PUMP SQUEALS OR CHATTERS

This may be caused by air in pipes.  Check all joints in
the oil supply pipe for leaks.  Check strainer in pump; if
dirty, clean.

INSUFFICIENT HEAT

Check limit control setting.  It may be that flame is not
allowed to stay on long enough to generate sufficient
heat in furnace to heat the house properly.  If the proper
size furnace has been selected according to house
requirements and satisfactory heat is not obtained,
recheck the heating plant for size and capacity in
relation to house.  Check for clogged filters.

Check and make sure the heat anticipator on the
thermostat is set correctly.

CARE OF FINISH

This furnace cabinet is made with a very durable and
corrosion resistant finish.  With normal cleaning it will
last for many years.

CLEANING OF THE HEAT EXCHANGER

All of these units have four clean out plugs for easy
cleaning of the heat exchanger.  They are accessible
from the front and back of these units by removing the
clean out access cover in the burner compartment and at
the back of unit.  The furnace should be checked
annually by a qualified service technician.

         WARNING

Under 

no

 circumstance should a soot

deterioration device be used in the
combustion chamber.  These products known
as “soot busters” or “soot sticks” are
comprised of chemicals that burn at very high
temperatures, which may exceed the
temperature rating of the combustion
chamber material.

Use of these products are detrimental to the
life expectancy of the combustion chamber
and will destroy the chamber.  Refer to the
“Cleaning of Furnace” section for proper
cleaning methods.

COMMON CAUSES OF TROUBLE

BURNER WILL NOT PRODUCE FLAME

Check oil level gauge to see that there is sufficient oil
in tank or tanks.  Check the burner mounted relay
control.

  Do not adjust this control

.

Check position of electrodes  –  incorrect position will
cause slow or delayed ignition.  Clean electrodes and
nozzle.  Check and clean strainer in pump.  If oil line
filter is used, check filter condition.

If burner runs but there is no flame the fuel pump may
be air bound.  Follow instructions for bleeding fuel
pump.

Check and make sure the solenoid valve on the oil
pump is being energized and opening.

BURNER STARTS OR STOPS TOO OFTEN

Check heat anticipator setting on thermostat.

NOZZLE PRODUCES A STRINGY FLAME

Worn tangential grooves in nozzle.  Replace nozzle.

BASEMENT TANK HUM

Occasionally with a two-pipe installation there may be
a low return line hum.  Eliminate hum by installing a
special anti-hum valve in the return line near pump.

HEAVY FIRE OR PULSATING FLAME.

These may occur after burner starts.  It may be caused
by a slight oil leak in the fuel pump and cannot be
corrected except by replacing the pump.  This happens
only when the burner is started.

CHATTERING SOUND OR HIGH PITCH NOISE

This noise from motor can usually be traced to where a
conduit or BX cable is fixed rigidly or attached to some
part of the building.  Relieving this strain may eliminate
noise.

       CAUTION

To avoid accidents, always open main switch
(OFF position) when servicing the burner.

Содержание FC085V42A

Страница 1: ...rbon Monoxide is invisible orderless and toxic Bard Manufacturing recommends a carbon monoxide alarm in your home even if you do not own a gas appliance Locate the carbon monoxide alarm in the living...

Страница 2: ...peeds 36 Table 11 Filter Sizes for Oil Furnaces 37 FIGURES Figure 1 FLF R Models Dimensions 5 Figure 2 FH Models Dimensions 6 Figure 3 FC Models Dimensions 7 Figure 4 Typical Unit Setup FLF 10 Figure...

Страница 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Страница 4: ...oil burner must have a generous supply of combustion air to operate properly The flow of combustion and ventilating air must not be obstructed from reaching the furnace See Combustion Air Requirement...

Страница 5: ...3 2 3 2 3 2 3 2 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 t n o r F t n o r F r a...

Страница 6: ...AND FH110 SPECIFICATION SHEET 19 1 4 16 RETURN OPENING CUT OUT OPTIONAL OIL ENTRANCE OIL ENTRANCE FRESH AIR KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE OPTIONAL LOW VOLTAGE ENTRANCE FLUE KNOCKOUT RETURN O...

Страница 7: ...AGE ENTRANCE REAR FLUE KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE ENTRANCE FRESH AIR LOW VOLTAGE KNOCKOUT OIL ENTRANCE FLUE KNOCKOUT OPTIONAL OPTIONAL OIL ENTRANCE SUPPLY OPENING 19 1 8 18 1 8 BOTTOM VIE...

Страница 8: ...and external static pressure ratings to ensure proper air delivery capabilities On replacement installations particularly if equipment is oversized the duct systems can easily be undersized Modificat...

Страница 9: ...B m u m i n i M t i u c r i C y t i c a p m A e m i T x a M e s u F y a l e D R C A H r o r e k a e r B t i u c r i C P H A L F P H A L F A 2 4 V 5 8 0 C F 1 0 6 5 1 1 6 8 2 1 9 6 7 1 7 1 3 0 1 5 1 A...

Страница 10: ...ow voltage thermostat entrance Shut off switch if not fused power line must include fuse or circuit breaker To power source To thermostat and optional A C unit Air Boot knockout optional Inspection do...

Страница 11: ...flue models remove appropriate cabinet knockout Mounting screws located under flue box cover Flue Box Cover L i n e d C h i m n e y Thimble Clean out Door keep closed Oil Burner MIS 1825 Follow all a...

Страница 12: ...must comply with NFPA31 BECKETT AFG OR NX OIL BURNER This furnace is equipped with a high static Beckett AFG or Beckett NX oil burner which is designed to produce adequate draft in nearly any vertical...

Страница 13: ...additional troubleshooting features to ease service and reduce down time The operational guide for the Genisys 7505 primary control is provided following on Page 14 BECKETT SOLID STATE IGNITER This i...

Страница 14: ...rryover Once flame is established the igniter remains on for 10 additional seconds to ensure flame stability 6 Run The flame is sustained until the call for heat is satisfied The burner is then sent t...

Страница 15: ...b t e s e r e h t r e t f A e b n e h t n a c n o t t u b e h t s d n o c e s 5 1 e c n e u q e s n o i t i n g i t x e n e h t g n i r u d d e p p a t e d o m e m i r P p m u P r e t n e o t f f o t...

Страница 16: ...ished during the four minute pump prime mode return to step 5 to re enter Pump Prime mode Repeat steps 5 through 7 until the pump is fully primed and the oil is free of bubbles 9 Terminate the call fo...

Страница 17: ...going into lockout giving the service agency a prior notice before a sooting condition or other failure can occur resulting in untold savings This monitor system is available through your local distr...

Страница 18: ...CTIONS SWITCHES DELAY SELECT TRANSFORMER LINE VOLTAGE SWITCHES LINE VOLTAGE TAP SELECT TAP SELECT COOLING SPEED SWITCHES HEATING SPEED CONDITIONER OR HEAT PUMP HOT ADJUSTMENT TAP SELECT HEATING BLOWER...

Страница 19: ...B N O F F O 5 2 2 1 5 8 0 C F F O N O 0 6 0 1 A 0 6 V 0 1 1 R L F D N O N O 0 6 0 1 A 0 6 V 0 4 1 R L F 5 2 1 A F F O F F O 0 6 8 1 B N O F F O 0 9 7 1 0 1 1 C F F O N O 5 4 6 1 D N O N O 5 4 6 1 l e...

Страница 20: ...e H 0 1 C F F O N O w o l f r i A g n i t a e H 0 1 D N O N O e g n a h C o N l e d o M p a T r e t t e L 1 h c t i w S 2 h c t i w S y a l e D n O s d n o c e S y a l e D n O M F C n u R e r P e m i...

Страница 21: ...i S e v a W f l a H d e i r a V s e l i f o r P p a T y a l e D 5 n i P e g a n n o T s g n i t t e S n o p U d e s a B s l a n g i S e v a W f l a H d e i r a V s e l b a T t c e l e S p a T l o o C...

Страница 22: ...f it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Che...

Страница 23: ...to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into t...

Страница 24: ...H F G F A y o B i H 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 0 0 5 0 1 0 0 0 7 8 5 6 0 0 0 0 1 9 0 0 0 6 7 5 5 0 0 0 0 7 7 0 0 0 4 6 A 8 4 V 0 1 1 H F X N y o B i H 5 8 0 d i l o S 0 6 G I S P 0 5 1 0 0...

Страница 25: ...k Smoke Readings After burner has been operating 5 or 10 minutes take a smoke measurement in the flue following the smoke tester instructions Oily or yellow smoke spots on the filter paper are usually...

Страница 26: ...icated if the net stack temperature during steady operation exceeds 600 F N Check Ignition Check operation over repeated cycles to ensure prompt ignition on starting O Check Pump Cutoff Slow pump cuto...

Страница 27: ...adjustment range 0 2 4 6 8 8 10 12 14 6 Knee Best air setting Plotted point Plotted point Plotted point CO Curve from plotted points 2 Air Settings Low High Bacharach Smoke Number Percent CO in Flue G...

Страница 28: ...Manual 2100 540D Page 28 of 45 FIGURE 12 PRESSURE GAUGE CONNECTION TO BLEED PORT MIS 1660 Pressure Gauge Remove Bleed Port to attach pressure guage...

Страница 29: ...RT UP SETTINGS l e d o M r e b m u N e l y t S r e n r u B o N t r a P e l z z o N d n a B r i A g n i t t e S r i A r e t t u h S g n i t t e S r i A t n e m t s u j d A e t a l P g n i t t e S e z i...

Страница 30: ...te combustion of the fuel oil Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fuel oil When structures are constructed too tightly to supply s...

Страница 31: ...THIS ASSEMBLE INNER FLANGE TO UNIT FOR AIR BOOT ACCORDING TO MANUAL IN LEFT SIDE REMOVE KNOCKOUT MAKE ALL SETTINGS REMOVE PUMP TO INTAKE AIR TUBE MIS 1833 AFG BURNER COMBUSTION AIR BOOT ASSEMBLY AFG...

Страница 32: ...ll appliances shall be provided For combustion air options see Combustion Air Requirements NOTE Each opening shall have a free area of not less than one square inch per 1 000 BTU per hour 140 square i...

Страница 33: ...per hour 70 square inches per gallon per hour of total input of all appliances in the enclosure FIGURE 16 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS NOTE Each air duct opening shall h...

Страница 34: ...quare inches per gallon per hour of the total input rating of all appliances in the enclosure FIGURE 18 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPAC...

Страница 35: ...e of a corrosion resistant material having an upward pitch of 1 4 for every foot of horizontal run and be made of material capable of handling temperatures up to 1800 F A barometric damper is supplied...

Страница 36: ...0 0 0 1 0 7 C A 0 6 V 0 1 1 H F X N 5 8 0 d i l o S 0 6 G I S P 0 5 1 0 9 0 6 0 0 2 A 5 7 0 0 9 0 6 C A 2 4 V 5 8 0 F L F G F A 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 9 0 6 0 0 2 A 5 6 0 0 9 0 6 C 5 5...

Страница 37: ...e type filters and 575 fpm for washable type filters See Figure 19 The counterflow filter kit part number FR25 comes with two washable filters If not installing the FR25 kit remember not to exceed 400...

Страница 38: ...cess door The electrical switch should be turned off prior to removing the access door Refer to Figure 21 below FIGURE 21 FILTER INSTALLATION LO BOY MODELS BY PULLING OUT ON SWELL LATCHES AND TILTING...

Страница 39: ...in checking the safety switch in this primary control A Flame Failure Simulate by shutting off oil supply manual valve while burner is on Within 9 seconds the control will shut the burner down and fl...

Страница 40: ...en the burner tube and combustion chamber may be assured prior to installation into the furnace See Figures 22 and 23 WARNING The procedures described in Figures 22 23 should be conducted only by a qu...

Страница 41: ...and corners of the front plate Pull entire assembly straight back away from furnace BE CAREFUL NOT TO TIP ASSEMBLY UP OR DOWN AS IT MAY DAMAGE THE COMBUSTION CHAMBER See Figure 23 BURNER AND COMB CHAM...

Страница 42: ...products are detrimental to the life expectancy of the combustion chamber and will destroy the chamber Refer to the Cleaning of Furnace section for proper cleaning methods COMMON CAUSES OF TROUBLE BU...

Страница 43: ...ON 45 0 120 50 300 88 ON ON 60 0 0 100 180 100 BLOWER Black BLOWER BACKUP ASSEMBLY HOT 2 1 1 2 3 4 5 6 7 1 2 8 9 3 4 5 7 PLUG Black Black Black 3 PIN CONTROL 9 PIN PLUG CONTROL PANEL VOLTAGE HIGH HEAT...

Страница 44: ...UE BLACK GRAY BLACK WHITE BROWN BLACK WHITE YELLOW BLACK 6 5 4 7 1 3 8 2 9 11 10 12 14 13 15 16 BLUE PURPLE WHITE RED RED WHITE RED YELLOW PURPLE ORANGE Black C 16 PIN WIRING 3 BLACK REMOVE PURPLE JUM...

Страница 45: ...IN BLOWER 2 16 PIN BLOWER CONTROL PLUG LIMIT SWITCH GREEN LED 7 RED LED 6 CFM BLINK AND COND UNIT 24V CONNECTIONS Black FIELD CONNECTIONS TO THERMOSTAT HARNESS DETAIL BLACK YELLOW BLUE BLACK GRAY BLAC...

Отзывы: