CHECKING TEMPERATURE SENSOR 

1.  Disconnect temperature sensor from board and 

from right-hand outdoor coil.

2.  Use an ohmmeter and measure the resistance of 

the sensor.  Also use ohmmeter to check for short 
or open.

3.  Check resistance reading to chart of resistance use 

sensor ambient temperature.  (Tolerance of part is 
±10%.)

4.  If sensor resistance reads very low, then sensor is 

shorted and will not allow proper operation of the 
heat pump control.

5.  If sensor is out of tolerance, shorted, open or reads 

very low ohms, it should be replaced.

TABLE 6 

Temperature (F) vs. Resistance (R) of Temperature Sensor

F

R

F

R

F

R

F

R

-25

196871

13

56985

51

19374

89

7507

-24

190099

14

55284

52

18867

90

7334

-23

183585

15

53640

53

18375

91

7165

-22

177318

16

52051

54

17989

92

7000

-21

171289

17

50514

55

17434

93

6840

-20

165487

18

49028

56

16984

94

6683

-19

159904

19

47590

57

16547

95

6531

-18

154529

20

46200

58

16122

96

6383

-17

149355

21

44855

59

15710

97

6239

-16

144374

22

43554

60

15310

98

6098

-15

139576

23

42295

61

14921

99

5961

-14

134956

24

41077

62

14544

100

5827

-13

130506

25

39898

63

14177

101

5697

-12

126219

26

38757

64

13820

102

5570

-11

122089

27

37652

65

13474

103

5446

-10

118108

28

36583

66

13137

104

5326

-9

114272

29

35548

67

12810

105

5208

-8

110575

30

34545

68

12492

106

5094

-7

107010

31

33574

69

12183

107

4982

-6

103574

32

32634

70

11883

108

4873

-5

100260

33

31723

71

11591

109

4767

-4

97064

34

30840

72

11307

110

4663

-3

93981

35

29986

73

11031

111

4562

-2

91008

36

29157

74

10762

112

4464

-1

88139

37

28355

75

10501

113

4367

0

85371

38

27577

76

10247

114

4274

1

82699

39

26823

77

10000

115

4182

2

80121

40

26092

78

9760

116

4093

3

77632

41

25383

79

9526

117

4006

4

75230

42

24696

80

9299

118

3921

5

72910

43

24030

81

9077

119

3838

6

70670

44

23384

82

8862

120

3757

7

68507

45

22758

83

8653

121

3678

8

66418

46

22150

84

8449

122

3601

9

64399

47

21561

85

8250

123

3526

10

62449

48

20989

86

8057

124

3452

11

60565

49

20435

87

7869

12

58745

50

19896

88

7686

Содержание I-TEC Series

Страница 1: ...s INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 578L Supersedes 2100 578K Date 1 31 19 I36Z1 A I36Z1 B I36Z1 C I48Z1 A I48Z1 B I48Z1 C I60Z1 A...

Страница 2: ...11 Figure 3 Compressor Shipping Bolts 12 Figure 4 Removal of Air Duct 12 Figure 5A Ducted Application 13 Figure 5B 3 Riser Application 13 Figure 5C 6 Riser Application 14 Figure 5D Required Clearance...

Страница 3: ...mmer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Conditio...

Страница 4: ...ulation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Tha...

Страница 5: ...ATMENT X Std Hydrophilic Fin Evap Uncoated Alum Cond Coil 1 Phenolic Coated ID Coil 2 Phenolic Coated OD Coil 3 Phenolic Coated ID OD Coil CONTROLS X 24V Terminal Block Only w o CompleteStat 1 Complet...

Страница 6: ...rnal Fuse or Ckt Breaker Field Power Wire Size Ground Wire Size Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B I36Z1 A0Z A05 A10 j A15 230 208 1 1 1 1 or 2 1 or 2 26 52 78 84 40 60 80 90 8 6 4 4 10 1...

Страница 7: ...l 2 2 x24 x30 Front Forklift Holes Remove Front Trim 58 16 94 Entrance High Voltage Entrance Low Voltage 20 x 24 Supply Frame Total Depth 3 8 8 7 With Sides Removed 26 2 4 4 1 2 31 1 61 Total Width 3...

Страница 8: ...ceipt of equipment the unit should be checked for external signs of shipping damage The skid must remain attached until the unit is ready for installation If damage is found the receiving party must c...

Страница 9: ...of top section and bottom base 4 On each side of the unit is a tie plate that secures the top and bottom sections with four 4 cap bolts Using a wrench or socket remove these screws from both plates an...

Страница 10: ...lter access must be considered before installing See Figure 5D for required clearances and recommended service access dimensions SECURING UNIT TO STRUCTURE Shipped with the I TEC unit is a wall mounti...

Страница 11: ...View 36 88 20 88 30 06 41 75 56 50 6 00 MIS 3197 A appropriate dimension to height Height dimension shown without 8 00 riser kit If unit uses riser kit add holes 4 lower fastener Inner wall Unit Floor...

Страница 12: ...Manual 2100 578L Page 12 of 42 FIGURE 3 Compressor Shipping Bolts FIGURE 4 Removal of Air Duct COMPRESSOR SHIPPING BOLT COMPRESSOR SHIPPING BOLT CRV AIR DUCT...

Страница 13: ...TTOM OF ROOF FLOOR OR FIXED CEILING SUSPENDED CEILING 20 MINIMUM 7 9 3 4 UNIT HEIGHT 9 7 MINIMUM CLEARANCE RECOMMENDED TO BOTTOM OF ROOF OR FIXED CEILING 9 2 MINIMUM REQUIRED INSTALLATION HEIGHT BOTTO...

Страница 14: ...EARANCE RECOMMENDED TO BOTTOM OF ROOF OR FIXED CEILING 6 RISER FIELD SUPPLIED DUCT MIS 3200 TURNING VANES RECOMMENDED MINIMUM 12 4 MINIMUM FROM TOP OF UNIT TO DUCT BOTTOM FLOOR OR FIXED CEILING BOTTOM...

Страница 15: ...12 MIN FOR LEFT SIDE ACCESS SIDE 12 MIN FOR RIGHT ACCESS WING WALL CONSTRUCTION TOP VIEW RIGHT CORNER CONSTRUCTION TOP VIEW LEFT CORNER CONSTRUCTION TOP VIEW CLOSET CONSTRUCTION TOP VIEW FILTERS RECO...

Страница 16: ...heat pumps are designed for use with free return non ducted and either duct free with the use of IPBDFZ Series Plenum Box 18 or 12 or a duct supply air system The IPBDZ Plenum Box mounts on top of th...

Страница 17: ...ht hand or left hand optional drain locations on the rear of the unit The hole is covered by insulation on the inside of the unit and will have to be cut away Located inside the unit about 12 in from...

Страница 18: ...Long Use 12 3 4 Long to Attach Inner Sleeve to Unit Back Self Tapping Screws Use 4 1 2 Long Screws to Attach frame to Exhaust Sleeve Use 12 Field Supplied Concrete or Wood Screws to Secure Outer Slee...

Страница 19: ...ed insulated 1 Outside wall 2 Area between sleeve and wall 3 Drain area behind unit SIZE VARIES OUTDOOR GRILLE INSIDE WALL AND SLEEVE INTERIOR FLOOR AREA BETWEEN WALL OUTSIDE WALL INSULATED INSULATED...

Страница 20: ...be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram will be mar...

Страница 21: ...stage electric heat When W3 terminal is energized it locks out compressor operation to limit discharge air temperature and required branch circuit ampacity NOTE For total and proper control using DDC...

Страница 22: ...el CS9B THO or Model CS9BE THO SC SC GND Thermostat W1 E A YO D L O B Y2 Y1 R G C W2 Bard 8403 060 Blue Yellow Orange 8403 084 MIS 3203 B 1 Not needed below 15KW Factory installed jumper Remove jumper...

Страница 23: ...6 1 Not needed below 15KW 2 to N C fire alarm circuit if emergency shutdown required Factory installed jumper Remove jumper and connect Install a jumper between G and A only when thermostat 2 5 Relay...

Страница 24: ...move jumper and connect 17 Connect to G terminal when thermostat has Occupancy Signal 3 3 4 CRV Wiring Harness 1 BROWN WHITE ORANGE BLACK WHITE RED WHITE 4 W3 A D C B W1 L 2 RT G Y1 3 Term Strip R 6 I...

Страница 25: ...ing multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system...

Страница 26: ...er in such a way as to cause rotation in the reverse direction verification of proper rotation must be made Verification of proper rotation direction is made by observing that suction pressure drops a...

Страница 27: ...r Heat pump heating cycle now in operation The second option has no Auto changeover position but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is plac...

Страница 28: ...SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals It may take up to 15 seconds wit...

Страница 29: ...o cooling load Thus the air conditioner is not running enough to remove the excess moisture being brought in Use a control system that in some way can control the system based upon occupancy RECOMMEND...

Страница 30: ...OFF position to eliminate risk of injury or death due to electrical shock 3 Remove six 6 screws holding front CRV door in place See Figure 16 FIGURE 15 CRV Motor Speed CFM Configuration MED HI 7961 7...

Страница 31: ...RV Speed Change Terminal Access BLOWER SPEED CONTROL LOCATION BLOWER SPEED CONTROL BLOWER REMOVED FOR CLARITY CRV DOOR TO ACCESS CRV COMPONENTS REMOVE 9 SCREWS FROM MIS 3207 A CRV INTAKE BLOWER NOTE C...

Страница 32: ...Manual 2100 578L Page 32 of 42 FIGURE 17 Ventilation Airflow Diagram Indoor Air VENT EXHAUST Supply Air Outdoor Air BLOWER BLOWER INTAKE VENT SUPPLY BLOWER Return Air MIS 3208...

Страница 33: ...d capacitor Replace capacitor Reversing valve does not energize heating only Heat pump control defective Check for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control R...

Страница 34: ...31 18 154529 20 46200 58 16122 96 6383 17 149355 21 44855 59 15710 97 6239 16 144374 22 43554 60 15310 98 6098 15 139576 23 42295 61 14921 99 5961 14 134956 24 41077 62 14544 100 5827 13 130506 25 398...

Страница 35: ...E 20 Outdoor Condensate Control FIGURE 18 Indoor Condensate Overflow Switch FIGURE 19 Outdoor Condensate Sensor happens on the same cooling call cycle a hard lockout of the compressor circuit will occ...

Страница 36: ...d or does not shut off refer to the next section for voltage checks to determine if the motor is getting the proper input signals If the motor IS NOT receiving any communication troubleshoot the commu...

Страница 37: ...tion simultaneous to call for compressor operation and is normal RED STATUS LIGHT LA Is illuminated when low ambient control switch is in the closed position NOTE This is not required in heat pump ope...

Страница 38: ...ine if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow dow...

Страница 39: ...hat the replacement control is correct for your application Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the co...