Manual 2100-684
Page
9 of 25
Reversing Valve Setup
1. Press LEFT button two (2) times to return to
ADDITIONAL SETUP.
2. Press UP or DOWN buttons to scroll to VALVE (see
Figure 11).
NOTE:
VALVE does not show up on
first screen
.
Continuing to press the UP or DOWN
button will display VALVE.
3. Press ENTER button to highlight choice of ACTIVE
HTG or ACTIVE CLG. Press UP or DOWN button to
toggle between the choices. Press ENTER button to
save choice.
4. Press LEFT button to return to the home screen.
DEHUMIDIFICATION
DEHUM:
ENABLE
ALLOW HEATING DEHUM: YES
DEHUM SETPT: 60%RH
DEHUM SPAN: 5%RH
FIGURE 10
Dehumidification (Heat Pump)
ADDITIONAL SETUP
VENTILATION
FAN
HUMIDITY
MOTION SENSOR
SENSORS
STAGING
VALVE
FIGURE 11
Additional Setup (Heat Pump)
SYSTEM
SYSTEM ENABLE:
AUTO
OCCUPANCY: SCHEDULE
OCC OVRIDE (MINS): 240
SCHEDULE
FIGURE 12
System Enable
System Enable
To enable heating or cooling from the home screen:
1. Press RIGHT button to access the Main Menu
screen.
2. Press ENTER button to enter the SYSTEM menu
(see Figure 12).
3. Press ENTER button to choose from available
SYSTEM ENABLE options (use UP or DOWN
buttons to scroll through choices):
• AUTO (factory default) = System is in “Auto-
Changeover” mode. HVAC system will cycle
heating and cooling automatically to stay
within preset heating and cooling setpoints.
• EMER HT = HP mode only.
• OFF = HVAC system is inactive.
• COOLING = System is in “Cooling-Only” mode.
HVAC system will cycle cooling in reference
to cooling setpoint only. Unit will not activate
heating sequence.
• HEATING = System is in “Heating-Only” mode.
HVAC system will cycle heating in reference
to heating setpoint only. Unit will not activate
cooling sequence.
4. Press ENTER button to save choice.
5. Press LEFT button to return to the home screen.
Setpoints
To access setpoints from the home screen:
1. Press RIGHT button to access the Main Menu
screen.
2. Press DOWN button to scroll to SETPOINTS. Press
ENTER button (see Figure 13). Factory default
values are shown in the figure.
SETPOINTS
COOL SETPT:
74
°
F
COOL SETBACK: 80
°
F
HEAT SETPT: 70
°
F
HEAT SETBACK: 64
°
F
HUMIDITY
CO2 SETPT (PPM): 1200
CO2 SPAN (PPM): 200
FIGURE 13
Setpoints
3. Press ENTER button to select COOL SETPT.
4. Press UP or DOWN buttons to enter appropriate
cooling setpoint. Press ENTER button to save new
cooling setpoint.
5. Press DOWN button to scroll to HEAT SETPT. Press
ENTER button.