background image

Low Range ZPM - Zone Pressure Sensor

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

1 of 4

 Installation & Operations

38926_ins_ZPM_LR

rev. 04/09/20

Identification and Overview

Switch Setup - Outputs, Ranges, Units/Response

Fig 2:

 Setup 

Switches for 

Low Range 

Units

1. Select OUTPUT

2. Select RANGE

If unit is ordered with a Custom Range, 

then the switch must be set to R6.

3. Choose DIRECTION

Bidirectional is a plus/minus range so 

choosing 0.5” range is -0.5” to +0.5” 

Bidirectional and 0” to +0.5” Unidirectional

4. Choose UNITS - Inches WC or PASCALS

5. Choose RESPONSE TIME

Fast Response = 1/2 second

Slow Response = 4 seconds

Do not have power applied to unit when changing settings.  After changing settings, apply power and Auto-Zero 

the unit in its orientation of operation.

6. Mount, Terminate and Auto-Zero the unit 

as described in later sections. Attach 

the deadhead tubing to the ports during 

Auto-Zeroing

BAPI’s ZPM is designed for quick 

and easy field installation. The 

outputs, ranges, units, directionality, 

and response time are quickly set in 

the field with no tools, no power and 

no small components.
The optional LCD display helps with 

troubleshooting because it displays 

the actual differential pressure 

over the entire operational range 

regardless of which pressure range 

is selected for output to the system 

controller. Three LEDs on the 

face of the unit indicate when the 

pressure is “Out of Range Low”, “In 

Range” or “Out of Range High”.

Fig. 1:

 ZPM unit and 

associated parts

Bulkhead fitting 

for static tube

Static tube 

and hose 

with surge 

damper 

(for units 

ordered with 

the included 

Static Tube.)

Cover latch 

screw

Conduit 

foam plug

Static tube 

screws

Mounting 

screws

Deadhead 

tubing

Отзывы: