Manual 2100-684 
Page 

9 of 25

Reversing Valve Setup

1.  Press LEFT button two (2) times to return to 

ADDITIONAL SETUP.

2.  Press UP or DOWN buttons to scroll to VALVE (see 

Figure 11). 

NOTE:

 

VALVE does not show up on 

first screen

Continuing to press the UP or DOWN 

button will display VALVE.

3.  Press ENTER button to highlight choice of ACTIVE 

HTG or ACTIVE CLG. Press UP or DOWN button to 
toggle between the choices. Press ENTER button to 
save choice.

4.  Press LEFT button to return to the home screen.

DEHUMIDIFICATION

DEHUM: 

ENABLE

ALLOW HEATING DEHUM: YES

DEHUM SETPT: 60%RH

DEHUM SPAN: 5%RH

FIGURE 10

Dehumidification (Heat Pump)

ADDITIONAL SETUP

VENTILATION

FAN

HUMIDITY

MOTION SENSOR

SENSORS

STAGING

VALVE

FIGURE 11

Additional Setup (Heat Pump)

SYSTEM

SYSTEM ENABLE:

 AUTO

OCCUPANCY: SCHEDULE

OCC OVRIDE (MINS): 240

SCHEDULE

FIGURE 12

System Enable

System Enable

To enable heating or cooling from the home screen:

1.  Press RIGHT button to access the Main Menu 

screen.

2.  Press ENTER button to enter the SYSTEM menu 

(see Figure 12). 

3.  Press ENTER button to choose from available 

SYSTEM ENABLE options (use UP or DOWN 
buttons to scroll through choices):

 

•  AUTO (factory default) = System is in “Auto-

Changeover” mode. HVAC system will cycle 
heating and cooling automatically to stay 
within preset heating and cooling setpoints.

 

•  EMER HT = HP mode only.

 

•  OFF = HVAC system is inactive.

 

•  COOLING = System is in “Cooling-Only” mode. 

HVAC system will cycle cooling in reference 
to cooling setpoint only. Unit will not activate 
heating sequence.

 

•  HEATING = System is in “Heating-Only” mode. 

HVAC system will cycle heating in reference 
to heating setpoint only. Unit will not activate 
cooling sequence.

4.  Press ENTER button to save choice.

5.  Press LEFT button to return to the home screen.

Setpoints

To access setpoints from the home screen:

1.  Press RIGHT button to access the Main Menu 

screen.

2.  Press DOWN button to scroll to SETPOINTS. Press 

ENTER button (see Figure 13). Factory default 
values are shown in the figure.

SETPOINTS

COOL SETPT:

 74

°

F

COOL SETBACK: 80

°

F

HEAT SETPT: 70

°

F

HEAT SETBACK: 64

°

F

HUMIDITY

CO2 SETPT (PPM): 1200

CO2 SPAN (PPM): 200

FIGURE 13

Setpoints

3.  Press ENTER button to select COOL SETPT.

4.  Press UP or DOWN buttons to enter appropriate 

cooling setpoint. Press ENTER button to save new 
cooling setpoint.

5.  Press DOWN button to scroll to HEAT SETPT. Press 

ENTER button.

Содержание CompleteStat CS9B-THOA

Страница 1: ...ATION OPERATION QUICK START GUIDE Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 684 Supersedes NEW Date 3 20 18 CompleteStatTM Controller Models CS9B THOA CS9B THOCA CS9...

Страница 2: ...o Economizer 16 WD 2 Conventional 1H 1C or 2H 1C with Honeywell W7220 JADETM Control Economizer with or without Dehumidification 17 WD 3 Conventional 1H 2C or 2H 2C with Honeywell W7220 JADETM Control...

Страница 3: ...n the bottom and top of the controller clockwise inward until they clear the cover Remove base plate from controller INSTALLATION 3 Route control wiring through base plate 4 With the embossed UP arrow...

Страница 4: ...Setback 15 Heat Setback 16 Standby Time Minutes 17 Motion Sensing Daily Schedule 18 Date 19 Time 20 Occupied Minimum Cooling 21 Occupied Maximum Cooling 22 Unoccupied Minimum Cooling 23 Unoccupied Max...

Страница 5: ...onds factory default is 120 seconds See page 14 in the latest version of CompleteStat Controller Advanced Programming Features 2100 685 for information on adjusting the inactivity setting NOTE If the...

Страница 6: ...No economizer or standard vent package ERV CRV MFAD EN DIS Economizer in system FAN SETUP SPEEDS CONSTANT SPEED OFF DELAY SECS 0 UNOCC AUTO OCC AUTO FIGURE 5 Fan Setup Air Conditioner 3 Press ENTER b...

Страница 7: ...8 8 Press UP or DOWN button to scroll through AUX HEAT screen choices W O LOCKOUT Auxiliary heat will activate regardless of compressor operation or outdoor air temperature factory default If W O LOCK...

Страница 8: ...IONAL SETUP 7 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To access or change blower settings press DOWN button to scroll to FAN Press ENTER button to enter...

Страница 9: ...EM ENABLE options use UP or DOWN buttons to scroll through choices AUTO factory default System is in Auto Changeover mode HVAC system will cycle heating and cooling automatically to stay within preset...

Страница 10: ...The controller will not allow heating cooling setpoints to contradict one another or to be within a degree of conflicting operation NOTE Any system startup with indoor ambient temperatures lower than...

Страница 11: ...r Output 24VAC SPST Relay SC Not Used 24VAC Hot O B Reversing Valve Output 24VAC SPST Relay G Indoor Blower Output 24VAC SPST Relay IN9 Not Used ROS Remote Occupancy Sensor Input Dry Contact Input to...

Страница 12: ...tioning or through constant fan operation Operation G Y O Y1 Y2 W1 E W2 O B D A Fan Only X 1st Stage Cooling Economizer X X 2nd Stage Cooling X X X 3rd Stage Cooling if employed X X X X 1st Stage Heat...

Страница 13: ...at must be configured for a heat pump application see Auxiliary Electric Heat Setup on page 7 Operation G Y O Y1 Y2 W1 E W2 O B D A Fan Only X 1st Stage Cooling X X 1st Stage Heating X X X X2 2nd Stag...

Страница 14: ...ectric Heat Setup on page 7 Operation G Y O Y1 Y2 W1 E W2 O B D A Fan Only X 1st Stage Cooling X X X 2nd Stage Cooling X X X 3rd Stage Cooling X X X X 1st Stage Heating X X X X2 2nd Stage Heating X X...

Страница 15: ...Factory T or W Economizer w JADE W7220 Control On Off 8 Gas Electric THOA THOCA A C 1H 1C None 1 Stage A C with Gas Heat CRV ERV MFAD On Off 9 Gas Electric THOA THOCA A C 1H 2C None 2 Stage A C with G...

Страница 16: ...es and jumpers Factory installed wires and jumpers Wire for dehumidification units only 1 Remove jumper for 2 stage heat 15kW or more 3 Wire only for 2 stage cooling if available 4 W A2 units use D te...

Страница 17: ...installed wires and jumpers Factory installed wires and jumpers Wire for dehumidification units only 1 Remove jumper for 2 stage heat 15kW or more 3 CompleteStat programmed for damper economizer Enabl...

Страница 18: ...Factory installed wires and jumpers 1 Remove jumper for 2 stage heat 15kW or more 3 CompleteStat programmed for damper economizer Enable Disable 4 Field installed wire nut 1 2 3 3 4 CompleteStatTM WIR...

Страница 19: ...alled wire nut on 9 EER W A2 A1 units For W AA units consult unit installation instructions 2 Field installed wires and jumpers Factory installed wires and jumpers Wire for dehumidification units only...

Страница 20: ...wires and jumpers 1 Field installed wire nut 3 CompleteStat programmed for damper economizer Enable Disable 4 CH S Series heat pumps use DH dehumidification terminal CompleteStatTM WIRING DIAGRAM 8 G...

Страница 21: ...ump Series with No Ventilation Wire for dehumidification units only 2 Field installed wires and jumpers Factory installed wires and jumpers 1 W G Series uses A terminal for ventilation 3 Wire not used...

Страница 22: ...RAM 11 I TEC 2 Stage Heat Pump Series with CRV Ventilation Package Wire for dehumidification units only 2 Field installed wires and jumpers Factory installed wires and jumpers 1 Wire not needed if aux...

Страница 23: ...ith ERV Ventilation Package and 8403 067 CO2 Detector Fully Modulating Wire for dehumidification units only 2 Field installed wires and jumpers Factory installed wires and jumpers 1 Wire not needed if...

Страница 24: ...on Field installed wires and jumpers Factory installed wires and jumpers Q Series with factory installed thermostat had no terminal board and were wired directly from Plug 4 Use provided colors to wir...

Страница 25: ...StatTM WIRING DIAGRAM 15 QW S Series 2 Stage Heat Pump with or without Dehumidification and Ventilation WIRING DIAGRAM 16 C H Heat Pump 2 Stage with Honeywell W7220 JadeTM Control Economizer with or w...

Отзывы: