Manual 2100-392
Page 25
TO REMOVE BURNER ONLY
Disconnect fuel line, power cord and wires from T, T
on primary control. Loosen (3) 1/4 inch nuts securing
burner mounting flange. Twist burner counterclockwise
and pull straight back away from the furnace. (See
Figure 16A.)
TO REMOVE THE ENTIRE COMBUSTION
CHAMBER MOUNTING SYSTEM
Disconnect fuel line, power cord and wires from T, T
on primary control. Remove (6) 5/16 inch bolts from
around front plate. Next remove (2) 5/16 inch nuts
from upper right and left hand corners of the front plate.
Pull entire assembly straight back away from furnace.
Be careful not to tip assembly up or down as it may
damage the combustion chamber. (See Figure 16B.)
NOTE:
PULL BURNER & CHAMBER
ASSEMBLY STRAIGHT BACK.
DO NOT ANGLE UP OR DOWN
TO PREVENT CHAMBER
DAMAGE.
FIGURE 16B
REMOVAL OF ENTIRE COMBUSTION CHAMBER MOUNTING SYSTEM
(2) 5/16 INCH NUTS
SECURING FRONT
PLATE
(6) 5/16 INCH BOLTS
SECURING FRONT PLATE
MIS-509