Manual 2100-684
Page
3 of 25
IMPORTANT:
For optimum temperature sensor
performance, the Bard CompleteStat must be mounted
on an interior wall and away from any heat sources,
sunlight, windows, air vents, air circulation obstructions
and/or any other cause of erratic or false temperature
sensing.
Thermostat covers are not recommended as
they interfere with motion and temperature sensing.
Mounting Controller
1. It is recommended that18 AWG solid-conductor
control wire is used for installation. See the low
voltage wiring diagrams beginning on page 15 for
exact number of conductors.
NOTE:
Shielded wire must be used in applications
where transient signals may accumulate and
affect digital signal from control to unit.
2. Turn the hex screws in the bottom and top of the
controller clockwise (inward) until they clear the
cover. Remove base plate from controller.
INSTALLATION
3. Route control wiring through base plate.
4. With the embossed “UP” arrows of the base plate
pointing in the appropriate direction, fasten the
base plate to the desired wall location. A vertical/
horizontal 2x4 wall handybox can be used for the
CO
2
-sensing CompleteStat and a vertical-only 2x4
wall handybox can be used for non-CO
2
-sensing
CompleteStat.
5. Make appropriate control wire connections to
terminal blocks. See low voltage wiring diagrams
beginning on page 15.
6. Replace controller over base plate, being careful
not to pinch/dislodge connections.
7. Turn hex screws in bottom/top of controller counter-
clockwise (outward) to secure cover.
Models
Dimensions in Inches (mm)
Height
(A)
Width
(B)
Depth
CS9B(E)-THOA
5.551
(141)
4.192 (106)
1.125 (29)
CS9B(E)-THOCA
5.192 (132) 1.437 (36.5)
FIGURE 1
CompleteStat Dimensions
B
A