Manual 2100-292
Table 3 — Specifications (continued)
MODELS
CTHAC481-A
CTHAC481-B
CTHAC601-A
CTHAC601-B
Electrical Rating (60HZ/V/Ph)
230/208-1
230/208-3
230/208-1
230/208-3
Operating Voltage Range
197 - 253
187 - 253
197 - 253
187 - 253
Minimum Circuit Ampacity
26
17
35
21
Q
Field Wire Size
10
12
8
10
R
Delay Fuse Maximum or Circuit Breaker
45
25
60
35
Total Unit Amps 230/208
19.4/21.0
12.8/13.4
22.7/26.7
15.3/17.2
COMPRESSOR
Volts
230/208
230/208
230/208
230/208
Rated Load Amps 230/208
17.9/19.5
11.3/11.9
21.2/25.2
13.8/15.7
Branch Circuit Selection Current
19.5
12.6
26.3
15.7
Lock Rotor Amps 230/208
102/102
91/91
135/135
150/150
Crankcase Heat
Immersion Type
None
FAN MOTOR AND CONDENSER
Fan Motor — HP / RPM
1/4 - 825
Fan Motor — Amps
1.5
Fan — Diameter
24" - 2,600
SWEAT CONNECT SYSTEM
Suction Line Size ID
7/8"
7/8"
7/8"
7/8"
Liquid Line Size ID
3/8"
3/8"
3/8"
Factory Charge R-22 Oz.
155 oz.
155 oz.
153 oz.
153 oz.
SHIPPING WEIGHT — Lbs.
250
250
255
255
Q
75º C copper wire size
R
Maximum time delay fuse or HACR type circuit breaker
Table 3 — Specifications
MODELS
CTHAC181-A
CTHAC241-A
CTHAC301-A
CTHAC361-A
CTHAC421-A
Electrical Rating (60HZ/V/Ph)
230/208-1
230/208-1
230/208-1
230/208-1
230/208-1
Operating Voltage Range
197 - 253
197 - 253
197 - 253
197 - 253
197 - 253
Minimum Circuit Ampacity
15
15
19
20
25
Q
Field Wire Size
14
14
12
12
10
R
Delay Fuse Maximum or Circuit Breaker
20
20
30
30
40
Total Unit Amps 230/208
7.9/8.6
10.2/11.4
13.4/14.0
14.5/15.8
19.1/19.6
COMPRESSOR
Volts 230/208
230/208
230/208
230/208
230/208
230/208
Rated Load Amps
6.8/7.5
9.1/10.3
12.3/12.9
13.4/14.7
17.6/18.1
Branch Circuit Selection Current
8.6
10.3
13.7
14.7
18.1
Lock Rotor Amps 230/208
49/49
56/56
75/75
82/82
105/105
Crankcase Heat
None
Immersion Type
FAN MOTOR AND CONDENSER
Fan Motor — HP / RPM
1/6 - 825
1/4 - 825
Fan Motor — Amps
1.1
1.5
Fan — Diameter / CFM
20" - 2,000
24" - 2,600
SWEAT CONNECT SYSTEM
Suction Line Size ID
5/8"
3/4"
3/4"
3/4"
7/8"
Liquid Line Size ID
1/4"
3/8"
3/8"
3/8"
3/8"
Factory Charge R-22 Oz.
73 oz.
79 oz.
84 oz.
96 oz.
102 oz.
SHIPPING WEIGHT — Lbs.
155
155
180
180
250
Q
75º C copper wire size
R
Maximum time delay fuse or HACR type circuit breaker