background image

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

2 of 4

Installation & Operating Instructions

rev. 08/21/17

28173_ins_CO2_Duct

CO

2

 Duct and Rough Service Sensor

 Duct Unit Mounting

1.  BAPI recommends placing the sensor in the middle of the duct wall, 

away from stratified air, to achieve the best reading. The unit should 

also be a minimum of 3 duct diameters from an elbow, damper or 

other duct restriction.

2.  Drill a 1” hole for the aspiration probe. 
3.  Position the box so that airflow is directly into the holes on one side 

of the aspiration probe.  There are no upstream or downstream holes, 

the air direction is not important.

4.  Mount the enclosure to the duct using BAPI recommended #10 

screws through a minimum of two of the mounting feet on opposite 

corners.  A 1/8’ pilot screw hole in the duct makes mounting easier.  

Use the enclosure mounting feet to mark the pilot-hole locations.

5.  Snug up the screws so that the foam backing is depressed to prevent 

air leakage but do not over-tighten or strip the screw threads. 

6.  Use the provided #6 screws to secure the cover for IP66 rating.
7.  BAPI recommends sealing the conduit opening with fiberglass 

insulation.

Fig. 5:

 Duct unit mounting

 Rough Service Unit Mounting

Mount the Rough Service sensor on a solid, non-vibrating surface.  Wall mounting in a room should be 3 to 5 feet 

above floor level.  The Rough Service CO

2

 transmitter may be mounted in any orientation.  If you are mounting 

inside a duct or mixing box, mount with the latch facing into the moving air.
Refer to local codes for further sensor/transmitter installation information.  See BAPI’s “Coverage Area” Application 

Note for further mounting recommendations.  To get to this application note, go to www.bapihvac.com, select 

“Resource Library” from the banner. Click on “Application Notes” then scroll down the page to the heading “Air 

Quality Related” and chose “Coverage Area and Mounting Recommendations for BAPI Indoor Air Quality Sensors”.

1.  BAPI recommends #10 (M5) screws of a type and length suitable for the mounting surface.  Four mounting 

screws keeps the box from twisting, 

twisting may prevent the latch from 

operating properly.  A pilot-hole 

makes mounting easier.  Use the 

enclosure mounting feet to mark the 

pilot-hole locations.

2.  Snug up the screws so that the 

foam backing is depressed but do 

not over-tighten or strip the screw 

threads.

3.  Place the provided #6 screws into 

the holes on each site of the lid 

latch to make the cover tamper 

resistant.

Fig. 3:

 Mounting the Rough Service 

sensor to a wall

Fig. 4:

 Drill Template, 

center 7/8” hole for rear 

conduit entry

Отзывы: