background image

Manual 2100-585C 

Page  6 of 22

INSTALLATION

        WARNING

Failure to provide the 1/4 inch clearance 

between the supply duct and a combustible 

surface for the first 3 feet of duct can result in 

fire causing damage, injury or death.

WALL MOUNTING INFORMATION

  1. Two holes for the supply and return air openings 

must be cut through the wall as shown in Figure 2.

  2. On wood frame walls, the wall construction must be 

strong and rigid enough to carry the weight of the 

unit without transmitting any unit vibration.

  3. Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 

weight of the installed unit.

MOUNTING THE UNIT

  1. These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 

both sides.  A bottom mounting bracket, attached 

to skid for shipping, is provided for ease of 

installation, but is not required.

  2. The unit itself is suitable for 0 inch clearance, 

but the supply air duct flange and the first 3 feet 

of supply air duct require a minimum of 1/4 inch 

clearance to combustible material for model series 

H36, H42, H48 and H60.  However, it is generally 

recommended that a 1-inch clearance is used for 

ease of installation and maintaining the required 

clearance to combustible material.  See Figures 

2A-C for details on opening sizes.

  3. Locate and mark lag bolt locations and bottom 

mounting bracket location.  See Figure 2.

  4. Mount bottom mounting bracket.

  5. Hook top rain flashing, attached to front - right of 

supply flange for shipping, under back bend of top.

 6.  Position unit in opening and secure with 5/16 lag 

bolts; use 7/8 inch diameter flat washers on the lag 

bolts.

  7. Secure rain flashing to wall and caulk across entire 

length of top.  See Figure 2.

  8. For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 

and screwed or welded to the structural wall itself 

(depending upon wall construction).  Be sure to 

observe required clearance if combustible wall.

  9. On side-by-side installations, maintain a minimum 

of 20 inches clearance on right side to allow access 

to control panel and heat strips, and to allow proper 

airflow to the outdoor coil.  Additional clearance 

may be required to meet local or national codes.

10. Care should be taken to ensure that the recirculation 

and obstruction of condenser discharge air does not 

occur.  Recirculation of condenser discharge air 

can be from either a single unit or multiple units.  

Any object such as shrubbery, a building or other 

large object can cause obstructions to the condenser 

discharge air. Recirculation or reduced airflow caused 

by obstructions will result in reduced capacity, 

possible unit pressure safety lockouts and reduced 

unit service life.

  For units with blow through condensers, it is 

recommended there be a minimum distance of 10' 

between the front of the unit and any barrier or 20' 

between the fronts of two opposing (facing) units.

NOTE: For side by side installation of two (2) H**A models there 

must be 20" between units.  This can be reduced to 15" by using 

a H**L model (left side compressor and controls) for the left unit 

and H**A (right side compressor and controls) for right unit.

Clearances Required for Service Access 

and Adequate Condenser Airflow

MODELS

LEFT

SIDE

RIGHT

SIDE

DISCHARGE 

SIDE

H24A, H36A

15"

20"

10'

H24L, H36L

20"

15"

10'

H42A, H48A, H60A

20"

20"

10'

H42L, H48L, H60L

20"

20"

10'

Minimum Clearances Required to

Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST THREE FEET

CABINET

H24A, H24L

0"

0"

H36A, H36L

1/4"

0"

H42A, H42L

H48A, H48L

H60A, H60L

1/4"

0"

Содержание H24A2-A

Страница 1: ...CONDITIONER Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 585C Supersedes 2100 585B Date 10 22 14 H24A2 A H36A2 A H42A2 A H48A2 A H60A2 A H24L2 A H36L2 A H42L2 A H48L2 A H60L2 A ...

Страница 2: ...ly 20 Table 7 Electric Heat 21 Table 8 Optional Accessories 21 Table 9 Vent and Control Options 22 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Condensate Drain 5 Installation 6 Wall Mounting Information 6 Mounting the Unit 6 Minimum Clearances 6 Clearances Required 6 Wiring Main Powe...

Страница 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 T...

Страница 4: ... as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct ...

Страница 5: ...t be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required with installations not requiring a return air duct The spacing between louvers on the grille shall not be larger than 5 8 inch Any grille that meets with 5 8 inch louver criteria may be used It is recommend...

Страница 6: ... flashing to wall and caulk across entire length of top See Figure 2 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side by side installations maintain a minimum of 20 inches clearance on right side to...

Страница 7: ...nting Side Wall Location Shipping Flashing Entrances Electrical Optional Entrance Electrical High Voltage Entrance Electrical Low Voltage Top Rain models non Econ vent door for Standard flush Lockable Access Panel Heat Electric Disconnect Panel Access Heater C Breaker Built In Rain Hood 4 Pitch Ventilation Air Dimensions of Basic Unit for Architectural Installation Requirements Nominal MODEL WIDTH...

Страница 8: ...OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE OPENING TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER DUCT Wall Opening and Hole Location View Right Side View SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND SUPPLY AIR SUPPLIED Return Opening Supply Opening H A UNIT SHOWN H L UNIT CONTROLS AND HEATER ACCESS IS ON OPP...

Страница 9: ... 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS DUCT RETURN AIR Right Side View SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location View Return Opening 16 7 8 4 7 16 4 5 8 9 7 8 29 7 8 17 5 8 3 11 16 5 3 8 8 3 8 28...

Страница 10: ...1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION TOP PANEL HEATER ACCESS FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL 1 4 CLEARANCE ON ALL MATERIALS Supply Openi...

Страница 11: ...his is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death NOTE 1 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES ...

Страница 12: ...AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME...

Страница 13: ...TIC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSASSHOWN FINISHEDCEILING WALL CLOSETWALL SURFACE OPENINGW GRILLE SLEEVE ORBELOWCEILINGRAFTERSASSHOWN SUPPLYAIRDUCT OUTSIDE WALLSLEEVE SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSASSHOWN FINISH...

Страница 14: ...the 24V transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are connected with brass jumper bar which can be removed and RT and R connected to external NC normally closed contact such as a fire smoke detector that will cause immediate shutdown of the equipment upon activation C terminal is grounded G terminal is the fan input Y terminal is th...

Страница 15: ...charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to insure optimal system performance Refer to instructions for the cylinder that is being utilized for...

Страница 16: ... will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired If the high pressure switch opens again in this same operating cycle the unit will ...

Страница 17: ...t charge quantity The pressure table on the following page shows nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge the unit to the seri...

Страница 18: ...73 132 501 134 529 135 558 136 586 80 67 Low Side High Side 128 348 130 375 133 402 135 429 138 457 139 485 141 514 143 543 144 572 145 601 85 72 Low Side High Side 132 360 135 388 138 416 140 444 143 473 144 502 146 532 148 562 149 592 150 622 H42A L 75 62 Low Side High Side 123 320 124 342 126 367 128 391 130 416 132 443 134 469 136 496 137 526 139 554 80 67 Low Side High Side 132 328 133 351 13...

Страница 19: ...110 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 58 58 26 52 60 60 30 60 6 6 10 6 10 10 10 10 H60A2 A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 42 42 60 86 112 60 60 60 90 125 8 8 6 3 2 10 10 10 8 6 60 60 26 52 60 60 30 60 6 6 10 6 10 10 10 10 MODEL Rated Volts Phase No Field Power Circuits Single Circuit Dual Circuit Minimum Circuit Ampacity Maximum External Fuse or Ckt Brkr Field Power Wire ...

Страница 20: ...15 1400 1365 1225 1185 1660 1610 1125 1085 TABLE 6 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Values shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter Derate ESP by 15 for 2 inch pleated filters Model H24A L H36A L H42A L H48A L H60A L Outlet FRONT FRONT TOP FRONT FRONT Speed Single High Low High Low High Low High Low A0Z A04 A05 A08 A10 A15 A20 50 50 50...

Страница 21: ...D WMCB 03A X WMCB 05A X WMCB 08A X X WMCB 09A X Left Hand Units H24L2 A H36L2 A H42L2 A H48L2 A H60L2 A Heater Kits EHWA02A A05L X EHW02A A08L X EHWA02 A10L X EHWA03 A05L X EHWA03 A10L X EHWA03 A15L X EHWA05 A05L X X X EHWA05 A10L X X X EHWA05 A15L X X X Circuit Breakers WMCB Pull Disconnects WMPD WMCB 03A X WMCB 05A X WMCB 08A X X WMCB 09A X TABLE 7 ELECTRIC HEAT Models KW 240V 1 208V 1 Amps BTUH...

Страница 22: ...DDC X X CMC 24 DDC X CMC 28 LAC X X X BOP 2 Blank Off Plate X EWM2 E EWM2 T Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X BOP 3 Blank Off Plate X EWM3 E EWM3 T Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X BOP 5 Blank Off Plate X EWM5 E EWM5 T Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X ...

Отзывы: