Installation & Operating Instructions

BAPI-Stat 4 Room Humidity Sensor (BA/

B4

-H200 Series)

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 12/15/17

Specifications subject to change without notice.

3 of 5

Fig 5:

 R34 %RH Adjustment Potentiometer

Adjustments for Units with a Display

The optional technician adjustments allows a technician to set temperature and humidity offsets, °F or °C 

display indication and which parameters are shown on the display.  When the unit is powered up, pressing 

switch SW1 will enter the user calibration adjustment mode (See Fig 4) and the LCD will show page zero, P0.  
The page numbers auto-scroll to P5 and then the unit returns to the normal run mode.  Pressing SW1 when 

any page number is displayed will show the calibration value that is associated with that page.  The variable will 

auto-scroll and will show all the allowed values for the selected page.  Pressing SW1 when the variable value 

you need is shown will record that value and return to showing page numbers.

* “When active” means when moving the setpoint slider.

** Display toggles through selections

.

Optional Technician Adjustments

Potentiometer R34 (Fig. 5) can be used to adjust the humidity output by ±5%. A high accuracy 

humidity reference is recommended.

Fig 4:

 SW1 

Calibration 

Switch

Humidity Output Selection

Fig 6:

 Humidity Output Jumpers

Moving the jumper on connector J4 will change the humidity output from 4 to 20mA, 0 to 5VDC or 0 to 10VDC. 

Fig 6 shows the jumper in the 4 to 20mA position. The 0 to 10 VDC jumper is used for the 2 to 10 VDC signal if 

an H212 or H312 was ordered.

Parameter 

Page Designator  Adjustment

Temperature Offset 

P0 

±5° in 0.1° increments. A high accuracy reference is recommended.

Humidity Offset 

P1 

±5% in 0.1% increments or R34 (When R34 is selected, humidity offset is set

 

  

by turning potentiometer R34, See Fig. 5 below.)

Display Units 

P2 

°F or °C

Display RH to Temp Toggle Time 

P3 

3 to 11 seconds

Display Resolution 

P4 

0 = 0.5 

 

 

1 = 0.1

Display Section 

P5 

0 = Temperature, Humidity and Temperature Setpoint when active*

 

 

1 = Temperature and Temperature Setpoint when active*

 

 

2 = Humidity and Temperature Setpoint when active*

 

 

3 = Temperature, Humidity and Temperature Setpoint**

 

 

4 = Temperature and Temperature Setpoint**

 

 

5 = Humidity and Temperature Setpoint**

 

 

6 = Temperature Setpoint

 

 

7 = Temperature and Humidity**

 

 

8 = Temperature

 

 

9 = Humidity

Humidity Offset Potentiometer R34

Optional Test Balance Switch (SW2)

Optional Test and Balance Switch (SW2)

NORM: Thermistor/RTD will operate normally

LOW: Will set the sensor value low

HI: Will set the sensor value high

The test and balance switch is used by the balancer to equalize the flow of air or water. It can also be used to verify sensor 

termination in a point-to-point checkout of the control system.  The “NORM” position allows the real sensor to be monitored. The 

“HI” position forces the output to a very hot reading and the “LOW” position forces the output to a very cold output (See Table 1).

 

Sensor Type 

Low Temp (40º F) Resistance  High Temp (105º F) Resistance

 

1000Ω RTD 

1.02KΩ (41.2º F) 

1.15KΩ (101.5º F)

  3000Ω Thermistor 

7.87KΩ (39.8º F) 

1.5KΩ (106.8º F)

 

10K-2 Thermistor 

30.1KΩ (34.9º F) 

4.75Ω (109.1º F)

 

10K-3 Thermistor 

26.7KΩ (35.9º F) 

5.11KΩ (108.4º F)

  10K-3(11K) Thermistor 

7.32KΩ (43.7º F) 

3.65Ω (105.2º F)

Table 1: Test and Balance Resistance Values

Содержание BA-H200 Series

Страница 1: ... by backing out the lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor ...

Страница 2: ...dependent 4 to 20 mA Output Unit Termination Terminal Function OVR1 OVR2 Override Output Dry Contact Switch If unit is a common CG model see Note below SET1 SET2 Setpoint Output If unit is a common CG model see Note below SEN1 SEN2 Sensor Output Resistive Output Semiconductor SEN1 SEN2 If unit is a common CG model see Note below EXT OVR Allows remote control of the LCD indicator for occupancy and ...

Страница 3: ... in the 4 to 20mA position The 0 to 10 VDC jumper is used for the 2 to 10 VDC signal if an H212 or H312 was ordered Parameter Page Designator Adjustment Temperature Offset P0 5 in 0 1 increments A high accuracy reference is recommended Humidity Offset P1 5 in 0 1 increments or R34 When R34 is selected humidity offset is set by turning potentiometer R34 See Fig 5 below Display Units P2 F or C Displ...

Страница 4: ...n temperature is displayed the INSIDE icon as well as the appropriate units icon are illuminated Relative Humidity When relative humidity is displayed the INSIDE icon as well as RH are illuminated Setpoint Slidepot When the temperature setpoint is active see technician adjustments moving the slidepot enough to change the setpoint by one degree will display the setpoint on display units Override Bu...

Страница 5: ...ferent from the room conduit draft Incorrect Temperature Determine that the temperature sensor s wires are connected to the correct controller input terminals and check the wires at the sensor and controller for proper connections Determine if the sensor is exposed to an external environment different from the room conduit draft Measure the physical temperature at the sensor s location using an ac...