Bard 2100-737A Скачать руководство пользователя страница 22

Manual 2100-737A 

Page 

22 of 25

TABLE 3A 

Cooling Pressures

Low side pressure  ± 4 PSIG                                                         
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil.  If there is any doubt as to correct operating charge being in the system, the charge 
should be removed, system evacuated and recharged to serial plate charge weight.

NOTE:  Pressure table based on high speed condenser fan operation.  If condensing pressures appear elevated check condenser fan wiring.  See 

“Condenser Fan Operation”.

Air Temperature Entering Outdoor Coil °F

TABLE 4

Electrical Specifications

TABLE 3B

Heating Pressures (All Temperatures °F)

Model

Return Air 

Temperature

Pressure

75

80

85

90

95

100

105

110

115

120

125

T60H

75º DB

62º WB

Low Side

High Side

124
331

126
353

128
377

130
401

132
427

134
453

135
481

137
509

139
539

140
570

142
602

80º DB

67º WB

Low Side

High Side

133
340

135
363

137
387

139
412

141
438

143
465

145
493

147
523

148
553

150
585

152
617

85º DB

72º WB

Low Side

High Side

137
352

139
375

142
400

144
426

146
453

148
481

150
510

152
541

154
572

156
605

157
639

Model

Return Air 

Temperature

Pressure

0

5

10

15

20

25

30

35

40

45

50

55

60

65

T60H

70º

Low Side

High Side

36

281

41

287

47

294

53

301

60

309

66

317

73

326

81

335

88

345

96

355

104
366

113
377

122
389

131
401

Models

Rated Volts, 

HZ and 

Phase

No. of 

Field 

Power 

Circuits

Single Circuit

Multiple Circuit

Min. 

Circuit 

Ampacity 

Max. 

External 

Fuse or 

Circuit

 Breaker

Field 

Power 

Wire 

Size

Ground 

WIre 

Size

Minimum 

Circuit 

Ampacity 

Maximum 

Circuit Exterior 

Fuse or Circuit 

Breaker

Field Power 

Wire Size

Ground 

WIre Size

Ckt. 

A

Ckt. 

B

Ckt. 

C

Ckt. 

A

Ckt. 

B

Ckt. 

C

Ckt. 

A

Ckt. 

B

Ckt. 

C

Ckt. 

A

Ckt. 

B

Ckt. 

C

T60H2-A00, A0Z

-A05
-A10

-A15

-A20

230/208-60-1

1

1 or 2
1 or 2
1 or 2
1 or 3

43
69
95
95

113

60
80

100
100
125

8
4
3
3
2

10

8
8
8
6

43
43
43
43

26
52
52
52

52

50
50
50
50

30
60
60
60

60

8
8
8
8

10

6
6
6

6

10
10
10
10

10
10
10
10

10

T60H2-B00, B0Z

-B09

-B15

-B18

230/208-60-3

1
1
1
2

34
59
59

N/A

40
60
60

N/A

8
6
6

N/A

10
10
10

N/A

59

28

60

30

6

10

10

10

T60H2-C0Z

-C06

-C15

-C18

460-60-3

1
1
1
1

18
32
32
34

25
35
35
35

12
10
10

8

12
10
10
10

  

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to the National Electrical Code (latest version),  

 

Article 310 for power conductor sizing.

Caution:

  When more than one field power circuit is run through one conduit, the conductors must be derated.  Pay special attention to note 8 of Table 310 

regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.

 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.

  Based on 75°C copper wire.  All wiring must conform to the National Electrical Code and all local codes.

  Maximum KW that can operate with the heat pump on is 10KW.  Full heat available during Emergency Heat Mode.

  Maximum KW that can operate with the heat pump on is 9KW.  Full heat available during Emergency Heat Mode.

IMPORTANT: 

 While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance 

with the National Electrical Code and all local codes.

Содержание 2100-737A

Страница 1: ...nted Packaged Heat Pump Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 737A Supersedes 2100 737 Date 5 14 21 T60H2 A T60H2 B T60H2 C Page...

Страница 2: ...tions 3 Wall Mount General Information 4 Heat Pump Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions 6 W...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards...

Страница 5: ...factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installati...

Страница 6: ...lashing to wall and caulk across entire length of top See Figure 3 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the struct...

Страница 7: ...13 A Cond Air Inlet Electrical Entrances Optional Side Wall Mounting Brackets Built In Location Shipping Return Air Opening Supply Air Opening Top Rain Flashing Bottom Installation Bracket Back View...

Страница 8: ...3 4 32 12 5 1 2 2 29 OPENING 1 Return Opening IT IS RECOMMENDED THAT A BEAD OF SUPPLY AIR NOTES TOP FLASHING AT TIME OF INSTALLATION RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING...

Страница 9: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 12: ...t is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of...

Страница 13: ...he correct set points NOTE The additional LAB low ambient bypass relay is required to prevent heater operation during low temperature cooling operation OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figure...

Страница 14: ...at This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the therm...

Страница 15: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 16: ...ONITOR All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two...

Страница 17: ...emperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically If some abnormal or temporary condition such as a high wind causes the he...

Страница 18: ...as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor fr...

Страница 19: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Страница 20: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Страница 21: ...y testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this inf...

Страница 22: ...Minimum Circuit Ampacity Maximum Circuit Exterior Fuse or Circuit Breaker Field Power Wire Size Ground WIre Size Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C T60H2 A00 A0Z A...

Страница 23: ...le filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires wiring modification consult...

Страница 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Страница 25: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Отзывы: