings 8 Carefully lift the top section straight up avoiding tipping 9 Move the top section through the doorway place on flat surface free of debris 10 The bottom base can now be moved...

Страница 10: ...eability and filter access must be considered before installing See Figure 5D for required clearances and recommended service access dimensions SEcuring unit to structure Shipped with the I TEC unit i...

Страница 11: ...94 1 31 Min 20 34 Max 3 1 48 1 2 Max 48 Min 3 Centered 8 Centered 43 1 4 Max 49 16 8 20 20 20 43 7 42 3 4 Min 16 11 15 4 43 3 8 Duct Grille Floor Optional Outside Ceiling Wall Sleeve Telescoping Wall...

Страница 12: ...Manual 2100 578E Page 12 of 41 FIGURE 3 COMPRESSOR SHIPPING BOLTS FIGURE 4 removal of air duct compressor shipping bolt compressor shipping bolt crv air duct...

Страница 13: ...TTOM OF ROOF FLOOR OR FIXED CEILING SUSPENDED CEILING 20 MINIMUM 7 9 3 4 UNIT HEIGHT 9 7 MINIMUM CLEARANCE RECOMMENDED TO BOTTOM OF ROOF OR FIXED CEILING 9 2 MINIMUM REQUIRED INSTALLATION HEIGHT BOTTO...

Страница 14: ...EARANCE RECOMMENDED TO BOTTOM OF ROOF OR FIXED CEILING 6 RISER FIELD SUPPLIED DUCT MIS 3200 TURNING VANES RECOMMENDED MINIMUM 12 4 MINIMUM FROM TOP OF UNIT TO DUCT BOTTOM FLOOR OR FIXED CEILING BOTTOM...

Страница 15: ...24 MIN 12 MIN FOR LEFT SIDE ACCESS SIDE 12 MIN FOR RIGHT ACCESS WING WALL CONSTRUCTION TOP VIEW RIGHT CORNER CONSTRUCTION TOP VIEW LEFT CORNER CONSTRUCTION TOP VIEW CLOSET CONSTRUCTION TOP VIEW FILTE...

Страница 16: ...heat pumps are designed for use with free return non ducted and either duct free with the use of IPBDFZ Series Plenum Box 18 or 12 or a duct supply air system The IPBDZ Plenum Box mounts on top of th...

Страница 17: ...he right hand or left hand optional drain locations on the rear of the unit The hole is covered by insulation on the inside of the unit and will have to be cut away Located inside the unit about 12 in...

Страница 18: ...Long Use 12 3 4 Long to Attach Inner Sleeve to Unit Back Self Tapping Screws Use 4 1 2 Long Screws to Attach frame to Exhaust Sleeve Use 12 Field Supplied Concrete or Wood Screws to Secure Outer Slee...

Страница 19: ...ed insulated 1 Outside wall 2 Area between sleeve and wall 3 Drain area behind unit SIZE VARIES OUTDOOR GRILLE INSIDE WALL AND SLEEVE INTERIOR FLOOR AREA BETWEEN WALL OUTSIDE WALL INSULATED INSULATED...

Страница 20: ...e sizing information and maximum fuse or HACR Type circuit breaker size Each unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of...

Страница 21: ...ging in the motor could result in motor failure TABLE 4 WALL THERMOSTATS W2 terminal is first stage electric heat if equipped First stage electric heat can be operated simultaneously with the heat pum...

Страница 22: ...rip R 3 SC W1 E A D L O B Y2 Y1 24V G COM W2 Completestat Model CS9B THO or Model CS9BE THO SC SC GND Thermostat W1 E A YO D L O B Y2 Y1 R G C W2 Bard 8403 060 Blue Yellow Orange Red 1 Not needed belo...

Страница 23: ...B Y2 Y1 R G C W2 Bard 8403 060 Blue Yellow Orange MIS 3204 A 1 Not needed below 15KW 2 to N C fire alarm circuit if emergency shutdown required Factory installed jumper Remove jumper and connect 3 Con...

Страница 24: ...uit if emergency shutdown required Factory installed jumper Remove jumper and connect 3 3 4 CRV Wiring Harness RT Connect to G terminal when thermostat has Occupancy Signal 4 BROWN WHITE ORANGE BLACK...

Страница 25: ...multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system ma...

Страница 26: ...wer in such a way as to cause rotation in the reverse direction verification of proper rotation must be made Verification of proper rotation direction is made by observing that suction pressure drops...

Страница 27: ...on a circuit is completed from R B and R Y1 on each heating on cycle energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor R G also make startin...

Страница 28: ...SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals It may take up to 15 seconds with...

Страница 29: ...ergize the CRV and indoor blower during occupied periods of the day NOTE The ventilation package comes with a blower interlock function but is disabled when it is shipped from the factory in case you...

Страница 30: ...D BLUE MED LO VENT OPTION INTAKE EXHAUST SPEEDS 7961 755 2 RED HI MED HI BLUE ORANGE NOM CFM BLACK WIRE COLOR LO ORANGE RED WIRE WITH WHITE TRACE 300 375 450 525 TO CHANGE SPEEDS MOVE BROWN BROWN WHIT...

Страница 31: ...rv speed change terminal access BLOWER SPEED CONTROL LOCATION BLOWER SPEED CONTROL BLOWER REMOVED FOR CLARITY CRV DOOR TO ACCESS CRV COMPONENTS REMOVE 9 SCREWS FROM MIS 3207 A CRV INTAKE BLOWER NOTE C...

Страница 32: ...Manual 2100 578E Page 32 of 41 FIGURE 17 ventilation airflow diagram Indoor Air VENT EXHAUST Supply Air Outdoor Air BLOWER BLOWER INTAKE VENT SUPPLY BLOWER Return Air MIS 3208...

Страница 33: ...d cleaners aromatic solvents temperatures in excess of 170 F or steam Damage to the wheel may result Do not disassemble and immerse the entire heat wheel in a soaking solution as bearing and other dam...

Страница 34: ...eplace capacitor Reversing valve does not energize heating only Heat pump control defective Check for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valv...

Страница 35: ...54529 20 46200 58 16122 96 6383 17 149355 21 44855 59 15710 97 6239 16 144374 22 43554 60 15310 98 6098 15 139576 23 42295 61 14921 99 5961 14 134956 24 41077 62 14544 100 5827 13 130506 25 39898 63 1...

Страница 36: ...trol is bypassed d If motor is not running go to next section 4 If the motor does not appear to be running at the proper speed or does not shut off refer to the next sectionforvoltagecheckstodetermine...

Страница 37: ...ermistor Temperature Resistance Chart in this manual Table 6 GREEN STATUS LED Blinks indicating there is a call for fan operation simultaneous to call for compressor operation and is normal RED STATUS...

Страница 38: ...ne if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down...

Страница 39: ...e control module is now completely detached from the motor Verify with a standard ohmmeter that the resistance from each motor lead in the motor plug just removed to the motor shell is 100K ohms Refer...

Страница 40: ...13 12 11 9 3 5 1 2 4 MIS 2839 FIGURE 21 control connector motor half Suggested mating connector Housing AMP 350809 1 Contact AMP 350537 1 WARNING Applying 240VAC line input with PIN 1 to PIN 2 jumper...

Страница 41: ...85 54 293 60 301 67 309 74 318 81 326 89 334 97 342 106 349 114 356 122 363 130 370 138 377 I60Z1 70 DB Low Side High Side 38 285 42 289 46 293 50 297 54 301 58 305 63 309 67 313 80 335 94 357 100 365...

Отзывы: