Installation & Operating Instructions

BAPI-Stat 4 Room Humidity Sensor (BA/

B4

-H200 Series)

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 12/15/17

Terminations

BAPI recommends using twisted pair of at least 22 AWG. Larger gauge wire may be required for long runs. All wiring must 

comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as 

AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to supply highly inductive loads such as 

motors, contactors and relays. BAPI’s tests show that fluctuating and inaccurate signal levels are possible when AC power 

wiring is present in the same conduit as the signal lines.  

  Fig 3:

 Circuit Board

Notes:

On Common Ground (-CG) Models:  

On the common (-CG) models, terminals “OVR2”, “SEN2”, and “SET2” are connected 

together internally but they are not connected to Ground “GND”. If you intend to use “GND” as common, then a jumper must 

be added from terminal “GND” to “SEN2”. This is only allowed on Voltage Output models. Do not install this jumper on 4 to 20 

mA Output models.

On

 

Differential Ground (-DF) Models: 

All terminals are independent.

4 to 20 mA Output Unit Termination

Terminal 

Function

OVR1 & OVR2... Override Output – Dry Contact Switch 

 

If unit is a common (-CG) model, see Note below.

SET1 & SET2 .... Setpoint Output 

 

If unit is a common (-CG) model, see Note below. 

SEN1 & SEN2 ... Sensor Output – Resistive Output. 

 

(Semiconductor: SEN1=+, SEN2=-)

 

If unit is a common (-CG) model, see Note below. 

EXT-OVR ........... Allows remote control of the LCD indicator for 

occupancy, and is activated by logic LOW or power 

supply ground at this terminal.

VOUT ................. Not Used
V+ ...................... Power, see specifications section for details
GND ................... 4 to 20 mA Humidity Signal [to analog input of 

controller]

0 to 5 VDC, 0 to 10 VDC & 2 to 10 VDC Output Unit Termination

Terminal 

Function

OVR1 & OVR2... Override Output – Dry Contact Switch 

 

If unit is a common (-CG) model, see Note below.    

SET1 & SET2 .... Setpoint output. 

 

If unit is a common (-CG) model, see Note below. 

SEN1 & SEN2 ... Sensor Output – Resistive Output. 

 

(Semiconductor: SEN1=+, SEN2=-)

 

If unit is a common (-CG) model, see Note below.

EXT-OVR ........... Allows remote control of the LCD indicator for 

occupancy, and is activated by logic LOW or power 

supply ground at this terminal.

VOUT ................. Voltage Humidity Signal [to analog input of controller]
V+ ...................... Power, see specifications section for details
GND ................... To controller power supply ground

2 of 5

BAPI recommends wiring the product with power disconnected.  Proper supply voltage, polarity, and wiring 

connections are important to a successful installation.  Not observing these recommendations may damage the 

product and will void the warranty.

Содержание BA-H200 Series

Страница 1: ... by backing out the lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor ...

Страница 2: ...dependent 4 to 20 mA Output Unit Termination Terminal Function OVR1 OVR2 Override Output Dry Contact Switch If unit is a common CG model see Note below SET1 SET2 Setpoint Output If unit is a common CG model see Note below SEN1 SEN2 Sensor Output Resistive Output Semiconductor SEN1 SEN2 If unit is a common CG model see Note below EXT OVR Allows remote control of the LCD indicator for occupancy and ...

Страница 3: ... in the 4 to 20mA position The 0 to 10 VDC jumper is used for the 2 to 10 VDC signal if an H212 or H312 was ordered Parameter Page Designator Adjustment Temperature Offset P0 5 in 0 1 increments A high accuracy reference is recommended Humidity Offset P1 5 in 0 1 increments or R34 When R34 is selected humidity offset is set by turning potentiometer R34 See Fig 5 below Display Units P2 F or C Displ...

Страница 4: ...n temperature is displayed the INSIDE icon as well as the appropriate units icon are illuminated Relative Humidity When relative humidity is displayed the INSIDE icon as well as RH are illuminated Setpoint Slidepot When the temperature setpoint is active see technician adjustments moving the slidepot enough to change the setpoint by one degree will display the setpoint on display units Override Bu...

Страница 5: ...ferent from the room conduit draft Incorrect Temperature Determine that the temperature sensor s wires are connected to the correct controller input terminals and check the wires at the sensor and controller for proper connections Determine if the sensor is exposed to an external environment different from the room conduit draft Measure the physical temperature at the sensor s location using an ac...

Отзывы: