Manual 2100-614I
Page
14 of 43
SPECIFICATIONS FOR OPTIONAL
REMOTE COMMUNICATION BOARD
CB5000 Communication Board
NOTE:
If the communication board (Bard part number
CB5000) was not originally factory installed, it can be
field installed at anytime. It allows remote access via
Ethernet, depending upon level of authority assigned,
to all functions of the controller system the same as if
one was in the building where the controller system is
physically installed.
Required input connections to the CB5000 (these are
all internal connections from either the alarm board or
main controller board):
1. Fire/smoke connection from MC4002 main
controller board.
2. Refrigerant lockout inputs.
3. If economizers are used, an additional 24V signal
wire is required from each air conditioner to the
controller system.
4. Communication cable from CB5000 plugs into the
Ethernet connection on main MC4002 controller
board.
exists, ground the shield by moving the ground jumper
on the right side of the Ethernet port to jumper both
pins together.
1. Connect CAT 5 or CAT 6 Ethernet cable from
computer to Ethernet port on the CB5000.
2. Change the computer’s IP address as shown below
to gain initial access to the CB5000.
NOTE 1
:
Record the computer’s current IP settings
BEFORE making any changes. Reset back to these
original settings once an IP address to the CB5000 has
been assigned.
For XP or Windows 2000:
1. Open Control Panel, double click Network
Connections.
2. Double click Local Area Connection on the General
tab and select Properties.
3. Using the General tab, scroll to Internet Protocol
(TCP/IP).
4. Highlight Internet Protocol (TCP/IP) and select
Properties.
5. Change the addresses as follows:
IP
address:
192.168.1.50
Subnet mask:
255.255.255.0
Default gateway:
192.168.1.1
Preferred DNS server:
192.168.1.10
Alternate DNS server:
192.168.1.11
6. Click OK and close all windows.
7. Start the browser, enter the CB5000’s default IP
address
192.168.1.67
and hit Enter.
8. The
MC4000 log in page should appear.
For Vista, Windows 7 or Windows 10:
1. Open Control Panel, click Network & Internet.
2. Click Network & Sharing Center.
3. Click Local Area Connection or Ethernet link.
4. Click Properties.
5. Highlight Internet Protocol Version 4 (TCP/IPV4)
and select Properties.
6. Change the addresses as follows:
IP
address:
192.168.1.50
Subnet mask:
255.255.255.0
Default gateway:
192.168.1.1
Preferred DNS server:
192.168.1.10
Alternate DNS server:
192.168.1.11
7. Click OK and close all windows.
8. Start the browser, enter the CB5000’s default IP
address
192.168.1.67
and hit Enter.
9. The
MC4000 log in page should appear.
Operating System
No special software is required to access the system.
The CB5000 has a default address, simply follow these
instructions.
To Access the System
IMPORTANT:
The CB5000 is shipped with the Ethernet
shield ungrounded. Before moving jumper to ground
the shield, check for voltage between the ground on the
MC/MV and the shield of the Ethernet cable that will be
plugged into the Ethernet port on the CB5000 board.
This cable must be connected to the network before
testing for voltage. If voltage exists, do not move the
jumper as the CB5000 will be damaged. If no voltage
CB5000 Communication Board
Reset button to return to
default controller settings
Ethernet Port
IP Default
Address Reset
Phone jack connection to
main controller board
Ground Jumper