background image

Installation and Operating Instructions

CO

2

 Room Sensor in the BAPI-Stat 3 Enclosure 

with Common Ground Configuration

Specifications subject to change without notice.

26141_ins_room_CO2

1 of 6

rev. 04/27/18

Fig. 1: 

BAPI-Stat 3 Room CO

2

 Sensor

The BAPI CO

2

 Sensor is an accurate and reliable way of incorporat-

ing demand controlled ventilation into a building’s HVAC strategy. It 

measures the CO

2

 in a range of 0 to 2,000 ppm with a field selectable 

output of 0 to 5 or 0 to 10 VDC.
The non-dispersive infrared (NDIR) technology has been optimized 

to reduce drift. The sensor is also altitude compensated for long-

term accuracy and stability. Changing air pressure, due to altitude 

or weather patterns, can change the output of most CO

2

 sensors by 

as much as 17%. The BAPI unit has a built-in barometric sensor that 

continuously compensates the output for accurate readings despite 

inclement weather or the altitude of the installation.
The unit can be ordered as CO

2

 alone, or with optional temperature 

sensing, temperature setpoint, occupant override and humidity sens-

ing. The large format display is easy to read and alternates between 

the measured values (CO

2

, Temperature or Humidity). The display is 

also field adjustable between °F or °C and all the displayed values 

may be turned on or off by an HVAC technician. 
Optional indication of the CO

2

 level as “Good, Fair or Poor” is avail-

able as a three-color LED on the unit or as an arrow on the display.

  Identification and Overview

 Specifications

Power for 0 to 5 VDC Outputs:

 

9 to 35 VDC @ 240mA (9 to 24 VDC recommended)

Power for 0 to 10 VDC Outputs: 

15 to 35 VDC @ 240mA (15 to 24 VDC recommended)

Sensing Elements:

CO

2

 –  Single Beam Non-Dispersive Infrared (NDIR)

 

or Dual Channel NDIR for “24/7” Model

Humidity – Capacitive Polymer ±2% RH Accuracy

Temperature Sensor:

 

Thermistor, RTD or Semiconductor

Operating Environment:

32 to 122°F (0 to 50°C)

0 to 95%, RH non-condensing

Material

 ABS Plastic, Material Rated UL94V-O

CO

2

 Detection Range:

 0 – 2000 ppm 

Start-Up Time:

 <2 Minutes

Response Time:

 

<2 Minutes for 90% step change typical (after start-up)

Mounting:

 2”x4” J-Box or drywall – screws provided

Override Output:

Contact ....SPST, 24V AC/DC, 0.5A max

Sensor .....Shorts Out direct temperature sensor

Setpoint ...Contact in parallel, resistive setpoint only

LCD Display:

Main Display: 0.76” 4-digit Numeric Values

Minor Display: 0.34” 3-digit Alpha-Numeric 

 

 (PPM, %RH, °F, °C)

Occupancy BAPI Man Icon: (Blk=Occupied)

Measurement Offsets:

 (Field Adjustable)

±5° (F or C) in 0.1° increments

±5% RH in 0.1% RH increments

CO

2

 Accuracy:

 

(Single Channel Automatic Background Calibration model)

400 to 1,250 ppm: ±30ppm or 3% of reading, 

 

 

      whichever is greater

1,250 to 2,000 ppm: ±5% of r 30ppm

CO

2

 Accuracy:

 (“24/7” Dual Channel Model)

75ppm or 10% of reading (whichever is greater)

CO

2

 Drift Stability (Dual Channel DCD “24/7” Units):

  <5% of full scale over life of product.

LED CO

2

 Level Indicator:

Good, Green < 1,000 PPM

Fair, Orange = 1,000 to 1,500 PPM

Poor, Red > 1,500 PPM 

Certifications:

 RoHS

Warranty Period:

 5 Years from manufacture date

Отзывы: