The 418 MHz Receiver, 900 MHz Receiver and Analog Output Modules can be
mounted in snap track, DIN Rail or surface mounted. The text and figures refer to
the 418 MHz Receiver, but the mounting process is the same for both receivers.
SNAPTRACK MOUNTING
Push in the blue mounting tabs on the bottom of the receiver and output modules.
These units will now fit into the board slots of 2.75” snap track. Insert the receiver
at the far left of the snap track, then insert each analog output module and slide it
to the left until its connectors are fully mated into the receiver or the next analog
output module. You may attach up to 127 analog output modules to a receiver.
If your output modules cannot fit in one piece of snap track, then mount another
piece of snap track nearby and insert the additional modules. Connect wires from
the right side of the first string of modules to the left side of the second string of
modules on the second snap track. (See “Extending the RS485
Network” on pg. 5.) This configuration requires one or more
Pluggable Terminal Block Connector Kits (BA/AOM-CONN).
DIN RAIL MOUNTING
Push out the blue mounting tabs on the bottom of the
receiver and output modules. These units will now snap
onto DIN Rail. Catch the EZ mount hook on the edge of the
DIN rail as shown in Fig 9. Then rotate into place.
Attach the receiver at the far left of the DIN Rail, then attach
each analog output module and slide it to the left until its
connectors are fully mated into the receiver or the next
analog output module. You may attach up to 127 analog
output modules to a receiver.
If your output modules cannot fit onto one piece of DIN Rail,
then mount another piece nearby and attach your additional modules. Connect wires from the
right side of the first string of modules to the left side of the second string of modules on the
second DIN Rail. (See “Extending the RS485 Network...” on pg. 5.) This configuration requires
one or more Pluggable Terminal Block Connector Kits (BA/AOM-CONN).
SURFACE MOUNTING
Push out the blue mounting tabs on the bottom of the receiver and output modules. Attach the
receiver to the surface by inserting a screw in each blue tab. Attach Analog Output Modules by
placing each one against the surface and sliding it to the left until its connectors are fully mated
into the receiver or the next analog output module. Attach each module to the surface with two
screws, one in each blue tab. You may attach up to 127 analog output modules to a receiver.
If your output modules cannot fit in one straight line on the surface, then mount a second string
of modules nearby. Connect wires from the right side of the first string of modules to the left
side of the second string of modules. (See “Extending the RS485 Network...” on pg. 5.) This
configuration requires one or more Pluggable Terminal Block Connector Kits (BA/AOM-CONN).
Fig. 8:
Receiver & output modules mounted on DIN Rail.
Fig. 9:
Catch the EZ Mount
hook on the edge of
the DIN Rail, then
rotate into place.
Fig. 10:
Receiver and output
modules surface mounted.
Mounting of the 418 MHz Receiver, 900 MHz Receiver and Analog Output Modules
Fig. 7:
Receiver
and output
modules
mounted in
snaptrack.
Wireless Temperature and Humidity Transmitter Specifications
FCC Approval #:
T4F061213RSO (418MHz Room Transmitter Only)
T4F060811TEMP (418MHz Temperature Probe Only)
T4F060811RH (418MHz Temp & Humidity Probe Only)
OUR9XSTREAM (Repeater Unit Only)
Compliance:
This device complies with Part 15 of the FCC rules
Operation is subject to the following conditions.
1. This device may not cause harmful interference.
2. This device must accept any interference received, including
interference that may cause undesired operation.
FCC Radio Frequency Interference Statement:
This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15, Subpart B, of the
FCC Rules. This equipment generates, uses, and can radiate radio
frequency energy. If not installed and used in accordance with the
instructions, it may cause interference to radio communications.
Supply Power:
Two AA 3.6V Lith. batteries, 2.25 AH
5 to 8 year battery life at 10 second transmit rate
Inputs:
Temperature - Thermistor
Relative Humidity - Capacitive
Accuracy:
±0.54°F (±0.3°C) / ±2% RH
Transmitted Range:
-40 to 185°F (-40 to 85°C ) • 0-100% RH
Antenna:
Built inside the enclosure
Environmental Operation Range:
Temp: 32° to 140°F (0° to 60°C)
Humidity: 5% to 95% RH non-condensing
Enclosure Material & Rating:
ABS Plastic, UL94 V-0
Radio Frequency:
418 MHz North America
Transmitter Interval: