Standard remote control module is shown as below. Output signal
includes cw/ccw output, start/stop output, 0 - 5V voltage output.
One side of the module is DB15 plug. Another side is wiring
terminal.
Insert
the
corresponding
standard
remote
control
module into the DB15 socket which is in the rear of the pump to
get corresponding output signal. The location of the terminal is
shown as below. The terminal which hasn't signal output is open.
0-5V
5
4
3
2
1
0-5V Analog Output
1
4
3
5
2
0 - 5V Signal Output Module Wiring Diagram
External Control Module
Analog Signal Output Function
Terminal Definition of Standard External Control Module
-
1#
2#
3#
4#
5#
0- 5V analog output terminal.
Start/Stop signal output terminal. When the pump runs, the
output is high level; when the pump stops, the output is low level.
CW/CCW signal output terminal. When the pump turns
clockwise, the output is high level; when the pump turns counter
clockwise, the output is low level.
Reference potential for 0
5V analog output.
Reference potential for start/stop and cw/ccw output.
cw/ccw Signal
(5V TTL)
S t a r t / S t o p
Signal (5V TTL)
Note:
Standard external control module needs order separately.
1 7
1 8
Optional Accessory
Communication Function
Maintenance
Warranty
Footswitch
Note:
Note:
Connect to the external control interface. Control the start and
stop of the pump.
Footswitch is optional accessories. It can only control the start and
stop of the pump. The speed and direction of the pump are
controlled by the knob and switch on the operation penal.
BT300-1F can connect to the control computer (computer, PLC,
SCM) through RS485 serial communication interface.
1. The I.D. of the pump which connects to the control computer
through RS485 serial communication interface must be unique
to prevent the communication from error.
2. Please contact Longer Company for communication protocol.
When the pump is idle, we recommend you to release the tubing
from pressure. This helps to protect the tubing from unnecessary
strain and prolongs its service life
Keep rollers clean and dry. This will prolong the service lives of
tubing and pump head.
The surface of drive and the pump head are not organic solvent and
aggressive liquids resistant. Please pay attention when using.
Note
If a trouble happens, please contact us or our dealers.
The warranty period for this product is one year. If repair or
adjustment is necessary within the warranty period, the problem
will be corrected at no charge if it is not due to misuse or abuse on
your part, as determined by the manufacturer. Repair costs outside
the warranty period, or those resulting from product misuse or
abuse, may be invoiced to you.