TROUBLESHOOTING
8301-067 Outdoor Temperature/Humidity Sensor
FIGURE 61
8301-067 Sensor Electrical Connections
8301-067 Sensor Connections
This unit utilizes a two wire 4-10mA signal from
the 8301-067 sensor to communicate outdoor
humidity and a 10KΩ Type III (AN) thermocouple
from the 8301-067 sensor to communicate outdoor
temperature. The humidity sensor is connected to
the sensor control board via the J13 connector. The
thermocouple wires are loose in the sensor housing and
require a butt splice connector or wire nut to connect to
the main unit wiring harness. See Figure 61 and Figure
62 for sensor wiring and terminal location.
FIGURE 62
8301-067 Sensor Terminal Connections
Tables 13 and 14 on pages 46 and 47 are correlation
charts for troubleshooting the sensor with a test meter:
Table 13: Temperature to Thermocouple Resistance
Table 14: Relative Humidity to Humidity Sensor Current
Output