Put a non-flammable floor plate with a minimum thickness of 12 mm in front of the
appliance above a flammable floor. The depth of the floor plate is dependent on the
vertical distance between the bottom of the appliance and the floor.
The non-flammable floor plate must have a width that extends minimum 150 mm from
each side of the appliance.
A
Minimum 15 cm from the sides of the appliance
B
Minimum depth of the non-flammable floor plate (see graph for exact depth)
C
Minimum 180 cm clearance from the front of the appliance
Figure 11. Height of appliance versus depth of the non-flammable floor plate
1. Measure the distance between the floor and the bottom of the visible part of the
appliance. This is the distance when the appliance is built into a fireplace surround.
2. Read on the vertical axis of the graph the minimum depth of the non-flammable floor
plate.
Example to find the correct minimum depth of a non-flammable floor plate
If the measured distance between the bottom of the visible part of the appliance is 20 cm,
according to the graph the minimum depth of the floor plate is 47 cm.
Clearances
Unilux-7 75
21
Содержание Unilux-7 75
Страница 1: ...Installation and maintenance manual Unilux 7 75 Serial number Production date...
Страница 40: ...Figure 15 Dimensions of frameless appliance with steel frame door Dimensions 40 Unilux 7 75...
Страница 42: ...Figure 17 Dimensions of appliance with built in frame and metal frame door Dimensions 42 Unilux 7 75...
Страница 44: ...Figure 19 Dimensions of appliance with classic frame and metal frame door Dimensions 44 Unilux 7 75...
Страница 49: ...Warranty Terms Unilux 7 75 49...
Страница 50: ...Warranty Terms 50 Unilux 7 75...
Страница 51: ...Warranty Terms Unilux 7 75 51...
Страница 52: ...Your Barbas dealer 001 25 03 2021 351376...