Q45U Long-Range Ultrasonic Sensors with Bipolar Discrete Outputs

Push Button

Indicator Status

Step 1

Push and hold until green indicator turns off
(approximately 2 seconds)

Push and Hold for 

 2 Seconds

Green: Goes off
Yellow: Is on steadily to indicate ready for teaching

first limit

Red:

Flashes to indicate strength of echo or is
off if no target is present

Step 2

FIRST LIMIT

(Near or Far)

Place the target at the first limit and press the
push button for less than 2 seconds

Push for < 2 Seconds

Target at

First Limit

Green: Remains off
Yellow: Flashes at 2 Hz to indicate ready for

teaching second limit

Red:

Comes on steadily for a moment, then
resumes flashing to indicate strength of
echo

Step 3

SET SECOND LIMIT

(Far or Near)

Place the target at the second limit and press
the push button for less than 2 seconds

Push for < 2 Seconds

Target at

Second Limit

Green: Remains off, then comes on steadily

(returns to 

RUN

mode)

Yellow: On steadily for a moment, then is either on

or off to indicate output state (returns to

RUN

mode)

Red:

Comes on steadily for a moment, then
resumes flashing to indicate strength of
echo (returns to 

RUN

mode)

Notes regarding window limit programming:

1)  Either the near or far limit may be programmed, first.

2)  There is a 2-minute timeout for programming of the first limit. The sensor will return to RUN mode with the previously

programmed limits. There is no timeout between programming of the first and second limit.

3)  The programming sequence may be cancelled at any time by pressing and holding the push button for 

2 seconds. The sensor

returns to RUN mode with the previously programmed limits.

4)  During limit programming, the 5-segment moving dot indicator displays the relative target position between 0 and 4.0 m (the

maximum recommended far limit position is 3.0 m).

5)

If the target is positioned between 3.0 and 4.0 m, the 5th segment of the moving dot indicator flashes to indicate that a valid
echo is received, but the target is beyond the recommended 3.0 meter maximum far limit.

6)

If a limit is rejected during either programming step, the sensor will revert to the first limit programming step (Step 2 in
programming chart). This will be indicated by Green - off, Red - flashing to indicate signal strength, and Yellow - on steadily.

7)

If both limits are accepted, the sensor will return to RUN mode, which is indicated by the Green LED coming on steadily.

8)  If the target is held at the same position for programming of both limits, the sensor will establish a 50 mm wide sensing

window, centered on the target position.

Window Limit Programming

The “Limits” push button, located under the transparent top cover, is used to program the near and the far limits. The near limit may
be set as close as 250 mm (9.8") and the far limit may be set as far as 3.0 m (118") from the transducer face. Minimum window
width is 25 mm (1.0"). Whenever possible, use the actual target to be sensed when setting the window limits. The following
procedure begins with the sensor in RUN mode. 

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание U-GAGE Q45U

Страница 1: ...tance for a 20 C change in temperature Temperature compensated models maintain the position of both sensing window limits to within 1 of each limit distance over the range of from 0 to 50 C and to wit...

Страница 2: ...ing the two slots shown in Figure 1 a small flat blade screwdriver may be used to lift up and remove the black inner cover to expose the 4 position DIP switch Figure 2 Those switches are used to progr...

Страница 3: ...nsor in a fill level application Sensor High Level Near Limit Pump in Application switch 1 off Pump out Application switch 1 on Low Level Far Limit Initial Level 1 Initial Tank Level Outputs are INACT...

Страница 4: ...ond limit 3 The programming sequence may be cancelled at any time by pressing and holding the push button for 2 seconds The sensor returns to RUN mode with the previously programmed limits 4 During li...

Страница 5: ...echo 5 segment moving dot LED indicates the position of the target within the sensing window Hysteresis ON OFF mode 10 mm HIGH LOW mode 0 mm Performance Specifications Repeatability 0 1 of measured d...

Страница 6: ...3500 mm 40 4000 mm 60 Q45U Effective Beam with 100 mm x 100 mm Plate Target Typical Q45U Series Dimensions 79 4 mm 3 13 44 5 mm 1 75 69 0 mm 2 72 87 6 mm 3 45 30 0 mm 1 18 Internal Thread 1 2 NPSM Ext...

Страница 7: ...Shield MQDEC2 506 MQDEC2 515 MQDEC2 530 2 m 6 5 5 m 15 9 m 30 Style Model Length Connector 5 Pin Mini style with Shield MBCC2 506 MBCC2 512 MBCC2 530 2 m 6 5 4 m 12 9 m 30 7 8 16UN 2B 28 mm 1 1 61 mm...

Страница 8: ...with curved mounting slots for versatility and orientation Clearance for M6 1 4 hardware 35 1 mm 1 38 35 1 mm 1 38 69 9 mm 2 75 7 1 mm 28 x 90 2 Slots R 25 4 mm 1 00 30 1 mm 1 19 57 2 mm 2 25 25 4 mm...

Отзывы: