Bard FC085V42A Скачать руководство пользователя страница 23

Manual

2100-540D

Page

23 of 45

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the unit being serviced.  

DO NOT

WORK ON THE MOTOR WITH AC POWER APPLIED.  

To avoid

electric shock from the motor’s capacitors, disconnect power and wait at
least 5 minutes before opening motor.

3. It is not necessary to remove the motor from the blower assembly, nor

the blower assembly from the unit.  Unplug the two cable connectors to the
motor control assembly.  There are latches on each connector.  

DO NOT

PULL ON THE WIRES.  

The plugs remove easily when properly

released.

4. Locate the screws that retain to the motor control bracket to the

sheet metal of the unit and remove them.  Remove two (2) nuts that
retain the control to the bracket and then remove two (2) nuts that
retain sheet metal motor control end plate.  

Refer to Figure 8.

5. Disconnect the three (3) wires interior of the motor control by

using your thumb and forefinger squeezing the latch tab and the
opposite side of the connector plug, gently pulling the connector.  

DO

NOT PULL ON THE WIRES, GRIP THE PLUG ONLY.  

Refer to

Figure 8.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K
ohms.  

Refer to Figure 9.  

(Measure to unpainted motor end plate.)  If

any motor lead fails this test, do not proceed to install the control
module.  

THE MOTOR IS DEFECTIVE AND MUST BE

REPLACED.

  Installing the new control module will cause it to fail

also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

8. Reverse the steps #5, 4, 3 to reconnect the motor control to the

motor wires, securing the motor control cover plate, mounting the
control to the bracket, and mounting the motor control bracket back
into the unit.  

MAKE SURE THE ORIENTATION YOU SELECT

FOR REPLACING THE CONTROL ASSURES THE
CONTROL'S CABLE CONNECTORS WILL BE LOCATED
DOWNWARD IN THE APPLICATION SO THAT WATER
CANNOT RUN DOWN THE CABLES AND INTO THE
CONTROL.

  DO NOT OVERTIGHTEN THE BOLTS.

9. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

10. Plug the 5-pin power connector into the motor.  Even though

the plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO

NOT FORCE THE CONNECTOR.

  It plugs in very easily when

properly oriented.  

REVERSING THIS PLUG WILL CAUSE

IMMEDIATE FAILURE OF THE CONTROL MODULE.

11. Final installation check.  Make sure the motor is installed as follows:

a. Motor connectors should be oriented between the 4 o’clock

and 8 o’clock positions when the control is positioned in its
final location and orientation.

b.Add a drip loop to the cables so that water cannot enter the

motor by draining down the cables.  

Refer to Figure 10.

The installation is now complete.  Reapply the AC power to the
HVAC equipment and verify that the new motor control module is
working properly.  Follow the manufacturer's procedures for
disposition of the old control module.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 

supplied when 
replacing an 

ECM 2.0 
control.

Figure 3

ECM 

2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Figure 9

Figure 8

Figure 10

Содержание FC085V42A

Страница 1: ...rbon Monoxide is invisible orderless and toxic Bard Manufacturing recommends a carbon monoxide alarm in your home even if you do not own a gas appliance Locate the carbon monoxide alarm in the living...

Страница 2: ...peeds 36 Table 11 Filter Sizes for Oil Furnaces 37 FIGURES Figure 1 FLF R Models Dimensions 5 Figure 2 FH Models Dimensions 6 Figure 3 FC Models Dimensions 7 Figure 4 Typical Unit Setup FLF 10 Figure...

Страница 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Страница 4: ...oil burner must have a generous supply of combustion air to operate properly The flow of combustion and ventilating air must not be obstructed from reaching the furnace See Combustion Air Requirement...

Страница 5: ...3 2 3 2 3 2 3 2 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 1 8 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 5 2 6 0 4 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 t n o r F t n o r F r a...

Страница 6: ...AND FH110 SPECIFICATION SHEET 19 1 4 16 RETURN OPENING CUT OUT OPTIONAL OIL ENTRANCE OIL ENTRANCE FRESH AIR KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE OPTIONAL LOW VOLTAGE ENTRANCE FLUE KNOCKOUT RETURN O...

Страница 7: ...AGE ENTRANCE REAR FLUE KNOCKOUT OPTIONAL HIGH VOLTAGE ENTRANCE ENTRANCE FRESH AIR LOW VOLTAGE KNOCKOUT OIL ENTRANCE FLUE KNOCKOUT OPTIONAL OPTIONAL OIL ENTRANCE SUPPLY OPENING 19 1 8 18 1 8 BOTTOM VIE...

Страница 8: ...and external static pressure ratings to ensure proper air delivery capabilities On replacement installations particularly if equipment is oversized the duct systems can easily be undersized Modificat...

Страница 9: ...B m u m i n i M t i u c r i C y t i c a p m A e m i T x a M e s u F y a l e D R C A H r o r e k a e r B t i u c r i C P H A L F P H A L F A 2 4 V 5 8 0 C F 1 0 6 5 1 1 6 8 2 1 9 6 7 1 7 1 3 0 1 5 1 A...

Страница 10: ...ow voltage thermostat entrance Shut off switch if not fused power line must include fuse or circuit breaker To power source To thermostat and optional A C unit Air Boot knockout optional Inspection do...

Страница 11: ...flue models remove appropriate cabinet knockout Mounting screws located under flue box cover Flue Box Cover L i n e d C h i m n e y Thimble Clean out Door keep closed Oil Burner MIS 1825 Follow all a...

Страница 12: ...must comply with NFPA31 BECKETT AFG OR NX OIL BURNER This furnace is equipped with a high static Beckett AFG or Beckett NX oil burner which is designed to produce adequate draft in nearly any vertical...

Страница 13: ...additional troubleshooting features to ease service and reduce down time The operational guide for the Genisys 7505 primary control is provided following on Page 14 BECKETT SOLID STATE IGNITER This i...

Страница 14: ...rryover Once flame is established the igniter remains on for 10 additional seconds to ensure flame stability 6 Run The flame is sustained until the call for heat is satisfied The burner is then sent t...

Страница 15: ...b t e s e r e h t r e t f A e b n e h t n a c n o t t u b e h t s d n o c e s 5 1 e c n e u q e s n o i t i n g i t x e n e h t g n i r u d d e p p a t e d o m e m i r P p m u P r e t n e o t f f o t...

Страница 16: ...ished during the four minute pump prime mode return to step 5 to re enter Pump Prime mode Repeat steps 5 through 7 until the pump is fully primed and the oil is free of bubbles 9 Terminate the call fo...

Страница 17: ...going into lockout giving the service agency a prior notice before a sooting condition or other failure can occur resulting in untold savings This monitor system is available through your local distr...

Страница 18: ...CTIONS SWITCHES DELAY SELECT TRANSFORMER LINE VOLTAGE SWITCHES LINE VOLTAGE TAP SELECT TAP SELECT COOLING SPEED SWITCHES HEATING SPEED CONDITIONER OR HEAT PUMP HOT ADJUSTMENT TAP SELECT HEATING BLOWER...

Страница 19: ...B N O F F O 5 2 2 1 5 8 0 C F F O N O 0 6 0 1 A 0 6 V 0 1 1 R L F D N O N O 0 6 0 1 A 0 6 V 0 4 1 R L F 5 2 1 A F F O F F O 0 6 8 1 B N O F F O 0 9 7 1 0 1 1 C F F O N O 5 4 6 1 D N O N O 5 4 6 1 l e...

Страница 20: ...e H 0 1 C F F O N O w o l f r i A g n i t a e H 0 1 D N O N O e g n a h C o N l e d o M p a T r e t t e L 1 h c t i w S 2 h c t i w S y a l e D n O s d n o c e S y a l e D n O M F C n u R e r P e m i...

Страница 21: ...i S e v a W f l a H d e i r a V s e l i f o r P p a T y a l e D 5 n i P e g a n n o T s g n i t t e S n o p U d e s a B s l a n g i S e v a W f l a H d e i r a V s e l b a T t c e l e S p a T l o o C...

Страница 22: ...f it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Che...

Страница 23: ...to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into t...

Страница 24: ...H F G F A y o B i H 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 0 0 5 0 1 0 0 0 7 8 5 6 0 0 0 0 1 9 0 0 0 6 7 5 5 0 0 0 0 7 7 0 0 0 4 6 A 8 4 V 0 1 1 H F X N y o B i H 5 8 0 d i l o S 0 6 G I S P 0 5 1 0 0...

Страница 25: ...k Smoke Readings After burner has been operating 5 or 10 minutes take a smoke measurement in the flue following the smoke tester instructions Oily or yellow smoke spots on the filter paper are usually...

Страница 26: ...icated if the net stack temperature during steady operation exceeds 600 F N Check Ignition Check operation over repeated cycles to ensure prompt ignition on starting O Check Pump Cutoff Slow pump cuto...

Страница 27: ...adjustment range 0 2 4 6 8 8 10 12 14 6 Knee Best air setting Plotted point Plotted point Plotted point CO Curve from plotted points 2 Air Settings Low High Bacharach Smoke Number Percent CO in Flue G...

Страница 28: ...Manual 2100 540D Page 28 of 45 FIGURE 12 PRESSURE GAUGE CONNECTION TO BLEED PORT MIS 1660 Pressure Gauge Remove Bleed Port to attach pressure guage...

Страница 29: ...RT UP SETTINGS l e d o M r e b m u N e l y t S r e n r u B o N t r a P e l z z o N d n a B r i A g n i t t e S r i A r e t t u h S g n i t t e S r i A t n e m t s u j d A e t a l P g n i t t e S e z i...

Страница 30: ...te combustion of the fuel oil Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fuel oil When structures are constructed too tightly to supply s...

Страница 31: ...THIS ASSEMBLE INNER FLANGE TO UNIT FOR AIR BOOT ACCORDING TO MANUAL IN LEFT SIDE REMOVE KNOCKOUT MAKE ALL SETTINGS REMOVE PUMP TO INTAKE AIR TUBE MIS 1833 AFG BURNER COMBUSTION AIR BOOT ASSEMBLY AFG...

Страница 32: ...ll appliances shall be provided For combustion air options see Combustion Air Requirements NOTE Each opening shall have a free area of not less than one square inch per 1 000 BTU per hour 140 square i...

Страница 33: ...per hour 70 square inches per gallon per hour of total input of all appliances in the enclosure FIGURE 16 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS NOTE Each air duct opening shall h...

Страница 34: ...quare inches per gallon per hour of the total input rating of all appliances in the enclosure FIGURE 18 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPAC...

Страница 35: ...e of a corrosion resistant material having an upward pitch of 1 4 for every foot of horizontal run and be made of material capable of handling temperatures up to 1800 F A barometric damper is supplied...

Страница 36: ...0 0 0 1 0 7 C A 0 6 V 0 1 1 H F X N 5 8 0 d i l o S 0 6 G I S P 0 5 1 0 9 0 6 0 0 2 A 5 7 0 0 9 0 6 C A 2 4 V 5 8 0 F L F G F A 5 7 0 w o l l o H 0 7 G I S P 0 0 1 0 9 0 6 0 0 2 A 5 6 0 0 9 0 6 C 5 5...

Страница 37: ...e type filters and 575 fpm for washable type filters See Figure 19 The counterflow filter kit part number FR25 comes with two washable filters If not installing the FR25 kit remember not to exceed 400...

Страница 38: ...cess door The electrical switch should be turned off prior to removing the access door Refer to Figure 21 below FIGURE 21 FILTER INSTALLATION LO BOY MODELS BY PULLING OUT ON SWELL LATCHES AND TILTING...

Страница 39: ...in checking the safety switch in this primary control A Flame Failure Simulate by shutting off oil supply manual valve while burner is on Within 9 seconds the control will shut the burner down and fl...

Страница 40: ...en the burner tube and combustion chamber may be assured prior to installation into the furnace See Figures 22 and 23 WARNING The procedures described in Figures 22 23 should be conducted only by a qu...

Страница 41: ...and corners of the front plate Pull entire assembly straight back away from furnace BE CAREFUL NOT TO TIP ASSEMBLY UP OR DOWN AS IT MAY DAMAGE THE COMBUSTION CHAMBER See Figure 23 BURNER AND COMB CHAM...

Страница 42: ...products are detrimental to the life expectancy of the combustion chamber and will destroy the chamber Refer to the Cleaning of Furnace section for proper cleaning methods COMMON CAUSES OF TROUBLE BU...

Страница 43: ...ON 45 0 120 50 300 88 ON ON 60 0 0 100 180 100 BLOWER Black BLOWER BACKUP ASSEMBLY HOT 2 1 1 2 3 4 5 6 7 1 2 8 9 3 4 5 7 PLUG Black Black Black 3 PIN CONTROL 9 PIN PLUG CONTROL PANEL VOLTAGE HIGH HEAT...

Страница 44: ...UE BLACK GRAY BLACK WHITE BROWN BLACK WHITE YELLOW BLACK 6 5 4 7 1 3 8 2 9 11 10 12 14 13 15 16 BLUE PURPLE WHITE RED RED WHITE RED YELLOW PURPLE ORANGE Black C 16 PIN WIRING 3 BLACK REMOVE PURPLE JUM...

Страница 45: ...IN BLOWER 2 16 PIN BLOWER CONTROL PLUG LIMIT SWITCH GREEN LED 7 RED LED 6 CFM BLINK AND COND UNIT 24V CONNECTIONS Black FIELD CONNECTIONS TO THERMOSTAT HARNESS DETAIL BLACK YELLOW BLUE BLACK GRAY BLAC...

Отзывы: