Page 17
Manual 2100-292
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct
operation charge being in the system, the charge should be removed, system evacuated, and recharged to
serial plate instructions.
TABLE 16 – CTHAC601
Indoor Section
Return Air
Temperature
Pressure
75
80
85
90
95
100
105
110
115
FCP60
75° DB/62° WB
Low Side
68
70
72
75
77
79
82
84
86
High Side
194
211
228
246
263
280
298
315
332
80° DB/67° WB
Low Side
73
75
77
80
82
84
87
89
91
High Side
199
217
235
252
270
288
305
323
341
85° DB/72° WB
Low Side
79
81
83
86
88
90
93
95
97
High Side
207
225
243
261
279
297
315
333
351
CEVA060
75° DB/62° WB
Low Side
60
61
63
64
65
66
67
68
70
High Side
197
210
222
235
248
261
273
286
299
80° DB/67° WB
Low Side
64
65
67
68
70
72
73
75
76
High Side
202
215
228
241
254
267
280
293
306
85° DB/72° WB
Low Side
69
70
72
73
75
77
78
80
81
High Side
209
222
236
250
263
276
289
303
317