BAPI’s CO

2

 room sensor comes calibrated and ready to operate.  In some 

installations the sensor may not match local instrumentation.  The technician 

adjustment procedure allows °F or °C display units, temperature or humidity 

offsets or display information to be changed at any time.

Removing Ground from Temperature Sensor

Some installations may experience erratic temperature readings.  A possible 

remedy may be to float the temperature sensor as shown in Figs 7 and 8.  Run 

wires directly from TP+ and TP- to the controller’s analog input.  The VOC/CO

2

 

and RH jumpers are omitted for clarity.

°F or °C Display Units

Figs 9 and figure 10 show the jumper positions for displayed values of Celsius 

or Fahrenheit degrees.  The jumpers on pins PRG and BNK are omitted for 

clarity.

Parameter Offsets & Display Information

Figs 11 and 12 show how to place the unit into field setup mode.  Take the 

jumper from the BNK terminals and place it on the PRG terminals.  The F/C 

jumper is omitted for clarity.
The major display should read P1 and the minor display should read DSP.
Use the UP/DN buttons (See Fig 13) to select the desired page.  
Press and release the ENT button to select the desired page.
Use the UP/DN buttons to adjust the desired value
Press and release the ENT button to save the change and return to the page 

display.
Adjust another page or place the jumper into normal operation.

Fig. 7: 

Temp. 

Sensor 

Grounded

Fig. 8: 

Temp. 

Sensor 

Floating

Fig. 9: 

°F

Fig. 10: 

°C

Fig. 11: 

Normal 

Operation

Fig. 12: 

Programming 

Setup

  

Optional Technician Adjustments

Fig. 13: 

Calibration 

Buttons

Main

Minor

Item Display

 

Action

1

Temperature Only

2

% RH Only

3

CO

2

 Only

4

Temperature and %RH (10 second rotation)

5

Temperature and CO

2

 (10 second rotation)

6

%RH and CO

2

 (10 second rotation)

7

Temperature, %RH and CO

2

 (10 second rotation)

8

Setpoint Display Only

Temperature 

Offset

P2

TMP

%RH Offset

P3

%RH

CO

2

 Offset

P4

CO2

Altitude

P5

ALT

 ±5° in 0.1° increments

 ±5% RH in 0.1% RH increments
 ±100 ppm in 1 ppm increments
 Effective Pressure Altitude (display only, no adjustment)

Table 4: Parameter Offsets & Display Information

Parameter

Display

Adjustment

Display Options

P1

DSP