23
UNIVERSAL-6 65
Installation instructions
3.3.1
Positioning of the
appliance
The appliance must be positioned on a concrete surface. If such a surface is not
immediately available, a suffi
ciently solid pedestal of noninfl ammable material should
be built from the creeping space
.
The appliance can be placed in position using the carrying brackets (dealer-accessorie)
supplied.
Ventilate the empty space in the chimney, by placing v
entilation openings at the top and
bottom of the chimney breast.
The total ventilation openings should be at least 450 cm
2
at the bottom of the chimney
breast and also at least 450 cm
2
at the top of the chimney breast.
(Total ventilation openings: 900 cm
2
.)
Figure 3: Use of ventilation of chimney
The ventilation openings at
the top should be at least
50 cm below the ceiling
Ventilation openings
Содержание UNIVERSAL-6 65