 Installation & Operations

38926_ins_ZPM_LR

rev. 04/09/20

Selectable Low Ranges

Inches WC

 

Pascals

0 to 0.10................................0 to 30

0 to 0.25................................0 to 50

0 to 0.50..............................0 to 100

0 to 0.75..............................0 to 175

0 to 1.00..............................0 to 250
-0.10 to 0.10 ......................-30 to 30

-0.25 to 0.25 ......................-50 to 50

-0.50 to 0.50 ..................-100 to 100

-0.75 to 0.75 ..................-175 to 175

-1.00 to 1.00 ..................-250 to 250

Power:

7 to 40 VDC 

for 4 to 20 mA Output
7 to 40 VDC or 18 to 32 VAC

for 0 to 5 or 1 to 5 V Output
13 to 40 VDC or 18 to 32 VAC

for 0 to 10 or 2 to 10 V Output

Port Size:

1/4” tubing (1/8” to 3/16” I.D.)

Specifications

Troubleshooting

POSSIBLE PROBLEMS:

LED does not light

     

LED is blinking fast

(1/2 second on, 1/2 second off)

Display is alternating between a 

number and “err”

Output stuck (high or low)

Output not tracking pressure properly

POSSIBLE SOLUTIONS:

- Check power connections for proper power

- The unit may be performing an auto-zero.  Wait 10 seconds and check again.
- Sensor is in an Error Mode. Cycle power.

- The measurement is out of selected range.

- Remove pressure from ports and perform auto-zero procedure

- Check rotary switch for proper pressure range selection
- Check rotary switch for proper output range selection

Typical Applications

NOTE:  

Best practice is to form a drip loop in the tubing to prevent condensation from reaching the ZPM.

Fig. 8:

 Duct Static Pressure Monitoring

 (ZPM Pressure Sensor mounted on the duct 

with a Static Pressure Probe in the duct.)

Fig. 9:

 Air Filter Pressure Drop Monitoring 

(ZPM Pressure Sensor mounted on the 

duct with a Static Pressure Probe on either 

side of the filter in a duct.)